Troubleshooting
Why V90 servo drives run alone but not together on Modbus RTU
Short answer
Each V90 answers alone because a single-drive test gives it the whole bus; the thirteen-drive network fails because one RS-485 master port holds one Modbus RTU request at a time and the schedule or the bus wiring breaks that. Fix it in order: unique addresses 1-13, termination at the two bus ends only, one transaction completed or errored before the next, then a measured round. The 38.4 to 115.2 kbit/s change triples wire speed, not the round.
On this page
Thirteen V90 servo drives that each run alone over Modbus RTU fail as a network for one structural reason: an RS-485 master port holds exactly one request at a time, and something in your multi-drive setup — overlapping requests, a terminator on every node instead of the two ends, or a duplicated address — breaks that single-exchange discipline. Fix it in this order: unique addresses 1 through 13, termination at the two physical bus ends only, one transaction completed or errored before the next is sent, then a measured round time for the whole network. Raising the bit rate triples the wire speed; it does not triple the polling round, and it cannot repair a wiring or addressing fault.
Why one drive answers and the network does not #
The Modbus over Serial Line specification permits one master on the bus, and slaves speak only when addressed, one transaction at a time. A single-drive test satisfies that trivially: two devices, a short cable, nothing else loading the line. Your thirteen-drive test adds every other drive's input loading, the cable's stubs and ends, and — most often — a master program that fires the next request before the last one has finished. That each drive works on its own proves its RS485 port, its framing and its register set; it proves nothing about the bus as built or about the master's schedule.
Three different failures hide behind a network that will not run, and each has its own fix: no valid replies once a second node joins, which is a bus build; valid replies with no motion, which is enable, fault or command-source state; valid motion arriving late and staggered, which is schedule. Before changing anything, record the first failing address, the transaction that was on the wire, and your master block's completion and error status — motor movement is the worst diagnostic instrument on this bench.
Work the bus in this order #
- Give every drive its own address. Set addresses locally, one drive at a time, and expect 1 through 13 with no repeats, whatever ordering number sits on each drive. A duplicate answers for its twin, and the collision looks like random faults that move between drives.
- Match framing everywhere. Your master and all thirteen drives need the same baud rate, parity and stop bits. A parity or stop-bit mismatch reads as silence or garbage, often at exactly one address.
- Build one line, not a tree. Run the bus from the master through each drive in sequence — no star branches, no long stubs — keep A and B at the same polarity at every tap, and keep the shield continuous, bonded at one point. The V90's RS485 port is the 9-pin SUB-D socket X12.
- Terminate the two physical ends only. A terminator on every node loads the line until even short frames fail. On the drive end nodes, set termination the way that drive's interface instructions specify; on the master end, a connector with separate line-in and line-out terminals lets the bus pass through cleanly.
- Baseline with status reads and motion inhibited. Poll one safe status register from every address until exchanges repeat cleanly, and enable motion only after every address answers on demand.
Leave the drives disabled through all of this: a speed reference arriving at thirteen enabled servos mid-commissioning is live machinery, and the machine's safety functions must be proven separately from this work.
Serialize the master program #
Siemens' application example for the V90 over Modbus (Entry ID 109480267) runs controlled positioning and speed control from an S7-1200-class master across the drive's RS485 port, and its sequence extends to thirteen addresses with one rule added: one outstanding transaction. While a request is active, keep its slave address and data stable; trigger the next request only from the master block's completion or error output. Give every transaction a bounded timeout and a retry cap, so a powered-down drive costs its timeout once, not the whole round.
On the hardware: a CPU 1217C with a CB1241 board and the same CPU with a CM1241 module are separate serial options. Configure and initialize the port that is actually wired before the first request, because a mismatched port fails on the first exchange.
Hold speed-reference writes behind the status reads in the round, on the pattern in speeding up Modbus RTU writes behind polled reads, and step the whole schedule the way it is laid out in how to poll many Modbus RTU slaves from one serial master.
Wire time for one polling round over 13 drives at 38.4 kbit/s #
This is your case: thirteen drives, each polled once per round with a single-register write and its echo. The inputs:
- Thirteen exchanges per round — one per drive, the network under commissioning.
- An 8-byte request and an 8-byte response echo per exchange — Modbus RTU framing for a single-register write (address, function, register, value, CRC).
- Eleven bits per character — start, 8 data, even parity, stop — the Modbus RTU character frame.
- 38.4 kbit/s — the lower of the two rates you have already tried.
- A 3.5-character silent interval between frames — the Modbus over Serial Line specification's end-of-frame quiet time.
- Not included: each drive's internal answer time, which is device-specific and must be measured on your real network.
