How-to
Which cable and software you need for FX3 PLC programming
Short answer
The FX3 family splits in two. An FX3U with the FX3U-USB-BD board fitted, or an FX3UC, programs over a straight USB A-to-Mini-B cable with the USB driver installed; an FX3G, FX3GC or FX3S has only the round 8-pin RS-422 programming port, so it needs a USB-to-RS-422 interface cable. GX Works2 is the software in every case.

On this page
Which cable you need depends on the exact CPU, not on the FX3 name, and GX Works2 is the software in every case. An FX3U with the FX3U-USB-BD expansion board fitted, or an FX3UC with its built-in USB connector, programs over a straight USB cable with a Mini-B plug at the PLC end. An FX3G, FX3GC or FX3S has no USB socket at all and programs through the round 8-pin RS-422 port, so the laptop needs a USB-to-RS-422 interface cable of the USB-SC09 type. A USB-to-RS-232 adapter is the one option that never applies, because no FX3 programming port speaks RS-232. Read the full model number off the CPU first, get the one cable that matches it, install GX Works2 with a valid license, then follow the steps below.
Read the full CPU model, not the family name #
The word FX3 on the box covers five CPU lines with two different programming connections, so the family name alone cannot pick the cable. Take the complete model number from the nameplate on the front of the CPU, including the suffix letters, before you order anything. Two things decide the connection: whether the CPU carries a USB socket, and whether the optional USB board is fitted. On an FX3U the USB route exists only when the FX3U-USB-BD expansion board is installed; the board carries a Mini-B female USB socket that its manual specifies for program transfer to the main unit and for monitoring. The FX3UC has its USB connector on the CPU itself. The FX3G, FX3GC and FX3S never offer USB, so their round 8-pin port is the only way in.
Match the CPU to its port and cable #
| CPU | Connection on the CPU | Cable from the laptop |
|---|---|---|
| FX3U | Round 8-pin RS-422 port; USB only through the FX3U-USB-BD board | USB-to-RS-422 interface cable, or a straight USB A-to-Mini-B cable into the board |
| FX3UC | USB Mini-B connector on the CPU | Straight USB A-to-Mini-B cable plus the USB driver |
| FX3G | Round 8-pin RS-422 port | USB-to-RS-422 interface cable (USB-SC09 type) |
| FX3GC | Round 8-pin RS-422 port | USB-to-RS-422 interface cable (USB-SC09 type) |
| FX3S | Round 8-pin RS-422 port | USB-to-RS-422 interface cable (USB-SC09 type) |
The interface cable for the round port is a USB-to-RS-422 assembly sold under names like USB-SC09, listed for the FX1N, FX3U and FX3G, with 2.5 m between the USB plug and the round plug. The older FX1S used the same round-port interface, and the page on getting FX1S programming software and an SC-09 cable covers that generation. The straight cable for the USB route is the ordinary USB A-to-Mini-B type sold for cameras and MP3 players: nothing about it is special, and the USB driver is what makes the link work.
Set up the connection in order #
- Power the PLC off before you plug anything in. The documented USB sequence for the FX3U-USB-BD begins with the PLC powered down, and the same order protects the round port.
- Confirm from the table which connection your exact CPU has, and that you hold the matching cable.
- Install GX Works2 with a valid license; if the laptop has none yet, the page on which PLC software you actually need to buy covers the licensing.
- USB route: with the FX3U still powered off, seat the FX3U-USB-BD in the CPU, install the USB driver from Mitsubishi Electric's download pages, connect the Mini-B male end of the cable to the board and the A plug to the laptop, then power the PLC up.
- RS-422 route: push the cable's round plug firmly into the programming port until it clips home, plug the A plug into a laptop USB socket, then install the driver the cable supplier documents.
- Open the laptop's device list and confirm the link enumerated: the board route appears through its driver, and the interface cable appears as a serial COM port.
- In GX Works2 open the project for the exact CPU and set the connection destination to match the physical link: USB for the board route, the assigned COM port for the interface cable.
- Prove the link with a read: connect online, read the CPU type or parameters, and compare what comes back with the nameplate.
