When a PLC output can drive a VFD digital input directly

Drives and motion Published 9 min read

Short answer

Yes: a sourcing PLC transistor output drives a 24 V VFD digital input directly when the input accepts a sourcing signal, its input current fits within the output point and group ratings, and the drive common is bonded to the PLC supply reference. Wire it straight inside a shared enclosure; add an interposing relay only for a rating, polarity or reference mismatch, or a long cable run exposed to drive switching noise.

On this page
  1. Can a PLC output drive a VFD digital input directly?
  2. Which ratings decide the direct connection?
  3. How do you check the current budget with real numbers?
  4. Why does the drive common need the PLC supply bond?
  5. Where does the drive 10 V potentiometer reference fit?
  6. When does the connection need an interposing relay?
  7. How do you wire and test it safely?
  8. Questions asked

Wire them straight. A PLC output with PNP transistor stages can drive a 24 V VFD digital input directly, with no interposing relay, once three checks pass: the drive input accepts a sourcing signal, its input current fits inside the PLC output point and group ratings, and the drive input common is bonded to the PLC supply 0 V. An interposing relay earns its place only when one of those checks fails — a polarity or reference that cannot be matched, an input current the point cannot carry, a drive input that runs on a voltage the transistor stage cannot supply — or when the signal cable leaves the shared enclosure, where switching noise from the drive starts to matter.

Can a PLC output drive a VFD digital input directly? #

Yes — a 24 V PNP output switches a 24 V drive input directly with plain panel wire and no interposing relay, provided the drive input accepts a sourcing signal, its input current sits inside the output point and group ratings, and the input common shares the PLC supply reference.

This is the normal arrangement, not a workaround. Drive digital inputs are small opto-isolated or resistive loads built to take a PLC-grade signal, and drives designed for PLC integration assume exactly this wiring: the Lenze i550 protec, for example, carries five digital inputs and two analog inputs on its control terminals. The trap is the mirror case. An NPN, sinking output pulls its load down toward the negative rail instead of feeding it positive, so that arrangement needs the drive input common lifted to the positive rail instead. Wire a sourcing output to an input whose common sits at the wrong rail and the input never energizes, no matter what the voltage label says.

Which command path — digital inputs, an analog reference or a network — is the interface decision that how a PLC controls a VFD: five interfaces compared walks through. The checks below are the electrical ones that decide whether that digital-input choice can be wired with nothing between the two devices.

Which ratings decide the direct connection? #

Four checks decide it: the drive input rated current per point, the PLC output rated load current per point, the total of everything sharing that output group common, and the polarity and reference match between a sourcing output and the drive input circuit — terminal labels alone decide nothing.

Find the numbers in two places. The drive manual digital-input chapter states what each input draws at its rated voltage; for the five inputs on the i550, that chapter carries the per-input figure. The PLC manual output chapter states the per-point load rating and the per-common group rating, the limit shared by every point hanging on one common. Then sum the group honestly: count every load the program can hold on at the same moment — pilot lights, interposing coils, the other drive inputs — and assume any combination the logic can produce, including fault states where a forward and a reverse output overlap.

The decision rule: input current under the point rating, group total under the group rating, and the steady-state sum kept under half the group limit so lamp inrush and simultaneous switching have headroom. Both hold — direct wiring is correct. Either fails — move a load to another group or interpose.

How do you check the current budget with real numbers? #

Take example values — 6 mA per drive input, 0.3 A per output point, 0.6 A per group common — and the worst case of four inputs commanded together draws 24 mA, just 8% of the point rating and 4% of the group limit, a factor of twelve in hand.

Worked example, with example values standing in for whatever your two manuals state:

  • Drive side, example: 6 mA per digital input.
  • PLC side, example: 0.3 A per output point, 0.6 A per group common.
  • Worst case: run forward, run reverse, remote mode and fault reset held on together — 4 × 6 mA = 24 mA on the group.
  • Point check: 24 mA against 300 mA is 8% of the rating; 300 / 24 ≈ 12.5, about a factor of twelve in hand.
  • Group check, empty common: 24 mA against 600 mA is 4%.
  • Group check, loaded common: the same group already carries 590 mA of lamps and one interposing coil; adding the drive inputs gives 614 mA, which is 14 mA over the 600 mA limit.

