PLC programming Published 7 min read

Short answer

Use the 1747-PIC only when the port is DH-485 — fixed SLC 500s, 5/01s, 5/02s and Channel 1 of a 5/03. On a 5/03, 5/04 or 5/05, Channel 0 is an RS-232 DF1 port that connects with a plain null-modem cable at 19200 baud; on a laptop without a serial port, the 1747-UIC replaces the PIC.

On this page
  1. Which SLC 500 processor am I connecting to?
  2. Do I have to use the 1747-PIC gray box?
  3. Why did the same cable work on my MicroLogix 1000?
  4. My laptop has no serial port — what replaces the 1747-PIC?
  5. What cable and settings do I use for DF1 on Channel 0?
  6. How do I connect through the second channel on a 5/04 or 5/05?
  7. How long will an upload take at 19,200 baud?
  8. The processor still does not show in RSLinx — what now?
  9. Questions asked

You need the 1747-PIC gray box only when the port you must program is DH-485: that means the fixed SLC 500 brick, the 5/01 and 5/02, and Channel 1 of a 5/03. On a 5/03, 5/04 or 5/05, Channel 0 is an ordinary RS-232 DF1 port, and a null-modem cable connects it to a PC serial port at 19,200 baud with no interface at all. On a laptop with no serial port, the 1747-UIC USB converter is the PIC's successor. Everything at the palletizer follows from one marking: the processor model on the faceplate.

Which SLC 500 processor am I connecting to? #

The model marking on the processor faceplate decides everything: fixed SLC 500 bricks, 5/01s and 5/02s carry only a DH-485 port, while the 5/03, 5/04 and 5/05 give you an RS-232 DF1 Channel 0 plus a second channel that varies by model. Read it before you open the laptop bag, because the interface choice — PIC, UIC, plain cable or Ethernet — hangs entirely on that one line of text.

Processor Port you program What the laptop needs
Fixed SLC 500 brick DH-485 only, hard-configured 1747-PIC on a built-in COM port, or 1747-UIC on USB
5/01 and 5/02 DH-485 only 1747-PIC or 1747-UIC
5/03 Channel 0 RS-232 DF1; Channel 1 DH-485 Null-modem serial cable on Channel 0
5/04 Channel 0 RS-232 DF1; Channel 1 DH+ Null-modem serial cable on Channel 0
5/05 Channel 0 RS-232 DF1; Channel 1 Ethernet Null-modem cable or an Ethernet link

On the fixed brick, that DH-485 port is hard-configured and is also the only route for programming, the HMI and peer-to-peer traffic, so you will be sharing it. Write down the full 1747 catalog number and which ports already have cables attached; if Channel 0 on a 5/03 or newer already carries the operator interface, that decides whether you connect on Channel 0 or Channel 1.

Do I have to use the 1747-PIC gray box? #

You need it only when the port you must reach is DH-485 — the fixed brick, the 5/01 and 5/02, or Channel 1 of a 5/03; on a 5/03, 5/04 or 5/05 the DF1 Channel 0 connects with a plain null-modem cable and no interface box. The PIC is not a cable: it converts the PC's RS-232 COM port to DH-485, which is a different electrical interface and a different protocol. The contractor's laptop card is almost certainly a 1784-PCMK, a PCMCIA interface doing the same DH-485 job and, with the right cables, DH+ and PLC-2 front-port programming as well. If the processor turns out to be a 5/03 or newer, you can stop here: the null-modem cable into Channel 0 answers the question.

Why did the same cable work on my MicroLogix 1000? #

Because the MicroLogix 1000 Channel 0 is an RS-232 port speaking DF1, so its null-modem cable really does plug straight into a PC; the port on a fixed, 5/01 or 5/02 SLC is DH-485, a multi-drop RS-485 network with token passing, and RS-232 levels cannot drive it. DH-485 is a network, not a point-to-point link: 19,200 baud, up to 32 nodes, 4,000 feet of cable. DF1 over RS-232 is the forgiving protocol your MicroLogix memory is built on. That memory still applies once the link is up — the faults behind a MicroLogix 1000 not found in RSLinx after a channel change are driver-side faults of the same kind you will debug on the SLC.

My laptop has no serial port — what replaces the 1747-PIC? #

Use the 1747-UIC, the USB interface converter that replaced the PIC: it presents DH-485 and RS-232 DF1 to RSLinx over USB, because the 1747-PIC itself is documented for built-in COM1 and COM2 ports only and fails on USB-to-serial adapters and add-in serial boards. Rockwell installation instruction 1747-IN024 draws exactly that line: the converter depends on the timing of a real PC UART, and an emulated port does not reproduce it. In RSLinx, configure the 1747-UIC driver and set its mode — DH-485 or RS-232 — to match the port you are reaching. The 1784-PCMK needs a PCMCIA slot that current laptops no longer carry.

What cable and settings do I use for DF1 on Channel 0? #

A standard null-modem cable — transmit and receive crossed, DB9 pin 2 to pin 3, signal ground on pin 5 — from the laptop COM port to Channel 0, then autoconfigure the DF1 driver in RSLinx; the port defaults to 19,200 baud full duplex. DF1 ports on this hardware accept 300 through 19,200 baud, so if someone changed the default, the autoconfigure routine finds whatever is actually set rather than guessing. Full duplex belongs on a point-to-point cable; half duplex belongs to modem and multi-drop links, and mixing them up yields a browse window with nothing in it.

