Connect a MicroLogix 1100 to a PowerFlex 4M over Modbus

Drives and motion Published 6 min read

Short answer

Use a 1763-NC01 cable to break out the MicroLogix 1100 RS-485 port, land the drive side on an AK-U0-RJ45-TB2P terminal block, set both ends to the same Modbus RTU format with a unique node address on the drive, and run one MSG at a time, waiting for DN or ER before the next. Never use that cable on a MicroLogix 1200 or 1500; it can damage the controller.

On this page
  1. What the link actually is
  2. Wire the RS-485 side
  3. Configure both ends
  4. Sequence the MSG instructions
  5. Choose the registers
  6. Worked example: poll cycle at 19.2 kbps
  7. Commission in layers
  8. Decisions
  9. Questions asked

Yes — this pairing is standard practice, and it needs two catalog items between controller and drive. A 1763-NC01 cable brings the MicroLogix 1100's RS-485 conductors out where you can land them, and an AK-U0-RJ45-TB2P terminal block turns the PowerFlex 4M's RJ45 comm socket into screw terminals. Set both ends to the same Modbus RTU format, give every drive on the cable its own node address, and run one MSG at a time, holding each step until the message ends in DN or ER. The RJ45 socket on the drive is a serial communications port, not Ethernet, and the registers you code against are listed in the Modbus section of the PowerFlex 4M user manual, publication 22F-UM001.

The PowerFlex 4M is directly compatible with Modbus RTU and is documented for multi-drop on an RS-485 network, so one controller port can serve several drives. The cable from the MicroLogix 1100 carries the two data conductors and the signal common; nothing about the connector chooses the pinout, which is why the assignments come from the manuals and not from connector shapes.

The AK-U0-RJ45-TB2P makes the drive end inspectable and serviceable. It converts the drive's comm socket to terminals; it does not translate protocols, fix polarity, or correct a mismatched format.

One boundary to respect: the 1763-NC01 is documented for the MicroLogix 1100, and the same support answer covers the 1400. The documented warning is that trying this cable on a MicroLogix 1200 or 1500 can damage the PLC. That is a hardware limit, not a setting to work around.

Wire the RS-485 side #

  1. De-energize the panel before changing communication wiring.
  2. Read the pin assignment for the controller's serial port and for the drive's comm socket in their manuals. Match functions — the two data conductors and the common — never wire colors or connector positions.
  3. Land the controller side on the 1763-NC01 leads and the drive side on the AK-U0-RJ45-TB2P terminals.
  4. For more than one drive, run one daisy-chained trunk past all of them; keep stubs out of it and add termination or biasing only where the two interface documents call for it.
  5. Check continuity end to end, confirm no conductor-to-conductor shorts, and carry the common reference through every node.
  6. Bring the link up with one controller and one drive before the rest of the bus joins, so endpoint problems stay separate from trunk problems.

Configure both ends #

On the controller, put Channel 0 in its Modbus RTU master role and set the channel's Control Line to "No Handshaking (RS-485 Network)". The screen-by-screen settings are in configuring MicroLogix 1100 Channel 0 for Modbus RTU.

Pick the serial format once for the whole cable: 19200 bps with even parity, unless a plant standard forces a different rate that both the channel and the drive support. The poll arithmetic at the end of this article shows that rate leaves a wide margin for a handful of drives, and a faster rate only adds one more setting to mismatch.

On the drive, the Modbus setup in the manual has you set five things: control source, speed reference, communication data rate, node address, and data format. For full serial control, point the control source and the speed reference at the comm port; during commissioning you can leave start and stop on the terminals and take only the reference over Modbus.

Give every drive on the cable a unique node address. Duplicates produce collisions and replies that look like they came from the wrong drive, and if the master keeps hitting node 0 no matter what you configured, that failure is explained in why Modbus RTU sends to slave address 0 instead of your device. Whatever addresses you choose, the baud, parity, and data format must be identical at both ends and at every node.

Sequence the MSG instructions #

The channel serves one transaction at a time, so the ladder does too.

  1. Give each transaction its own MSG and enable it only when the sequence is idle.
  2. Hold that step until the message ends with DN or ER.
  3. On DN, use the returned data and advance to the next step.
  4. On ER, capture the message's stored error information before clearing anything, allow two retries, then raise an alarm instead of free-running the request.
  5. After the last transaction, wrap to the first at the update rate the machine actually needs.

Overlapping messages contend inside the controller's message handling, and a physically sound bus then reads as intermittent. That discipline matters more with every drive you add.

Choose the registers #

The Modbus section of 22F-UM001 lists the drive's register addresses — the logic command word, the speed reference, and the status and feedback reads — and the functions the drive answers. Keep three decisions separate: the transport (RS-485 wiring and matched format), the target (that drive's node address), and the application data (the documented registers).

A completed write proves only that the drive accepted a value into a register. The drive acts on it only if its control source and speed reference are set to the comm port, which is why those two settings belong to the drive-side configuration and not to an afterthought.

