Fix a PowerFlex 40P opto output that will not turn on

Drives and motion Published 5 min read

Short answer

The opto outputs on PowerFlex 40P terminals 17 and 18 are always sinking NPN transistor outputs rated 30 VDC at 50 mA, and the drive's sinking/sourcing switch configures only the digital inputs. Fix it with a sourcing PLC input wired between +24 V and the output terminal, an interposing relay, or the drive's form C relay output.

On this page
  1. Why the input never sees the opto turn on
  2. The wiring that works with a sourcing input
  3. Measure before you change anything
  4. Worked example with real numbers
  5. Two ways out with a sinking input card
  6. Opto output limits
  7. Make sure A061 actually stuck
  8. The decision, case by case
  9. Questions asked

The opto output is almost certainly switching. The fault is on the PLC side: the opto outputs of a PowerFlex 40P are hard-wired as sinking NPN transistor outputs, and the sinking/sourcing switch on the drive's control board configures only the digital inputs. A sinking PLC input never closes a current loop with them, so the point never lights no matter what A061 says. Leave A061 [Opto Out2 Sel] at Motor Running and fix the field wiring: give the output a sourcing input, put an interposing relay in between, or move the signal to the drive's form C relay output.

Why the input never sees the opto turn on #

When A061 selects Motor Running and the drive runs, the opto transistor on terminal 18 conducts, but in one direction only. It ties terminal 18 to the opto common on terminal 19, a low-side switch to DC common. It never puts voltage on the terminal. The load has to sit between +24 V and terminal 18, with terminal 19 returning to the supply's DC common, which is exactly how the manual draws its brake-relay example in Publication 22D-UM001.

The sinking/sourcing switch on the control board looks like it should fix this and does not. It configures the digital inputs only, per the control wiring block diagram in Publication 22D-UM001; the opto outputs are sinking in every switch position. If the field-side naming still blurs, one clean reference on sinking, sourcing and dry contact differences settles which side of a discrete loop must supply the voltage.

The wiring that works with a sourcing input #

A sourcing input card supplies the voltage from its side and expects the field device to return current to DC common, the exact partner for a sinking output. Wire it as one series loop:

  • Supply positive to the sourcing input module's common.
  • The input point to drive terminal 18 (terminal 17 for Opto 1, selected with A058 [Opto Out1 Sel]).
  • Drive terminal 19 to the DC common of the same supply.
  • If the drive and the card run from separate supplies, bond the two DC commons together.

When the opto conducts, current runs from the supply, through the input point, into terminal 18, through the transistor, out of terminal 19 and back to common, and the point turns on.

Measure before you change anything #

Put a DC voltmeter across the opto itself: black lead on terminal 19, red lead on terminal 18.

  • Motor stopped, A061 at Motor Running: the meter reads the supply, about 24 VDC.
  • Motor running: the reading collapses to the transistor's on-state drop, at most 1.5 VDC.
  • A reading that never moves between those states means the parameter never stuck, a lock rejected the edit, or you are on the wrong terminal pair.
  • A reading that moves while the PLC point stays dark means the input type is the fault; rewire per the loop above.

Re-terminate with the loop dead, and remember the drive's own power terminals stay live whenever the disconnect is closed.

Worked example with real numbers #

Say the sourcing input point draws 12 mA at 24 V, an illustrative value; read your module's data sheet for the real figure. The documented limits are 30 VDC maximum, 50 mA continuous per output, and 1.5 VDC maximum on-state drop.

  • Voltage at the input when on: 24.0 V − 1.5 V = 22.5 V.
  • Current as a share of rating: 12 mA ÷ 50 mA = 24%.

Decision: the loop passes with margin, so wire direct and skip the relay. For an interposing relay with a 30 mA coil, 30 mA ÷ 50 mA = 60% of rating and the coil still sees the same 22.5 V, far above any hold-in threshold, so that also passes. The off state is clean too: 0.1 mA of leakage through a 2 kΩ coil develops only 0.1 mA × 2000 Ω = 0.2 V, nowhere near pickup.

