Troubleshooting
Why the V20 digital input DI3 will not acknowledge a fault
Short answer
A V20 on macro Cn002 that refuses an S7-300 acknowledge through DI3 at terminal 10 usually fails on one of two things: the fault cause never cleared, or the PLC output and drive share no common reference, so the drive never registers DI3 even with the input voltage confirmed. Toggle the PLC output, watch r0772.2, and let that bit decide whether to fix the wiring or the fault state.
On this page
Twenty-four volts at terminal 10 and P0703 set to function 9 do not acknowledge a V20 fault by themselves. The acknowledge only lands when three things hold at once: the fault's cause is gone, the PLC output and the drive share a 0 V reference so DI3 forms a complete circuit, and the drive actually registers the input change, which you prove by watching r0772.2 move while you toggle the output. When a V20 on macro Cn002 will not acknowledge from an S7-300 digital output, the missing piece is almost always that shared reference or a cause that never really cleared. This is the hardwired path; a speed setpoint sent over USS to an HMI or controller has its own separate failure mode, covered in why a CB1241-driven V20 takes no HMI speed entry. Work the checks in order and let r0772.2 tell you which side of the terminal the problem sits on.
What the Cn002 acknowledge path needs #
In the reported setup, connection macro Cn002 is selected after a factory reset and quick commissioning, terminal 10 works as DI3, and the fault-acknowledge function sits on that input through P0703[0] = 9. The operating instructions make the clearing sequence explicit: remove the condition that raised the fault, then acknowledge it externally, where an input has been set up for the job. The assignment alone clears nothing; it only names the input that will carry the acknowledge once everything else is right.
One precondition no parameter supplies: the fault's cause must be gone. The drive will not wipe a trip whose condition still stands, and it should not — the acknowledge re-enables the drive, so confirm the machine is safe to restart before you pulse DI3.
A factory reset and quick commissioning also rewrite the terminal assignments, so re-read the digital input parameters in the drive as they stand today. What was set before the reset is history; the values in the drive now are what count.
Why the terminal-to-earth reading is not proof #
The measurement that convinces most reports — meter from terminal 10 to the panel earth with the output on, and watch the full output voltage appear — tests the wrong pair. A digital input is a series circuit: current leaves the PLC output, enters the drive at the input terminal, and must leave again through the drive's common terminal to return to the PLC. What the input responds to is the voltage across its own pair, terminal to common, never terminal to earth. Without a return path the pair develops no operating voltage, and the drive ignores DI3 completely while the earth-referenced meter still shows a confident number. That reading proves the PLC side is live; it says nothing about the drive's side of the loop.
Trace the acknowledge signal in order #
Five checks settle it:
- Clear the fault cause at its source — the tripped device, the overloaded machine, whatever raised the fault. An acknowledge forced over an active condition will not stick, and forcing one is not safe.
- Re-read the input assignments in the drive now, after the reset and quick commissioning:
P0703[0] = 9on DI3 at terminal 10. Settings from before the reset are not evidence. - Confirm or fit the bond between the PLC common and the drive common. One detail from the reported setup matters here: DI1 already runs the drive from the same PLC, and where DI1 and DI3 share one input common, a working DI1 is itself evidence that the common exists — which shifts suspicion toward the DI3 wire and its terminal. Where inputs are fed in separate groups, each group needs its own reference check.
- Toggle the PLC output to terminal 10 and watch r0772.2 in the drive. The bit must change with every off-on transition. This is the drive-side twin of tracing an HMI command that never reaches the PLC output: prove the signal at each boundary instead of assuming the last link works.
- Split on the result. r0772.2 static means the drive never sees DI3 and the external path is broken. r0772.2 following the output means the path is proven and the fault state itself refuses to clear.
Worked example: 24 V to earth, 0.3 V to the drive common #
The case as reported: a V20 on Cn002, DI3 at terminal 10 carrying the acknowledge through P0703[0] = 9, an S7-300 digital output pulsing terminal 10, and a confirmed voltage at the input — yet the fault stays latched.
