Troubleshooting
Why PLC-5 MSG fails when DH+ is split through a ControlLogix rack
Short answer
A PLC-5 MSG sends to a station number on its own DH+ wire, so once the peer sits on a second segment behind the ControlLogix chassis the message has no route, and the bridging module answers with the routing-failure status the PLC-5 displays as D000 hex. Restoring the direct DH+ link brought the instructions back; keeping the split means moving the transfer into the ControlLogix processor.

On this page
When one DH+ link becomes two, a PLC-5 MSG instruction does not follow the cable. The instruction transmits on its own channel to a station number, and a station number names a node on the sender's wire, not a route through an intermediate chassis. With the PLC-5/40 on one segment and the PLC-5/80 on the other, the message goes out on the local wire, the peer is not on it, and the DH+/RIO module answers with its routing-failure status, D0 hex, which the PLC-5 displays as D000 hex in the message's error word. Unchanged target-device and node settings cannot repair that. Two designs work: restore the direct DH+ link between the controllers, or move the transfer into the ControlLogix processor.
The split removed the path the message uses #
A PLC-5 MSG aimed at a DH+ peer carries a target device, a station number and a channel. All three describe the local wire. Before the change both controllers shared one link, so a message to the partner's station crossed a single cable and arrived. Now each controller is alone on its own segment, the two segments meet only inside the ControlLogix chassis, one per DH+/RIO module, with the Ethernet module alongside for the SCADA clients, and the instruction still transmits on the sender's wire, addressed to a station that is no longer there.
The 1756-DHRIO user manual (1756-UM514) documents the module's side of this: a DH+ message it cannot route comes back with the routing-failure status named above, and the PLC-5 passes it into the message's error word. That code, read in RSLogix 5, is the fingerprint of the fault. The split was made to speed the network up, but the analog exchange is precisely the traffic that now has to cross segments, so it gained nothing and lost its path.
Prove each segment before you chase the route #
Work through these checks in order and write each result down:
- Connect a DH+ interface to segment one and browse it with the matching RSLinx driver.
- Go online with the PLC-5/40 through that connection; an icon in the browse is not a usable programming connection.
- Record the station number the browse shows and the number base the tool is using.
- Repeat on segment two with the PLC-5/80.
- Open the failing MSG in RSLogix 5 and read its error word with both segments powered.
Two results decide where you stand. A controller absent from its own segment's browse has a local problem, meaning channel configuration, cable or termination, and you fix that before touching any routing question. Both controllers reachable on their own segments while the MSG stays down means the fault sits between the networks: local communication is proven, and the cross-segment path is what does not exist for a PLC-5 message.
Two limits on what a browse proves. The workstation enters through its own interface, often the Ethernet module and the chassis, so its route is not the message's route, and a good browse is not a PLC-to-PLC test. And some RSLinx releases show DH+ station numbers in octal while other tools show decimal, so note the base before comparing digits; the conversion is worked out below.
Worked example: the PLC-5/40 to PLC-5/80 message on two DH+ segments #
Inputs, all from your split network and the module documentation:
- Sender: a PLC-5/40, the only PLC on segment one.
- Receiver: a PLC-5/80, the only PLC on segment two.
- Each segment lands on its own 1756-DHRIO in the ControlLogix chassis; the Ethernet module in the same chassis serves the SCADA clients.
- Error word on the failing instruction: D000 hex, the PLC-5's display of the module's D0 hex routing-failure status (1756-UM514).
- Station numbers for the arithmetic, taken as an example: the PLC-5/80 is configured as station 47 octal, the MSG target points at 47, and the workstation browse lists that same controller as 39.
The rule in words: PLC-5 station addresses on DH+ are octal, 00 to 77 for the 64 stations a link can hold. A display in another base must be converted before it is compared with the message's target, and only a mismatch after conversion is an addressing fault.
The arithmetic:
- 47 octal = (4 x 8) + 7 = 32 + 7 = 39 decimal, so the browse and the MSG target are the same station.
- The reverse trap: 47 decimal is 57 octal, because 5 x 8 + 7 = 47, which would be a different station entirely.
Result: the addressing is right, both controllers pass their local browse, and the error word carries the bridging module's routing-failure code, so the message is correctly addressed and undeliverable.
Decision: when the error word shows that code while both controllers are locally reachable, stop editing the message. The first is already proven on this network; the second is the alternative below.