The rule in words: round wire time equals the number of exchanges times (request transmission + response transmission + one silent interval). The arithmetic:
- Character time: 11 bits ÷ 38,400 bit/s = 286.5 µs
- One frame, 8 characters: 8 × 286.5 µs = 2292 µs ≈ 2.29 ms
- Silent interval: 3.5 × 286.5 µs = 1003 µs ≈ 1.00 ms
- One exchange: 2.29 + 2.29 + 1.00 = 5.58 ms
- One round, 13 exchanges: 13 × 5.58 ms = 72.5 ms
At 115.2 kbit/s the same arithmetic gives 95.5 µs per character, 1.86 ms per exchange and 24.2 ms per round — exactly threefold faster on the wire, because 115,200 is three times 38,400.
The result: 72.5 ms of pure wire time per round at 38.4 kbit/s, 24.2 ms at 115.2 kbit/s, with each drive's answer time added on top thirteen times over.
The decision: wire time is the floor, not the round. If the measured round — wire time plus thirteen drive answer times — exceeds the update interval your motion actually needs, trim the poll first: fewer registers per exchange and reference writes held behind status reads shrink the round at any rate. Take the faster rate second, and expect less than a threefold gain on the whole round, because drive answer time and program time do not shrink with the wire. If the measured round fits the machine's update interval, the rate setting is done. The wider effect of one port's round time is laid out in why Modbus RTU drive polling on one serial port is slow.
Failure patterns and the decision for each #
| Symptom on the thirteen-drive network | First cause to check | Decision |
|---|---|---|
| Communication that works alone dies when a second node joins | Duplicate address, terminator on every node, star branch or swapped A/B | Unique addresses, one line, termination at the two ends only — leave the rate alone |
| Replies are valid but drives stay still | Enable chain, active fault, or the drive still following its local command source | Fix the controls state: a drive that answers a write while faulted or on its local source is not a comms failure |
| One address never answers | Framing mismatch on that drive, its tap wiring, or an unsupported register in the request | Match framing and verify registers against that drive's list before blaming the bus |
| Failures move between addresses | Requests overlapping on the port, or retries from an earlier timeout still in flight | Serialize: one outstanding transaction, bounded timeout, capped retries |
| All drives reply, motors run late and out of step | The round exceeds the machine's update interval | Measure the round and apply the worked example's decision |
Commit the three diagnoses before enabling anything: dead-when-a-second-node-joins is a bus build, silent-but-valid is a controls state, late is a schedule. The rate setting belongs to the third case only.
Acceptance before any drive turns #
With the schedule serialized, log the master's completion and error counts across many full rounds: zero unexpected timeouts and a repeatable round time are the pass mark. Then enable one drive at a time through the network commands, confirming each accepts its reference and reports the expected status before the next joins.
The decisions in one place: a network that dies when a second node joins is fixed with unique addresses, one line and two-end termination; valid replies without motion are fixed in the drive's command source, enable chain and fault state; late motion is fixed by measuring the round and, only if the round misses the machine's update interval, by trimming the poll and then taking the faster rate. Change the rate last, because it scales the wire time threefold and nothing else.
Questions asked
Can several Modbus master calls run at the same time on one RS-485 port?
No. The port carries one transaction at a time; overlapping calls come back with busy or error status and stall the round. Step a single master call through the slave addresses, or gate several calls so the next starts only when the previous completes or reports an error. Keep the active call's slave address and data stable until it finishes, because changing them mid-transaction corrupts the exchange.
Does raising the baud rate fix a thirteen-drive network that fails?
It helps a slow round and repairs nothing. The faster setting triples the wire speed and nothing else: drive answer time, program scan and timeout waits are unchanged, so the whole round gains less than a factor of three. On this network the wire time alone falls from about 72.5 ms to about 24.2 ms per round; if your machine needs updates faster than 24.2 ms of wire time plus drive answer time, one port cannot serve it at any rate. Serialize first, measure second, change the rate last.
Does the drive with the different ordering number need different settings?
No. Give it the next free address, match the framing the master uses, and terminate it only if it sits at a physical end of the bus. Before it joins the schedule, confirm from its own register list that every address the round reads and writes exists there, and watch its first few exchanges specifically. A register the drive does not support returns an exception, and an unscheduled exception can look exactly like a random network fault.
What happens to the round when one drive is powered down?
With a bounded timeout and a retry cap, the master skips that address after its timeout expires and finishes the remaining twelve. Add the timeout times the retry count into the round time for every round while the drive is down, and log the error so the gap is visible. Without a cap, one dead drive spends the whole round in repeated timeouts while eleven healthy drives wait.
Does it matter whether the RS-485 port is a CB1241 board or a CM1241 module?
Both are S7-1200 serial options and either can run this master. What matters is that the project configures and initializes the port that is actually wired, and that every drive's framing matches it. If a project carries both, prepare the Modbus configuration for the wired port before the first request, because an uninitialized or wrong port fails on the very first exchange, which looks like a dead network rather than a configuration slip.