Why a VFD runs at minimum speed when the analog reference is lost

Drives and motion Published 8 min read

Short answer

The run command and the speed reference are separate paths, so a drive with a live run command answers a dead analog input with whatever its settings prescribe: zero speed, its minimum frequency, a held value, a stop or a fault. A low, steady speed with no parameter matching it is either a partially failed channel or a minimum-frequency clamp, and you meter the input to tell them apart.

On this page
  1. What speed does a VFD run at when the analog reference is lost?
  2. Why does the drive keep running when the speed signal is gone?
  3. Does a broken 0-10 V wire look the same as a broken 4-20 mA loop?
  4. Why is the drive stuck at 10 Hz when normal is 40 Hz?
  5. Can you program a default speed for when the reference is lost?
  6. How do you check what the drive is actually seeing?
  7. What should the drive do when the reference fails?
  8. Questions asked

A drive that still has its run command does not stop when its analog speed reference dies. It responds to what its input now measures and to the settings that decide what a bad reference means, so the motor settles at zero speed, runs at its minimum frequency, holds its last value, ramps to a stop, or faults, depending on configuration. A machine stuck at a low, steady speed while every status light says run is therefore not a run-logic failure: it is the drive obeying a dead or partially failed output card, and the fix starts by decoding which behavior you are watching.

What speed does a VFD run at when the analog reference is lost? #

It runs at whatever its settings make of the failed input: 0 Hz when the minimum frequency is zero and nothing detects the loss, the minimum frequency when that limit sits above zero, or it holds, ramps to a stop, or faults instead of running. The response to a lost reference is a configured behavior, not something you can infer from the model name. Two groups of settings decide it: the scaling and limits applied to the input, and the loss-of-signal action taken when the input goes invalid or under-range.

What the input sees Minimum frequency at 0 Hz Minimum frequency above zero
True zero: broken voltage-reference wire, dead unipolar current channel Stands still, enabled Runs at the minimum frequency
Under-range: broken live-zero loop reading near zero current Follows its loss-of-signal action: fault, warn, hold or stop Same, or the minimum after the clamp
A low but valid signal from a partially failed channel Follows the signal, scaled Follows the signal, or the minimum if the scaled value is lower

Drives differ only in which actions they offer and what they name the setting; the signal-loss section of your drive's manual tells you which ones yours has.

Why does the drive keep running when the speed signal is gone? #

Because the run/enable command and the speed reference are separate control paths: digital inputs or a safety input decide whether the drive may produce torque, while the analog input only says how fast, so a valid run command keeps the drive enabled with a zero or clamped reference. That is why the symptom confuses people: the PLC run bit is set, the drive display says running, and the speed is simply whatever the reference path delivers. A safety input or Safe Torque Off, when the machine has it, sits on the enable path and blocks torque regardless of the reference, but a plain lost reference never touches that path. Changing the PLC start logic or the enable wiring fixes nothing here. The split is easier to see across the five ways a PLC can command a VFD, and how a PLC controls a VFD: five interfaces compared walks through them.

Does a broken 0-10 V wire look the same as a broken 4-20 mA loop? #

No: a broken 0–10 V wire reads zero volts or floats and picks up noise, a broken 4–20 mA loop reads 0 mA and falls below the 4 mA live zero, and a failed 0–20 mA channel sitting at 0 mA still looks like a valid minimum command. The current loop defined by IEC 60381-1 puts its live zero at 4 mA precisely so an open circuit is distinguishable from a valid low measurement, but the drive must be configured to treat that under-range reading as a fault, warning, hold or stop, and on plenty of installed drives that setting is off or set to ignore. A voltage input gives you no such gap: a broken conductor leaves the terminal floating, so the drive reads zero, a mid-span value, or a value that wanders with induced noise, and the output frequency wanders with it. A 0–20 mA loop has no live zero either, so its broken state is a perfectly valid minimum command.

Why is the drive stuck at 10 Hz when normal is 40 Hz? #

A drive sitting at a round, low figure like 10 Hz against a 40 Hz normal is showing either its configured minimum frequency clamping a zero request, or a partially failed output still sending a low but valid signal the drive obeys. Two worked examples show both.

Take an example drive scaled 0–50 Hz over a 0–10 V input. Normal operation at 40 Hz corresponds to 40 Hz ÷ 50 Hz × 10 V = 8 V at the terminal. Break that conductor and the terminal drops to zero, a zero-speed request; with the minimum frequency set to 10 Hz, the clamp lifts the request to that limit and the motor turns at it, with no other parameter in the drive containing the number.

Now suppose the reference is a live-zero current loop, 4–20 mA scaled 0–50 Hz, and the failing card settles at 7.2 mA instead of dying cleanly. The drive computes (7.2 mA − 4 mA) ÷ (20 mA − 4 mA) = 0.2, and 0.2 × 50 Hz = 10 Hz, the same display with nothing set anywhere near it. A partially failed channel is exactly the case where you search the parameter list and find nothing, because the number lives in the broken card, not in the drive.

One more possibility closes the set: if the drive's selected reference source is a preset or the keypad rather than the analog input, the terminal value is ignored altogether, so read the active source on the display first.