Worked example: poll cycle at 19.2 kbps #

Illustrative numbers, chosen so you can redo them at another rate: 19200 bps, RTU characters of 11 bits (start, 8 data, parity, stop), a read of two registers — an 8-byte request and a 9-byte response — the 3.5-character silent interval between frames, and an assumed 5 ms for the drive to turn a request around.

  • Request on the wire: 8 characters x 11 bits ÷ 19200 b/s = 4.58 ms
  • Response on the wire: 9 x 11 ÷ 19200 = 5.16 ms
  • Silent interval in both directions: 2 x (3.5 x 11 ÷ 19200) = 4.0 ms
  • Drive turnaround: 5 ms
  • One transaction: 4.58 + 5.16 + 4.0 + 5 = 18.7 ms

Three drives on the bus: 3 x 18.7 = 56 ms per full poll, so each drive's command and status refresh about eighteen times per second. Ten drives would take about 190 ms, roughly five updates per second per drive — enough for supervisory speed control, not for a position loop. Carried further, the same arithmetic is why Modbus RTU drive polling on one serial port is slow as drive counts grow.

The decision: one shared bus is the right call for up to about ten of these drives at 19.2 kbps. Add a second port for isolation or segmentation, not for speed.

Commission in layers #

  1. Read a fixed, documented drive value and confirm DN; compare the number against the drive's display.
  2. Read a feedback register and watch it track the drive's state.
  3. Write a safe, documented-writable value and read it back.
  4. Run the start, stop, and reference tests under the machine's commissioning rules, with the control source and reference now on the comm port.
  5. Break the link deliberately: confirm the PLC catches ER and the drive does what its communication-loss choice says. Set that choice before you trust the link.
  6. Add the remaining drives one at a time, confirming the address and stable polls at each before the next joins.

Decisions #

  • MicroLogix 1100 and one PowerFlex 4M: 1763-NC01 plus AK-U0-RJ45-TB2P, one read and one write MSG sequenced on DN and ER, about 19 ms per transaction at 19.2 kbps.
  • Several drives: the same trunk, unique node addresses, the same sequencer, at the same per-drive cost per poll.
  • A MicroLogix 1200 or 1500 in the cabinet: stop at the cable, and use the serial arrangement that controller's documentation specifies, because the 1763-NC01 is not it.

Questions asked

Can I use the 1763-NC01 breakout cable with a MicroLogix 1400 or 1200?

The manufacturer's support answer documents the 1763-NC01 with both the MicroLogix 1100 and the 1400 for an RS-485 network. The 1200 and 1500 are different: the documented warning says the cable can damage those controllers. Use it only on the 1100 or 1400, and give a 1200 or 1500 the serial arrangement its own documentation specifies.

What does an ER on the MSG usually mean?

Capture the message's stored error before clearing it, because it separates the two families of failure. An error for no response is a timeout: wiring, polarity, wrong node address, or a drive at a different rate or parity. An error for a bad checksum or framing points to mismatched format or noise on the pair. Fix that family before touching the ladder sequence.

How many PowerFlex 4M drives can share the one port?

The PowerFlex 4M manual documents multi-drop on RS-485, so the electrical limit is not the first one you hit. The update rate is: each transaction costs about 19 ms at 19.2 kbps in the worked example, so ten drives complete a full poll in roughly 190 ms, about five updates per second per drive. That is still comfortable for supervisory speed control.

Can I start and stop the drive from its terminals and use Modbus only for the speed reference?

Yes. The drive's setup separates the control source from the speed reference, so set start and stop to the terminals and the reference to the comm port. It is a sound commissioning position: the machine keeps a hard-wired stop path while you prove the serial link, and you can move the command word to Modbus once the reference path is trusted.

Keep reading

  • How-to

    Control an ATV12 drive from a TM200 PLC over Modbus RTU

    The ATV12 takes start/stop from register 8601 (CMD) and speed from register 8602 (LFRD, in rpm) once you set Fr1 to Mdb in the CtL- menu and match address, baud, parity and stop bits at both ends. The ladder then writes both words cyclically, one request at a time, gated on completion. Start from the TVDA sample project in Machine Expert Basic.

    Drives and motion

  • How-to

    How to commission five VFD drives on one Modbus gateway

    Prove the link in three passes: open the Modbus TCP connection to the gateway, verify one read from one drive against its own display, then run one serial transaction at a time across all five. A TCP-to-RTU gateway must serialize every RS-485 request, so schedule run commands ahead of power reads instead of polling all five at once.

    Drives and motion

  • Troubleshooting

    Why a CJ2M Modbus RTU master gets no answer from an S7-1200

    Yes, a CJ2M can poll an S7-1200 over Modbus RTU. The simulators proved each PLC's serial settings, not the cable or the port mode between them: set the Omron port to the mode the MRTU_CPU_Master package requires, bring the send pair onto RDA and RDB for 2-wire operation, load the S7-1200 port at even parity, and confirm the frame on the wire with a known value.

    Industrial networks