Inputs, with their sources:
- Output voltage, ON state: 24 V DC — the S7-300 output level, the value reported present at DI3.
- Meter reading, DI3 to machine earth, output ON: the same value, confirmed in the reported setup, and exactly the reading that misleads.
- Meter reading, DI3 to the drive common terminal, output ON: 0.3 V DC — an example measurement for an unbonded pair, where only stray and leakage potential appears.
- Meter reading, DI3 to the drive common terminal, output OFF: 0 V DC — example measurement.
Rule in words: a digital input responds to the voltage across its own pair — input terminal to input common — so the swing the drive can act on is the ON reading minus the OFF reading on that pair, not the terminal-to-earth figure.
Arithmetic:
- Swing on the input pair: 0.3 V DC − 0 V DC = 0.3 V DC, against the full 24 V the output delivers: 0.3 ÷ 24 = 0.0125, so the drive sees about 1 percent of the change it is being asked to register.
- Terminal-to-earth comparison on the same ON state: it matches the output level exactly, and it moves nothing in the drive.
Result: r0772.2 never changes. The drive never sees the acknowledge, and the latched fault outlives every pulse.
Decision: a proven input pair swings by the full output voltage between OFF and ON; this pair swings 0.3 V DC, about one percent of that, so the loop has no return path. Fit the bond between the two commons. Re-meter afterwards and expect the pair to swing the full output voltage with r0772.2 following every toggle; once it does, a pulse after the cause is cleared acknowledges the fault.
If r0772.2 follows but the fault stays #
Then the wiring argument is closed: the drive receives the acknowledge command. Two possibilities remain. First, the cause is not actually gone — re-verify it at the source, not at the drive, because a latched trip can survive on a condition hiding downstream of whatever was tightened or replaced. Second, the fault itself is the refusing party. The reported experience is blunt on this point: with the input state proven and the cause confirmed removed, a fault that still will not acknowledge is a drive-side problem, not an input-assignment one. Stop re-terminating the cable at that point; the remaining checks are the fault code's own clearing rules and the drive itself.
The decision for each case #
- r0772.2 static while the output toggles: the external path is broken. Fit or verify the common bond, then meter the input pair for the full output swing; when DI1 already proves the common, the DI3 conductor and its terminal are the unique suspects left.
- r0772.2 follows and the acknowledge now clears: the repair is proven — the shared reference was the fault.
- r0772.2 follows, cause confirmed gone, fault still latched: the fault state is the problem, not the input path. Chase the fault code's clearing rules, not the wiring.
In the reported setup — input voltage confirmed, the P0703 assignment standing, DI1 running the drive — the order above is the answer, and the single most likely fix is step 3: tie the PLC common to the drive common, then prove the acknowledge at r0772.2 before touching anything else.
Questions asked
Which faults will DI3 never acknowledge, no matter what I do with the input?
Some fault codes need a power cycle to acknowledge; no digital input pulse clears them. When r0772.2 follows the PLC output and the cause is genuinely gone, look up the active fault code in the manual's fault and warning list: entries marked as needing a power cycle are cleared by switching the drive off and back on, not by pulsing terminal 10 again.
Can I acknowledge from the keypad to test the acknowledge path?
Yes, and it makes a clean fork in the diagnosis. With the cause removed, acknowledge from the drive's own panel first. If the panel acknowledge clears the fault but the DI3 pulse does not, the drive logic is healthy and the problem stays outside: the wiring, the PLC output or the shared reference. If neither path clears it, the fault state itself is the problem.
DI1 runs the drive from the same PLC output card. Does that prove the DI3 wiring is good?
No. Each digital input is its own terminal, its own wire and its own status bit, so a working DI1 proves the PLC supply and one cable pair and nothing about terminal 10. What a working DI1 does tell you, where both inputs share one common terminal, is that the shared reference exists — which moves the suspicion to the DI3 conductor, its terminal or the fault state. Verify DI3 at its own bit either way.