PLC programming Published 6 min read

Short answer

Order GX Developer under code GX-DEV-C1 with its paid license, and a genuine USB-SC09-FX cable (SC-09 if the PC has a serial port), through Mitsubishi Electric or an authorized distributor. Connect read-only, upload the existing FX1S program before any teaching use, and send PC commands to data registers the ladder reads, never to X input terminals, which cannot be written.

On this page
  1. What to order for an FX1S
  2. Buy it through official channels
  3. First connection, read-only
  4. Where the PC interface writes
  5. What runs the classroom interface
  6. If it will not connect
  7. Questions asked

For an FX1S-14MR you need two purchases, both through Mitsubishi Electric or an authorized distributor: GX Developer with its paid license — order code GX-DEV-C1 — and a genuine programming cable, USB-SC09-FX for a laptop without a serial port, SC-09 for a PC with a real COM port. Since February 2024 GX Developer is sold separately from the GX Works2 and GX Works3 packages, so it is its own line on the order. Connect read-only first, upload the existing program before any classroom use, and write PC commands to data registers the ladder reads — never to the X input terminals, which cannot be written.

What to order for an FX1S #

GX Developer is the package that programs this generation: Mitsubishi's software lineup lists it for Q, L, FX and legacy MELSEC controllers, with ladder as the language you will use. The newer GX Works2 was built to carry GX Developer's program assets forward for more recent controllers; the FX1S sits in the legacy group GX Developer covers, and since February 2024 GX Developer is a separate purchase in any case. Matching the package to the CPU generation is half the order — the same discipline as getting the right Micro/WIN version for an S7-200 CPU 224 on the Siemens side.

The FX1S programming port is RS-422, and the conversion to what your PC has lives in the cable:

PC side Order What the cable does
RS-232 COM port SC-09 converts RS-232 to RS-422 inside the cable
USB port only USB-SC09-FX converts USB to RS-422; the PC gains a serial port once the cable's driver is installed

Decision: USB-SC09-FX for every current laptop; SC-09 only if the teaching PC still has a serial port. Mitsubishi's FX communication manual for RS-232C, RS-485 and RS-422 documents the port and the protocol behavior; take it from Mitsubishi's documentation pages when you order.

Buy it through official channels #

GX Developer is paid, actively sold software; a licensed copy is the only copy. Refuse software that arrives by email or file share, whatever the sender calls it — unlicensed is unlicensed, and a licensed purchase is also what gets you the version and driver support you will want when an operating-system update changes how the USB cable enumerates. Ask the distributor to confirm in writing that the package supports the FX1S and your PC's operating system. Put the cable on the same purchase order, by its documented name rather than by connector appearance, because a plug that fits proves nothing about signal levels, pin assignment or driver. Legacy does not mean free on any vendor's shelf; it is the same position as getting RSLogix 500 through official channels for an SLC 500.

First connection, read-only #

Work in this order the first time you touch the rig:

  1. Isolate the loads: disconnect the pool valve and the curtain drive so no connection test and no accidental write can move anything — lamps are harmless, actuators are not.
  2. Photograph the nameplate and the programming connector. "FX1S-14MR", complete, is what goes into the order confirmation and the software's PLC-type selection.
  3. Install GX Developer from your licensed media. If you use USB-SC09-FX, install its driver and confirm the operating system lists the cable without warnings; a recognized adapter proves only that the PC sees the cable.
  4. In the connection setup, choose the COM number the operating system assigned to the cable and set the PLC type to the FX1S.
  5. Connect and read the controller identification; it should report an FX1S. Record any error message exactly instead of reinterpreting it as a cable fault.
  6. Upload the program and parameters and save the project under a dated name. Comments live in the original project file, not in the controller, so an upload returns the logic without them.
  7. Prove the path: monitor an X bit while someone presses a real input, or watch a timer's current value count.
  8. Download changes only after the step 6 file is saved, and only with the loads still isolated until the edited logic is verified.

Where the PC interface writes #

A classroom plan that sends commands "to the PLC inputs" needs one redesign. X devices are the electrical state of the input terminals: the ladder reads them, and nothing writes them through a communication port. The PC writes a device the logic consumes — a data register such as D100, or an M internal relay — and the program decides what happens next:

PC write → D100 command word → permission and interlock logic → Y outputs → status read back to the PC.

Device letters label fixed memory areas across the MELSEC range, and they keep the same jobs in the larger CPUs, as in how Q series PLC addressing works for I/O and analog modules. The FX1S manual carries this model's register map; D100 and the M range are ordinary writable devices on it.

A worked command word #

Give each bit of D100 one meaning:

  • bit 0, weight 1 — lamp on request
  • bit 1, weight 2 — pool fill request
  • bit 2, weight 4 — curtains open request
  • bit 3, weight 8 — curtains close request

Lesson call: lamps on, curtains open, pool idle. The interface writes 1 + 4 = 5 to D100 — binary 0101, so bits 0 and 2 are set and bit 1 is clear.

