Which PLC software you actually need to buy

PLC programming Published 8 min read

Short answer

Buy two packages for the CompactLogix machine: the programming suite whose version covers the controller's installed firmware revision, and one HMI development package matched to the touch panel's catalog number. Drop the standalone communications package that the suite bundles in Lite form, and drop the legacy PC HMI unless an existing project needs editing. Network configuration software is only for networks the machine actually has.

On this page
  1. The two purchases that cover this machine
  2. What each quoted line item does
  3. Match the software version to the firmware revision
  4. Three facts to read before you order
  5. When network configuration software earns its place
  6. Choose the edition by the languages in your project
  7. Perpetual or subscription, and how far back the licence reaches
  8. Keep the engineering machine off the office network
  9. The decision for your machine
  10. Questions asked

Buy exactly two packages for this machine: the programming suite that covers the controller's installed firmware revision, and one HMI development package matched to the touch panel's catalog number. Everything else on a four-line quote like the one you are holding is either bundled with the programming suite or belongs to a retired platform. This article names what each quoted line item does, shows how the firmware revision sets the software version you must buy, and ends with a buy-or-drop decision for every line on the quote.

The two purchases that cover this machine #

Studio 5000 Logix Designer, the package renamed from RSLogix 5000 during its version history, is the only software that opens and edits a CompactLogix project. If you will change controller logic, I/O configuration or tags, the programming suite line on the quote is mandatory. That exclusivity is not particular to your controller; it is the same rule behind why only Studio 5000 programs a ControlLogix 5571.

The second purchase is the HMI development package, and which package that is depends on the terminal's catalog number, not on preference. For a PanelView Plus class terminal it is FactoryTalk View Studio for Machine Edition, line 3 on the quote. Read the catalog number before you commit, because two other PanelView families take different packages, as the section below shows.

What each quoted line item does #

Quoted line What it is Buy it when
Studio 5000 Pro Edition The programming environment for CompactLogix and ControlLogix controllers, formerly RSLogix 5000. The Professional edition adds Structured Text and Function Block development. Always, if you will change controller logic, I/O configuration or tags.
RSLinx Classic Gateway The full RSLinx Classic communications package, with gateway features and extra driver capability. Only when another application on the PC needs more than the bundled Lite edition provides.
FactoryTalk View Studio for ME Development software for PanelView Plus class terminals: screen design and tag linking to the controller. The terminal's catalog number is a PanelView Plus or similar Machine Edition runtime.
RSView32 Works 150 tag The retired PC-based supervisory package, superseded by FactoryTalk View. Only to edit or keep alive an existing RSView32 application.
RSNetWorx (not on the quote) Network configuration for DeviceNet, with separate variants for ControlNet. The machine actually has DeviceNet or ControlNet nodes.

Studio 5000 bundles RSLinx Classic Lite, and the Lite edition browses the Ethernet network and goes online with the controller. Everything you described as "connect to the PLC" is covered by what already ships inside line 2. Line 1 earns its price only when another application on the same PC needs to share the connection or forward it to other stations, which a small single-machine setup does not.

Line 4 is the one to question hardest. RSView32 is the retired PC-based supervisory package; FactoryTalk View replaced it. A surplus SCADA PC tells you nothing about which package built whatever runs on it, so owning the PC is not a reason to own RSView32. Open the installed program list and search the PC for RSView32 project files: no project, no purchase. If the machine later needs control-room graphics, alarms and database logging on a PC, that is a separate decision about selecting SCADA software for mixed PLCs and SQL logging, not a line on this quote.

Match the software version to the firmware revision #

The software version must be compatible with the controller's installed firmware revision, and this is where most wasted purchases happen. Rockwell publishes the pairing. As a documented example, the compatibility table for a CompactLogix 5370 L3 controller at firmware revision 35.011 lists the minimum compatible software as Studio 5000 Logix Designer 35.00.00. Compare the numbers: the revision's 35.011 sits at or above the package's 35.000, so a v35.00.00 seat goes online with that controller, while a v32.000 seat does not, because 32 is below 35.

Older hardware shows the same rule from the other side. A 1769-L32E series A controller runs firmware anywhere from 13.034 to 20.019. A licence that installs version 31 and later carries nothing for that controller: 31.000 sits above the 20.019 ceiling, so no package it reaches can go online with the machine. For hardware like that you either obtain a licence that installs a version inside the range or you reflash the controller to a revision the licence covers.

A firmware flash takes the controller out of service until it completes. Run it in a scheduled outage with a verified project backup, never on a live machine.

Three facts to read before you order #

  1. The controller's firmware revision. Read it from the module properties in the programming software or from the browse window in the communications software. The label on the module is only valid if the unit has never been flashed. This number sets the minimum software version from the example above.
  2. The touch panel's catalog number. Read the label on the back of the panel. A PanelView Plus terminal takes FactoryTalk View Studio for Machine Edition. A PanelView 800 terminal is programmed in Connected Components Workbench, a separate package. A PanelView 5000 terminal is developed inside Studio 5000 itself, and the Professional edition includes that capability. There is no one package that programs every HMI panel family, so confirm the catalog number before buying the HMI line, because an 800 or 5000 on the machine makes FactoryTalk View ME redundant.
  3. What the SCADA PC actually runs. Its installed programs and project files decide the RSView32 line. If the search finds no RSView32 project, that line is dropped and the decision is closed.

While you are at the panel, read the catalog number on the 1734 adapter too, because it settles the network question in the next section.