Can you program a default speed for when the reference is lost? #

Yes, but only where the drive documents it: many drives let you choose the loss-of-signal action (fault, warn, hold last value, stop, or ramp to a preset or maximum frequency), and where they don't, the PLC must supervise the reference and write the fallback speed itself. The PowerFlex 70 user manual, for one, documents configuring an analog input to fault on signal loss, and its troubleshooting points first to broken or loose connections at the input terminals. Where the drive offers no preset-on-loss, send the reference over the network, detect the dead channel or stale value in logic, and write the preset from the PLC. A network reference that stops being written is its own fault, though: missing setpoint and control word writes to a PROFIBUS drive shows what that looks like from the drive end.

One caution belongs with the fallback choice: raising the minimum frequency so the machine fails safe at low speed turns every lost reference into uncommanded motion. For any machine that is safe only when stopped, the fault response is the correct fallback and a hidden minimum speed is the wrong one.

How do you check what the drive is actually seeing? #

Measure the signal at the drive's input terminals with a meter suited to the circuit and compare it with the drive's own input monitor and displayed frequency; the gap between commanded and measured values identifies a dead channel, a partial signal, or a configuration clamp. Work in this order:

  1. Record the drive display as found: status, active reference source, output frequency, monitored input value and any warning.
  2. Confirm from the schematics how the reference arrives, wired analog or network, and the signal range at both ends; never infer the range from the symptom.
  3. In an approved test condition, meter at the drive terminals: voltage across the input and its common for a voltage-reference circuit, current in series for a current loop.
  4. Compare the meter reading with the drive's input monitor and the PLC's commanded output value.
  5. Branch on the result. Commanded but not measured means the channel, the wiring, or a ground fault dragging the loop low, and fixing a 4-20 mA output ground fault with a signal isolator covers that repair; measured and matching but the speed still wrong points at scaling, limits or the loss action.

What should the drive do when the reference fails? #

Decide by consequence: if the machine is safe only when it stops, configure the drive to fault on signal loss over a live-zero current loop so the loss is detectable; if the process must keep moving, let the PLC write a defined fallback speed and alarm the failed reference. Commit per case.

Machine safe only when it stops, such as conveyors, feeders, anything with an operator at the inlet: wire the reference as a live-zero current loop, enable the under-range detection, and set the loss action to fault. Test it once by pulling the reference wire at the drive in a cleared, approved state and confirm the fault appears.

Process that must keep moving, such as extraction fans, cooling pumps or dilution air: take the fallback speed from the process, give it to the PLC to write on loss with an alarm, or use the drive's own preset-on-loss action where the manual lists one. Never leave the fallback as an accidental minimum-frequency clamp that nobody chose.

Partial signal from a sick channel: the drive is innocent, so repair or replace the analog output channel and leave the drive parameters alone.

In every case the number on the display is a chain: what the input measures, what the scaling and limits do to it, and what the loss action adds. Read those three and the mystery speed stops being a mystery.

Questions asked

How can I test the drive's loss response without a test bench?

Do it during a planned stop with the machine cleared or the motor uncoupled. Record the normal reference first, then simulate the failure at the drive end by pulling the reference wire or forcing the PLC channel to zero, and watch the display for the response. Restore the wire, confirm the normal speed returns, and write the observed behavior into the machine documentation so nobody has to guess again.

Can I run the drive from its keypad while the output card is down?

Usually yes. Most drives let you select the local keypad as the speed source and start from the terminals or the keypad, which is a standard stopgap for manual operation. Treat it as temporary: the source change is a configuration change, so record it and restore the original source selection before the machine goes back to automatic, or the next reference loss will look like a different fault.

What is different when the speed reference comes over a network?

No wire breaks, but the drive stops receiving setpoint writes and its communication-loss action takes over, typically a fault, a coast stop or a preset after a configured timeout. An address conflict after a power outage can produce exactly this picture: every status shows run while the speed word never arrives, and the drive sits at zero or its fallback. Check the connection and the timeout action, not the analog wiring.

Does running long hours at minimum speed harm the motor?

It can. A fan-cooled motor depends on shaft speed for airflow, so a belt or fan held at a low frequency under load cools poorly while the drive itself stays healthy, because its protections watch current, not winding temperature. If the process must run at minimum speed for long periods, verify the motor's thermal protection or use a separately ventilated machine for that duty.

Keep reading

  • Comparison

    How a PLC controls a VFD: five interfaces compared

    A PLC controls a VFD through one of five interfaces: discrete I/O, an analog speed reference such as 0-10 V or 4-20 mA, Modbus RTU or TCP, EtherNet/IP or BACnet/IP, or PROFIBUS or DeviceNet. Discrete and analog wiring carry commands only; the network interfaces also return status and fault data. Pick by how much the PLC must know about the drive, not by brand.

    Drives and motion

  • Explainer

    Can a PLC gateway replace a networked VFD with hardwired I/O

    Yes to the wiring, no to the disguise: a small PLC can drive a 4-20 mA speed reference and run/trip signals, but an EtherNet/IP scanner checks vendor ID and product code and will not connect to a gateway posing as the drive, so the upstream controller must be reprogrammed to talk to the PLC as itself. Fixed installations get a network-native drive; OEM machines built around customer-supplied drives get a defined hardwired interface.

    Drives and motion

  • Comparison

    Choosing how a CLICK PLC commands VFD speed safely

    Keep the proven RS-485 link as the speed reference and let the drive's acceleration and deceleration ramps enforce the motion limit, with the encoder supervising. A 0-10 V analog reference is an equally safe alternative; a pulse train is only a frequency reference and is unconfirmed on this drive. None of the three is a personnel-safety function.