The rungs that consume it:

  • X000, a key switch on the rig acting as the permission, in series with D100 bit 0 drives Y000, the lamp output.
  • X000 in series with D100 bit 2, and not D100 bit 3, drives Y002, curtains open.
  • X000 in series with D100 bit 3, and not D100 bit 2, drives Y003, curtains close.

Now the arithmetic that protects the rig. A student writes 13: lamp plus open plus close is 1 + 4 + 8 = 13, binary 1101, with bits 0, 2 and 3 all set. Both curtain rungs go false — each requires the opposite bit to be clear — so neither curtain output moves while the lamp still lights. Decision: the interface writes 5 for that lesson, and the PLC rejects the contradictory 13 by construction rather than by trusting the operator. Keep one-shot actions in separate pulsed M bits so a maintained command word cannot retrigger a counter on every scan.

What runs the classroom interface #

Two choices close the design. The interface can be custom code speaking the documented FX communication protocol, or a SCADA package — and in a SCADA package the write still has to come from a client the system treats as authorized, the rule behind why a tag write requires an authorized writable client. The computer can be the teaching laptop, or an industrial panel PC mounted on the rig so the class has a station that is always there and the controller wiring stays behind the panel.

If it will not connect #

Symptom Layer at fault First move
No serial device appears for the USB cable Driver Install the USB-SC09-FX driver; an unrecognized cable is a PC problem, not a PLC problem
Cable enumerated, GX Developer will not connect Connection setup COM number and PLC type in the transfer settings
Connection opens, writes do nothing Device choice You are writing an X; move the write to D or M
Command accepted, output stays off Program logic Permission input and interlock contacts, in that order

None of these four rows is a failed FX1S, and none is fixed by ordering different hardware. Work the table top to bottom before spending anything else.

Questions asked

Will GX Works2 or GX Works3 program the FX1S?

No. The FX1S generation is a GX Developer job: Mitsubishi lists GX Developer for Q, L, FX and legacy controllers, and the FX1S sits firmly in the legacy group. Since February 2024 GX Developer is purchased separately from the GX Works2 and GX Works3 packages anyway, so ordering the newer tool gains you nothing here. Ask for order code GX-DEV-C1.

A colleague offered to send me the software by email. Should I accept?

No. GX Developer is licensed paid software, and a copy passed between users is unlicensed however it arrives. Order through Mitsubishi Electric or an authorized distributor so you also get the correct version and driver support. The same goes for program files: the legitimate copy of your FX1S project is the one you upload from the controller yourself.

Can the PC interface switch the PLC inputs directly?

No. X devices are the electrical state of the input terminals; they are read-only over communication. The PC writes a data register such as D100 or an M internal relay, the ladder applies permissions and interlocks, and only then does a Y output switch. Inputs still belong to wires.

Which cable do I need, SC-09 or USB-SC09-FX?

USB-SC09-FX for any laptop without a serial port: the RS-422 conversion is inside the cable, and the PC sees a serial port once the driver is installed. SC-09 only fits a PC with a real RS-232 COM port. Both exist because the FX1S programming port itself is RS-422.

Will the upload bring back the program comments?

Not usually. Comments and rung notes live in the project file on the engineering PC, not in controller memory, so an upload returns the logic and device values only. Save the uploaded project under a dated name and treat it as the machine's only program backup until the comments are re-entered.

Keep reading

  • Troubleshooting

    Why only Studio 5000 programs a ControlLogix 5571

    A ControlLogix 5571 is programmed only with Studio 5000 Logix Designer (RSLogix 5000 in older releases) over an RSLinx or FactoryTalk Linx driver path. The USB port feeds that driver, not a terminal: PuTTY, minicom or picocom never reach a prompt on this VxWorks-based runtime. A controller missing from a device list means you check installed Studio 5000 revisions and the communications path first, and you flash firmware only to match an installed release's major revision — never to cure a browse fault.

    PLC programming

  • How-to

    How to compare two CLICK PLC programs for differences

    CLICK Programming Software has no built-in project compare, and the vendor has said none exists in the current release. The working method is to upload each machine's running program as a dated baseline, compare hardware, field assignments, configuration and logic in six passes, classify every mismatch, and load one merged program only after every difference has an owner.

    PLC programming

  • How-to

    PLC-5 heartbeat without the PLC-5 sending messages

    Let the ControlLogix do all the sending: it either writes an incrementing heartbeat word to the PLC-5 over Ethernet MSG or pulses a spare output into a spare PLC-5 input, and the PLC-5 resets a watchdog timer only on a genuinely new value or pulse edge — never on message-complete status. Set the preset above two update periods plus measured transfer delay; in the worked example, 1500 ms detects a dead link within 1.5 s.

    PLC programming