Worked example: reaching an FX3G port from a laptop 1.8 m away #
Inputs, with where each comes from:
- CPU: FX3G, with the round 8-pin RS-422 programming port (the table above).
- Cable: USB-SC09 type interface cable, 2.5 m long (the length in its product listing).
- Distance from the laptop's USB socket to where the CPU sits: 1.8 m, this example's own tape-measure reading. Measure yours the same way before ordering.
Rule in words: the interface cable is a fixed-length assembly, so the measured run must not exceed the cable's length.
Arithmetic: 2.5 m − 1.8 m = 0.7 m of slack.
Result: the cable reaches with 0.7 m to spare, so the laptop sits on the bench in front of the panel.
Decision: at this distance the interface cable is the right buy. If your own measurement runs past the cable's length, the same subtraction comes out negative, and the fix is to move the laptop closer or bring the CPU to the bench; if an extension is unavoidable, add it on the laptop's USB side, never on the round-plug side.
When GX Works2 will not connect #
Work from the laptop toward the PLC, and leave PLC parameters alone until the physical link is proven.
- Nothing enumerates on the laptop: the cable, its driver or the USB socket is at fault. Try another USB socket, reinstall the interface driver, and check the device list again before anything else.
- The device enumerates but the read fails: confirm the project's PLC series and CPU match the nameplate, and that the connection destination names the same COM port or USB link the laptop actually created.
- The round plug is half seated: an 8-pin plug needs a firm push until it clips home. The USB side still enumerates, so a loose plug looks like a software fault when it is not.
- An FX3S that replaced an FX1S lost its operator screen at the same time: that is a communication fault of its own rather than a programming problem, and the write-up on resolving FX3S HMI communication failures after an FX1S swap covers it.
- Everything above checks out and the read still fails: stop, and raise it with Mitsubishi Electric through its official support channel with the full CPU model, the cable type, the driver state and what each connection attempt returned.
The decision for each CPU #
- FX3U with the FX3U-USB-BD fitted: straight USB A-to-Mini-B cable, USB driver installed, GX Works2 connected over USB.
- FX3U without the board: the same interface cable as the FX3G, through the round port; fit the board only if you want the USB route on that machine.
- FX3UC: straight USB A-to-Mini-B cable plus the USB driver.
- FX3G, FX3GC or FX3S: USB-to-RS-422 interface cable into the round port. A straight USB cable has no socket to enter.
- Every case: GX Works2 with a valid license, and the USB-to-RS-232 adapter stays in the drawer.
Questions asked
Can I program an FX3U without the FX3U-USB-BD board?
Yes. The FX3U main unit also carries the round 8-pin programming port, so the USB-to-RS-422 interface cable sold for the FX1N, FX3U and FX3G programs it with no board fitted. Fit the FX3U-USB-BD only when you want the straight-USB route on that machine, or when one laptop must serve several USB-equipped CPUs and you want one cable in the bag.
Does the USB-to-RS-422 interface cable need its own driver?
Yes. The interface is an active USB-to-RS-422 converter, and the laptop sees it as a serial port only after its driver is installed. After the install, open the PC's device list and note the COM number it assigned, because that number is what the connection destination in GX Works2 must name. Moving the cable to a different USB socket can assign a different number, so recheck it after any move.
Which project setup does GX Works2 need for an FX3?
Open a project for the FX family and pick the exact CPU, suffix included, before going online. A project created for a different PLC series or CPU will not connect to an FX3 no matter how good the cable is, and the software reports a connection failure rather than naming the mismatch. Set the connection destination to USB for the board route, or to the assigned COM port for the interface cable.
How do I prove the connection before downloading a program?
Use a read, never a write. Connect online and read the CPU type or the parameter area, then compare the result with the nameplate on the front of the CPU. Only a successful read proves the cable, driver and connection settings together. Testing a new cable by downloading is how machines lose their running program, because a download overwrites whatever the PLC held.
Could a USB-to-RS-232 adapter do the job instead?
No FX3 CPU has an RS-232 programming port, so the adapter has nothing to plug into. The round connector is RS-422, and the USB-equipped CPUs take a straight USB cable. If a USB-to-RS-232 adapter is already in the drawer, leave it there for devices with a real serial port and get the USB-to-RS-422 interface cable instead.