Two ways out with a sinking input card #

  • Interposing relay: 24 VDC coil between supply positive and terminal 18, terminal 19 to DC common. The dry contact then switches the supply voltage into the sinking input point, and the input type stops mattering.
  • The drive's relay output: a form C contact selected with A055 [Relay Out Sel] for the same Motor Running condition. It is dry and polarity-free, drives either input type, and is rated 3 A at 250 VAC or 30 VDC resistive, derated for inductive loads, though a PLC input draws only milliamps.

Opto output limits #

Item Value
Output type Opto-isolated sinking NPN transistor, fixed
Terminals 17 = Opto Out 1 (A058), 18 = Opto Out 2 (A061), 19 = common
Maximum voltage 30 VDC
Maximum current 50 mA continuous per output
On-state drop 1.5 VDC maximum
Off-state leakage 0.1 mA maximum

Make sure A061 actually stuck #

An edited parameter can sit as a pending change until it is saved, and a program lock blocks keypad edits outright. Re-read A061 after a power cycle and confirm Motor Running is still the stored value, whether you set it from the keypad or the drive software. If edits refuse to commit, check the lock parameter before blaming the hardware.

The decision, case by case #

  • A sourcing input point is available: wire the loop direct, supply positive to the card common, point to terminal 18, terminal 19 to DC common. Done.
  • Only sinking points exist: interposing relay at the drive, dry contact into the input.
  • The signal needs a dry contact, more than 50 mA, or an AC side: use the form C relay output with A055.
  • One status bit is not enough anyway: put the drive on the network and carry run state, faults and frequency in one connection, the pattern shown in Start and stop a PowerFlex 700 over EtherNet/IP from CompactLogix.

Questions asked

Does the drive's sinking/sourcing switch change the opto outputs?

No. That switch configures the digital input terminals only. The opto outputs on terminals 17 and 18 are hard-wired as sinking NPN transistor stages that tie the output terminal to the common on terminal 19, in every switch position. Flipping the switch will not make an opto output source voltage.

Can I just swap the wires on terminals 18 and 19?

No. Reversing them reverse-biases the output transistor, so no current path exists and the input stays off in both states. Terminal 18 is the switched side, terminal 19 is the return to DC common, and the load belongs between supply positive and terminal 18.

What are the opto output ratings?

Each opto output switches a maximum of 30 VDC at 50 mA continuous, with an on-state drop of at most 1.5 VDC and off-state leakage of at most 0.1 mA. Anything needing more current, an AC signal, or a true dry contact belongs on the drive's form C relay output selected with A055.

Why does the same output drive a brake relay but not my input card?

The brake relay wiring puts the coil between +24 V and the opto terminal, with the return on the opto common, which is exactly the topology a sinking output needs. A sinking input card ties its terminal to common internally and expects the voltage from the field device, so the loop never closes.

How do I confirm A061 kept my selection?

A program lock can block edits from the keypad or drive software outright, and an edited parameter can sit as a pending change until it is saved. If the value survives a power cycle and the opto still never changes state measured terminal to terminal, look at the output stage.

Keep reading

  • How-to

    Bridging a PLC-5/15 DH+ network to a Kinetix 300 servo drive

    Yes, a DH+-to-EtherNet/IP gateway exchanges command and feedback words between a PLC-5/15 and a Kinetix 300, but it only moves data: the drive must execute the motion profile locally. Replace the stepper controller, pulse expander, and encoder-counter functions with an eight-word map that carries a 32-bit position as two 16-bit words behind a data-valid handshake. If the machine needs trajectory points streamed per scan, migrate the controller instead of bridging it.

    Drives and motion

  • How-to

    Control a PowerFlex 525 drive from two PLC controllers

    Yes — add the PowerFlex 525 to the Logix controller's Ethernet tree and its command tags appear, but a cyclic drive connection has exactly one owner. Give the Logix controller that ownership, read the MicroLogix machine's request into it, and let one rung select the command the drive follows. Never let two controllers write the speed reference.

    Drives and motion

  • How-to

    Control an ATV12 drive from a TM200 PLC over Modbus RTU

    The ATV12 takes start/stop from register 8601 (CMD) and speed from register 8602 (LFRD, in rpm) once you set Fr1 to Mdb in the CtL- menu and match address, baud, parity and stop bits at both ends. The ladder then writes both words cyclically, one request at a time, gated on completion. Start from the TVDA sample project in Machine Expert Basic.

    Drives and motion