On the empty common both checks pass and the direct connection is correct. On the loaded common the group limit fails, and the cure is not heavier wire: move a lamp to a spare group, or hand the drive inputs to an interposing relay. The method is what carries — read the drive per-input figure and the PLC point and group ratings, run the same two comparisons, and keep the sum under half the group limit.

Why does the drive common need the PLC supply bond? #

The sourcing output pushes current into the drive input, and that current must get back to the PLC supply through copper, not through earth: bond the drive digital-input common to the PLC 0 V with its own conductor, and keep protective earth out of the signal loop.

Without that bond the current still finds a way home — through earth conductors, cable shields and the grounded enclosures of everything else in the cabinet — and those paths carry noise. The input chatters, drops out under load, or never pulls in cleanly. The failure is not exotic: the S7-200 SMART analog inputs that fluctuated until the reference was bonded are the same missing conductor, showing up as noise instead of a dead input.

Practical points: on multi-input drives one common terminal usually serves the whole input group, so the drive diagram asks for one bond per group. Land it on the PLC supply negative terminal, not on a chassis stud in passing, and leave protective earth to fault protection — it never substitutes for a signal return.

Decision: one dedicated conductor from the drive input common to the PLC supply negative makes the direct connection legitimate; without it, current headroom counts for nothing.

Where does the drive 10 V potentiometer reference fit? #

Treat the potentiometer as a separate circuit: it can share the cabinet and the bonded reference, but it follows analog wiring rules, and the drive manual — not the digital-input chapter — defines the terminals and the permitted resistance range for its 10 V auxiliary reference output.

The scenario that usually raises this alongside the digital one: a speed pot across the drive auxiliary reference output, wiper into a PLC analog input, all in one cabinet. Three checks, none of them the digital ones above. Configure the analog input for the voltage range the wiper delivers. Land its return where both manuals require it, which is normally the PLC analog common sitting on the bonded reference. Keep the pot resistance inside the range the drive manual permits, or the reference sags and the speed reads low. If the drive reads the pot on its own analog input instead, the PLC leaves the loop entirely and only the drive manual applies.

Know the failure behavior too: with the wiper conductor open, many drives fall back to a stored default speed rather than stopping. That response, and the wiring that prevents it, is the subject of why a VFD runs at minimum speed when the analog reference is lost.

Decision: run commands and speed references are separate circuits with separate rules; clearing the digital-input checks clears nothing on the analog side, and the other way round.

When does the connection need an interposing relay? #

Add an interposing relay when the input current exceeds the output point or group rating, when polarity or supply reference cannot be matched, when the input needs a dry contact or a voltage the transistor stage cannot switch, or when the signal cable runs outside the shared enclosure.

Take the triggers in order. Current: rare with modern opto-coupled inputs, real with older or specialty inputs whose draw approaches the point rating. Polarity and reference: a sinking output facing a sourcing-required input, or a drive whose input common lives on an internal supply you cannot share. Voltage type: an input rated for alternating voltage, which no low-voltage transistor stage provides. Distance is the trigger that surprises people, and it deserves the mechanism rather than a magic number.

Inside one enclosure, with the run a metre or two and kept away from the motor cable, drive switching transients have almost nothing to couple into, and direct wiring is right. Once the cable leaves the panel — a drive mounted at the motor, tens of metres sharing a tray with motor cable — those transients land on the signal and the input chatters or ghost-switches. Shielded motor cable cuts the coupling substantially, and high-power installations show it can still leave enough behind to matter; an interposing relay separates the PLC side from the drive side, so the noise lands across a contact gap instead of into a semiconductor.

A relay is not free: its coil current joins the group budget, its contacts wear, and a welded contact is a new single point of failure.

Decision: all three electrical checks pass and the cable stays in the cabinet — no relay. Any check fails, or the run leaves the cabinet toward the motor — interpose.

How do you wire and test it safely? #

Wire with the cabinet isolated, land the output on the chosen input, run the common bond, then prove the path end to end: command each output from the PLC and watch the drive input indicator or status bit change with it before you let the drive run.