What each observation tells you #
| Observation | What it means | Next step |
|---|---|---|
| A controller is missing from its own segment's browse | Local channel, cable or termination problem | Restore local visibility before testing any route |
| Both controllers browse and go online locally, MSG still down | The cross-segment path does not exist for a PLC-5 message | Restore the direct DH+ link or move the transfer into the ControlLogix CPU |
| The error word shows the routing-failure status | The bridging module could not route the message | Stop editing target fields and make the path decision |
| Station digits differ between two tools | A number-base difference, not a configuration change | Convert both readings to octal and compare again |
| SCADA reaches both PLCs while the MSG fails | Different paths: client traffic through the Ethernet module, no PLC-to-PLC path | Do not count the SCADA screen as proof of the peer route |
| Messages resume when the direct wire returns | The fault was the segmented arrangement, not the program | Keep the peer link or commission the processor transfer |
Every row except the local-visibility and number-base rows ends in the same decision, because the failure has one root: a correctly addressed message with no way across the chassis.
Leave the target device and the analog wiring alone #
The target device and node were checked and had not changed, which is exactly what this failure predicts. Those fields name the peer correctly; they carry no route for a second network. Set to anything else they would be wrong; set as they are, the message is correctly addressed and undeliverable. The instruction was built for a directly connected peer and still assumes one.
Do not rewire around it either. Splitting the analog signals out to spare I/O cards replaces a communication fault with a measurement redesign, adding wiring, loading, scaling and signal-isolation questions, while the data transfer itself was never the problem. And leave the scaling untouched until delivery is restored: interpret the values only after they arrive.
Two designs that work #
- Restore the direct DH+ link between the two controllers. This is the arrangement your network already proved, because the instructions resumed the moment the wire was back. Peer-to-peer PLC-5 messaging belongs on one DH+ segment, the same conclusion reached in DH+ or Profibus for peer-to-peer PLC-5 messaging, so treat the peer link as permanent rather than as a temporary bypass.
- Keep the split and hand the transfer to the ControlLogix processor. The CPU messages each PLC-5 across the DH+/RIO channel serving that controller's segment, reads the analog words from one, writes them to the other, and the two PLC-5 MSG instructions are retired. The route from a Logix processor to a PLC-5 on DH+ is configured, not assumed: how to route a ControlLogix MSG to a PLC-5 over DH+ shows the path setup, and the data then crosses the backplane inside the controller, where the module-to-module routing limit no longer applies.
Either design removes the dependency the split created: a PLC-5 message that must leave its own wire.
Questions asked
Can the ControlLogix processor take over the transfer from both PLC-5 controllers?
Yes. The processor runs one message to the PLC-5/40 and one to the PLC-5/80, each across the DH+/RIO channel that serves that controller's segment, and copies the analog words between the two over the backplane. Trigger the read first and the write when the read completes, so the receiving controller never gets a half-updated set. Retire the two PLC-5 instructions once the new path is proven. The update rate is then set by how often the controller runs that pair, not by token rotation on either segment.
Why does the SCADA PC still reach both PLCs while the MSG instructions fail?
The SCADA route runs the other way through the chassis. The PC connects to the Ethernet module, and its request is bridged down the backplane to a DH+/RIO module and out to the PLC, a client-to-DH+ direction the chassis supports. The failed MSG is born on a DH+ wire as a PLC-5 message, and no module re-originates it onto the second segment. A live SCADA screen beside a dead MSG instruction is therefore consistent, not contradictory.
Does splitting the DH+ network actually speed up the analog exchange?
No. A DH+ link passes a token from station to station, so a split shortens the wait only for traffic that starts and ends on the same segment. The analog exchange is exactly the traffic that now crosses segments, so it gained nothing and lost the direct wire. With one or two controllers and a programming station on a link, token rotation is already short; the shared link was unlikely to be the slow part of the update.
Can both PLCs share one segment while the rest of the network stays split?
Yes, and it is worth doing when the second segment carries other stations. Put the PLC-5/40 and the PLC-5/80 back on one DH+ link so the peer transfer crosses a single wire, and keep the remaining nodes on the other segment so their traffic stays off the peer link. Each segment keeps its own cable, termination and DH+/RIO channel, and the chassis still reaches both through its two modules.