Two cautions before you go online. First, put the machine in a safe state and upload before you ever download: an accidental download to a running palletizer can drop outputs mid-cycle. Second, if a read succeeds but a script or SCADA poll misbehaves, the DF1 dialect matters — the differences behind why DF1 reads work on an SLC 500 but not a PLC-5 are protocol-level, not cable-level. And if Channel 0 already carries the operator screens, plan around unplugging them mid-shift; the setup for connecting SCADA to an SLC 5/03 over serial walks the same chain from the other end.

How do I connect through the second channel on a 5/04 or 5/05? #

On a 5/05, use the Channel 1 Ethernet jack and the Ethernet driver in RSLinx with the processor's IP address; on a 5/04, Channel 1 is DH+, which no PIC, UIC or serial cable reaches — it takes a PCMK-class card or a ControlLogix DH+ bridge. If the 5/05's address is unknown or the port sits on an isolated network, Channel 0 DF1 is the fallback: connect over serial and read the Channel 1 configuration off the processor. For DH+ work with no PCMCIA slot available, a ControlLogix DH+ bridge for reaching PLC-5 and SLC 500 data is the usual route.

How long will an upload take at 19,200 baud? #

Roughly 9.4 seconds of line time for a full 16 KB processor memory at the 19,200-baud default, so a connection that stalls for minutes is a settings fault, not the serial link being slow. The arithmetic, as an illustrative check:

  • 19,200 bits/s ÷ 10 bits per character (1 start, 8 data, no parity, 1 stop) = 1,920 characters/s.
  • 16 KB = 16,384 bytes → 16,384 × 10 = 163,840 bits on the wire.
  • 163,840 ÷ 19,200 = 8.53 s of pure character time.
  • Add about 10% for DF1 framing and acknowledgments: 8.53 × 1.10 ≈ 9.4 s.
  • The same 163,840 bits over the 5/05's 10 Mbps Channel 1 is about 0.016 s of line time.

Decision: for a one-time connect-and-upload visit, 19,200-baud serial is more than adequate — nobody needs Ethernet to read a program once. Choose the 5/05's Channel 1 when you will go online routinely, not because the upload requires it.

The processor still does not show in RSLinx — what now? #

Check the link in this order — the COM port number, the driver type, baud, duplex (full or half), error detection (CRC or BCC), and the station address — because a DF1 mismatch shows up as an empty network tree, not an error message. Confirm the cable landed on the COM port the driver thinks it did, and that the driver matches the physical path: DF1 for direct serial, the 1747-UIC driver for USB, DH-485 through the converter. On a DH-485 network, every node must run the same baud or the whole network stays silent. Only when the processor's name appears in the browse window is software on the table — RSLogix 500 programs the entire SLC 500 family, so if the blocker is the install or the license rather than the link, getting RSLogix 500 through official channels is the fix.

Questions asked

Can a USB-to-serial adapter drive the 1747-PIC instead of a built-in COM port?

No. The PIC's installation instruction limits it to built-in COM1 and COM2 ports and explicitly excludes USB-to-serial adapters and add-in serial boards, because the converter depends on the PC UART's timing. The supported USB path is the 1747-UIC, which RSLinx drives directly rather than as a mapped COM port.

What is the PCMCIA card the contractor uses instead of the gray box?

A 1784-PCMK PCMCIA communication card. It serves the same DH-485 role as the 1747-PIC and, with the right cables, also Data Highway Plus and PLC-2 front-port programming, which the 1747-UIC does not cover. Modern laptops dropped the slot, so on new hardware the UIC or a bridge takes the DH-485 and DF1 work.

Will my older RSLogix 500 install program the newer MicroLogix controllers too?

It programs every SLC 500 processor, but an RSLogix 500 release supports only the controllers that existed when it shipped, so a MicroLogix model introduced after your build will be refused by it. Update the software package through the vendor rather than reloading the controller for compatibility; the SLC projects keep working on the install you have.

Is DH-485 the same network as DH+?

No. DH-485 is the 19,200-baud, 32-node, 4,000-foot RS-485 network used by fixed SLC 500s, the 5/01 and 5/02, and Channel 1 of a 5/03. DH+ is the separate network on 5/04 Channel 1 and PLC-5 processors, and neither the 1747-PIC nor the 1747-UIC can reach it.

Keep reading

  • Troubleshooting

    MicroLogix 1000 not found in RSLinx after a channel change

    The MicroLogix 1000 is missing from RSLinx because the channel-configuration download changed its serial port from DF-1 to DH-485, so the DF-1 driver and Auto-Configure can never verify against it. Reach the controller through DH-485 with a 1747-UIC at its default 19200 baud, go online, set Channel Configuration back to DF-1, download, and re-run Auto-Configure.

    Industrial networks

  • Troubleshooting

    PLC-5 not visible in RSLinx after processor replacement

    A replacement PLC-5 stays invisible in RSLinx because the 1785-ENET sidecar answers the network on its own while the processor waits for an application that configures the Ethernet channel 3A. Leave the non-isolated serial port disconnected until the cable is checked, bring the processor up over serial DF1 or DH+, download the saved program, and the Ethernet path returns.

    PLC programming

  • Troubleshooting

    Connect SCADA to an SLC 5/03 and MicroLogix 1500

    None of the three listed drivers will work: ControlLogix and CompactLogix are different controller families, and the MicroLogix 1100/1400 connection is Ethernet to models that have an Ethernet port. Your SLC 5/03 and MicroLogix 1500 LRP are serial-only, so connect through an OPC server with a serial DF1 or DH-485 driver, or a protocol-aware gateway. Put both controllers on one DH-485 network and bridge it once.

    SCADA and data logging