  1. Read both terminal diagrams and mark four points: the PLC output terminal, the common its group shares, the chosen drive input, and the input common terminal the drive manual assigns to that group.
  2. Isolate the cabinet, wire output to input, and land the dedicated common bond from the earlier section. Keep each signal and its return as a pair, routed away from the motor cable.
  3. Re-energize with the drive disabled. Force each PLC output in turn and confirm the drive input LED or status bit follows it. Then switch the whole group on together and confirm nothing drops out — that is the group budget check under live conditions.
  4. Assign the drive function to each input in the drive parameter set, then exercise run, reverse and remote transitions with the machine in a safe commissioning state before production material reaches the line.
  5. If the panel also carries a local start and stop station on the drive own terminals, follow the conventions for wiring start and stop pushbuttons when a VFD replaces a DOL starter — those inputs follow the drive control diagram, not the PLC.

One safety note belongs here: keep the drive hardware stop input on its own contacts, not behind the PLC program. A run command through panel wiring is an operator path; a validated stopping function carries its own ratings, its own wiring and its own standard, separately.

The decision, end to end: with a sourcing output, input current inside both ratings, a bonded input common and the cable kept inside the shared enclosure, connect the PLC output to the drive input directly and leave the interposing relay in the spares cabinet. Add it the day a rating, a polarity, a voltage type or the cable route fails one of those.

Questions asked

Can a PLC relay output drive the same VFD inputs?

Yes, and the polarity checks disappear, because a relay output is a dry contact that simply bridges the drive input to its common. The trade-offs are slower response, contact wear over many operations, and switching noise on the contact, which is why transistor outputs remain the choice for frequent switching or pulse duty.

What changes when the drive inputs switch line voltage instead?

A semiconductor output cannot provide that voltage, so direct connection is out regardless of current. Fit an interposing relay whose coil accepts the PLC output rating and whose contacts carry the input rated voltage, commonly 110 V or 230 V AC on that style of drive, and keep the low-voltage and line-voltage wiring separated in the cabinet.

Which conductor size suits a PLC to drive input run?

The input current is a few tens of milliamps at most, so voltage drop never decides the size. Choose control wiring for mechanical strength and termination quality, keep each signal with its return as a pair, and follow the conductor size your panel standard already uses for the rest of its 24 V control wiring.

Can the drive auxiliary supply power the PLC input groups instead?

It is possible on some drives and usually a poor trade. The PLC inputs become sinking loads tied to the drive internal supply, which disappears whenever the drive powers down and leaves those inputs floating. Keep the PLC inputs on the PLC own supply and bond the drive input common to it as described above.

Does the same check apply when a drive output feeds a PLC input?

Yes, with the direction reversed: the drive output load rating must then cover the PLC input current demand, and polarity still has to match, since many drive transistor outputs sink toward their own common rather than sourcing. A drive relay output behaves as a dry contact and suits either input style.

Keep reading

  • Troubleshooting

    Fix a PowerFlex 40P opto output that will not turn on

    The opto outputs on PowerFlex 40P terminals 17 and 18 are always sinking NPN transistor outputs rated 30 VDC at 50 mA, and the drive's sinking/sourcing switch configures only the digital inputs. Fix it with a sourcing PLC input wired between +24 V and the output terminal, an interposing relay, or the drive's form C relay output.

    Drives and motion

  • How-to

    Connect a MicroLogix 1100 to a PowerFlex 4M over Modbus

    Use a 1763-NC01 cable to break out the MicroLogix 1100 RS-485 port, land the drive side on an AK-U0-RJ45-TB2P terminal block, set both ends to the same Modbus RTU format with a unique node address on the drive, and run one MSG at a time, waiting for DN or ER before the next. Never use that cable on a MicroLogix 1200 or 1500; it can damage the controller.

    Drives and motion

  • How-to

    Splitting VFD speed and start stop between Modbus and digital inputs

    Apply connection macro Cn011, set P0700 to 2 so the digital inputs carry start and stop, and keep the HSW register as the speed reference scaled against P2000. A successful register write proves the link, not the source selection, so prove each path separately and never zero P2000 to silence fault F72.

    Drives and motion