When network configuration software earns its place #

RSNetWorx for DeviceNet configures DeviceNet networks, and the ControlNet variants configure ControlNet. Your 1734 Point I/O is reached over the Ethernet network through its adapter, so the adapter's catalog number decides. An EtherNet/IP adapter means no DeviceNet nodes exist on this machine, and RSNetWorx has no job here. A DeviceNet adapter would put it back on the list. The general decision is the same for any network configuration tool: it is bought for a protocol the machine actually uses, never as a just-in-case purchase.

Choose the edition by the languages in your project #

Open the running project, or an upload from the controller, and look at the routine types. Ladder only, and you intend to keep it that way: a Lite edition seat covers the CompactLogix family, so confirm with the distributor that it supports your exact controller and buy the lower edition. Any Structured Text or Function Block routine in the project, or plans to write them: a Lite seat cannot edit those languages, so buy Professional. A PanelView 5000 terminal on the machine also means Professional, since that terminal's development is included there. Make this check before the seat arrives, because the running project, not the catalogue, is the specification.

Perpetual or subscription, and how far back the licence reaches #

Two decisions remain: licence term and version range. A subscription seat runs for a term, commonly annual, and gives access to download any released version, which removes the version-range problem in one move: whatever firmware revision you meet next, the matching package is included. A perpetual seat covers versions up to the release current at purchase; a newer release then needs a further purchase or a support contract. If you will maintain the software on this machine for years, subscription. If it is one planned change and the system then stays untouched, perpetual, or a contractor visit, which can beat owning a seat outright for a one-off system.

Ask the distributor, in writing, for the lowest version the licence will install. If that floor sits above your controller's firmware revision, you cannot go online with the machine until you close the gap, and that discovery belongs in the quote stage, not the outage.

Keep the engineering machine off the office network #

Studio 5000 versions install side by side, but sites that maintain several get into trouble when activations, drivers and operating systems mix. Put the programming software on a dedicated machine that stays off the office network, keep one virtual machine per version family, and control who has its login. If that machine should live at the cabinet rather than in an office, an industrial panel PC is built for the job: cabinet-door or console mounting, running the programming seat and HMI development side by side.

The decision for your machine #

  • Controller logic: buy Studio 5000 in an edition that covers the languages in your project, in a version whose range includes the installed firmware revision. For a 5370 L3 at revision 35.011, that means at least v35.00.00.
  • Line 1, RSLinx Classic Gateway: drop it. The Lite edition bundled with Studio 5000 browses the network and goes online.
  • Line 3, FactoryTalk View Studio for ME: buy it if the panel's catalog number is a PanelView Plus. A PanelView 800 takes Connected Components Workbench and a PanelView 5000 is developed inside Studio 5000, so either of those makes the line redundant.
  • Line 4, RSView32 Works: drop it unless the SCADA PC holds an existing RSView32 project you must edit.
  • RSNetWorx: drop it. The I/O adapter is EtherNet/IP, so there is no DeviceNet to configure.
  • If the touch panel is the only operator interface you need, no supervisory package is required at all; the same reasoning applies as in whether a Modbus HMI project needs SCADA software.

The quote shrinks from four lines to two, and both remaining purchases are decided by two labels you can read off the machine today: the controller's firmware revision and the touch panel's catalog number.

Questions asked

What does ESD mean on a software line item?

Electronic software delivery: the licence arrives as a download and an activation rather than on physical media. It describes how the product is delivered, not what the product does, so it does not change whether the line belongs on your order. Judge each line by its product name and edition, not by the ESD tag.

Can a third-party HMI or SCADA package replace FactoryTalk View Studio?

Yes, if you are not editing an existing PanelView Plus application. Any HMI or SCADA package with an EtherNet/IP driver for Logix controllers can read and write controller tags over the Ethernet network, and the controller needs no extra configuration for that. FactoryTalk View Studio is still the only tool that opens the existing PanelView Plus project, so switching packages means rebuilding the screens from scratch in the new one.

Do the 1783 Ethernet switches need their own software?

No separate purchase. An unmanaged switch needs no configuration at all. A managed switch is configured through its own web-based device manager from a browser on the PC you already have: give the switch an address on the machine network, connect, and work from there. The switches on your 1783 line do not add a line item to the order.

Can several Studio 5000 versions share one PC?

Yes. The installer places versions side by side, and each project opens in the version it was written for. In practice shops keep one virtual machine per version family, so an old project's activation and operating system never collide with a newer one. Decide this before the first install, because moving a licensed activation later means deactivating it on the old machine before it will run on the new one.

Keep reading

  • Selection guide

    Selecting SCADA software for mixed PLCs and SQL logging

    Shortlist the candidates, then pass or fail each one on nine commissioned paths: a live read from every PLC family in the mix, one parsed serial ASCII transaction, a browser client session on the target touch-panel PC, and one logged record in SQL Server or MySQL verified across a database outage. Accept a package only when every path passes all its checks; a failed path keeps a candidate alive only with a named gateway or OPC route.

    SCADA and data logging

  • Selection guide

    How to choose an S7 PLC family for a machine

    For a new machine, pick the S7-1200 when the job is standalone control with modest I/O and one or two axes, and the S7-1500 when you need coordinated motion, controller-integrated safety, a fast scan or a large I/O count. Use S7-300 and S7-400 only to extend plants that already run them. Program both current families in TIA Portal.

    PLC programming

  • Selection guide

    Migrating a MicroLogix 1500 machine to a current PLC

    Quote CompactLogix as the baseline for the rebuild: Rockwell's migration reference gives the MicroLogix 1500 two documented destinations, MicroLogix 1400 or CompactLogix 5370 (L1/L2), and a low-volume machine rebuild does not justify the Micro850 route. Take the Micro850 only for high build volume, after the 11 uncovered inputs, serial Modbus, the drive interface and a trial CCW import are verified.

    PLC programming