Why a download loses DH+ communication on an SLC 500 network
Short answer
A download writes the DH+ channel configuration along with the program, so a project whose node address or baud rate differs from the running controller takes the target off your route when the transfer ends. That, not a battery or factory defaults, is the usual cause when uploads and online sessions work but downloads end in Communication Lost; compare the settings first, then the wiring.

On this page
- A working upload proves less than it seems
- Rule out the familiar fixes that do not fit
- Read the symptom before changing anything
- Capture the state, then download once, on purpose
- Working the ten-controller network at 230 kbps
- Correct the configuration before you test the wire
- Prove the repair and file the settings
- Questions asked
A download carries more than the program: it also carries the DH+ communication configuration stored in the project file. When the transfer ends, the processor restarts its channel with whatever node address and baud rate that file holds. If those differ from the settings the controller was running, the target comes back on new terms while the PC keeps polling the old ones, and the software reports "Communication Lost". In most cases the processor is fine and nothing reset to factory defaults — your route to it broke. Compare the project's channel configuration with the running controller before you touch a battery, a terminator or the baud rate; the wiring and a controlled rate test come after that comparison, in that order.
A working upload proves less than it seems #
Uploads and online sessions prove the path that exists right now: your PC interface at the trunk's baud rate, talking to a station at its current address. A download rides the same path but writes the channel configuration along with the logic, and those settings take effect when the processor restarts communication at the end of the transfer. Everything the successful uploads proved — cable continuity, termination, a reachable address — was true of the old settings. The download is the one operation that can change them.
Treat the reported factory default mode as a symptom, not a finding. From a PC that has lost its route, a processor waiting in Program mode, a processor holding a fault, a processor with no program and a processor answering at a new address all look identical: nothing at the expected station. Reach the controller by another supported path, read its mode, fault status and channel configuration, and let that reading decide which condition you actually have.
Rule out the familiar fixes that do not fit #
- Replacing the battery. Memory retention is the suspect only when configuration disappears after power removal, not after a download. Keep retention as its own separate test.
- Writing the node address with first-scan logic. First-scan bits execute only when a valid program is running, and a failed download can leave the processor in Program mode with nothing executing at all. Logic cannot repair the configuration it needs in order to run.
- Power cycling immediately. That can erase the mode and fault information that identifies the branch. Record the state first; cycle later, and only as a deliberate test.
- Dropping the baud rate on the spot. It is a valid controlled test, but it belongs last, because it does nothing for a project that carries the wrong address.
Read the symptom before changing anything #
Four outcomes cover almost every version of this call, and each points somewhere different.
| After the download | Most likely cause | The check that decides it |
|---|---|---|
| Target gone at its old address; every other station fine | The downloaded settings changed its address or rate | Compare the project's channel configuration with the recorded running values, then browse again |
| Target answers but waits in Program mode | The transfer sequence changed the operating mode | Read the mode and confirm the intended program is present |
| Target reconnects with a fault or an empty program | The transfer failed partway, or the processor faulted | Record the fault and inspect program contents |
| Several stations turn intermittent | Wiring, termination or an interface problem older than the download | Compare station behavior and test the physical trunk |
Capture the state, then download once, on purpose #
Take the affected controller out of production under your site's maintenance procedure: a download stops control execution and can change what the outputs do, so the process must be held safe by other means while you test.
- Upload and save the running program before anything else, so a failed test costs you nothing — the procedure is to back up an SLC 500 program by upload before you lose it.
- Record the controller as it is now: DH+ node address in octal, baud rate, processor type, operating mode and any fault on the display.
- Open the offline project you intend to download and read its DH+ channel configuration next to those recorded values — node address first, baud rate second.
- Record the PC side: the interface's own address, the rate it is set to, and every hop in the route to the target.
- Note when "Communication Lost" appears. An error before any data moves points at the project or the transfer path, which is the branch covered by resolving a project that compiles but will not transfer to the PLC. A stall mid-transfer that never reaches the channel reconfiguration — a download stuck waiting for the target to reboot is one form — is a path problem too. An error that lands only at reconnection, after the progress window finishes, is the signature of settings that changed underneath the PC's route.
Working the ten-controller network at 230 kbps #
The inputs, each with its source:
- Stations sharing one trunk: ten SLC 500 controllers plus one PC interface — your network in this case.
- Running baud rate: 230 kbps — the rate the trunk uses today.
- Documented standard rate: 57.6 kb/s, at which a DH+ trunk may run up to 10,000 ft (3,048 m) — from the DH+ network overview documentation.
- Station addressing: octal 00 through 77 — the DH+ address field.
The rule in words: one trunk carries one baud rate, every station needs a unique octal address, and any lower-rate test is judged against the standard rate and its documented trunk length.
The arithmetic:
- Addresses in use: 10 controllers + 1 PC interface = 11 stations.
- Field capacity: the top address, octal 77, is 7 × 8 + 7 = 63 in decimal, so the field holds 64 addresses. 11 of 64 are used — exhaustion is impossible here, so a duplicate can only come from a copied project.
- Test window: 230 kbps ÷ 57.6 kb/s ≈ 4, so the same transfer needs about four times the wire time at the standard rate. A download that takes one minute today budgets four minutes for the test.
- Trunk: measure it end to end and compare with the 10,000 ft (3,048 m) documented at the standard rate.
The result: with 11 addresses inside a 64-address field and a trunk you can measure in ten minutes, neither address space nor distance explains the failure. The project's channel settings stay the prime suspect.
The decision: if the offline project's node address equals any other station's, or its baud rate is not the one the trunk runs, correct the project — and the PC route, if you mean to keep the new values — before the next download; that correction alone clears this symptom. Run the lower-rate test only when both settings already match and the transfer still fails, inside a window of about four times the last good transfer time. A trunk longer than 10,000 ft (3,048 m) puts even the standard rate outside its documented limit, so fix the topology before any test.
Correct the configuration before you test the wire #
- Set the project's node address and baud rate to the values planned for that controller, and confirm the address exists nowhere else on the trunk. Resolve duplicates before reconnecting anything.
- If you mean to change the settings deliberately, build the matching PC route before the download, not after the failure.
- Download over a stable, supported programming path, reconnect on the resulting settings, and only then request Run mode.
- If the settings matched and the transfer still failed, judge the installed trunk against the documentation for the actual interface and processor. How the network is configured determines the permissible trunk and drop lengths, so check continuity, the drop arrangement, shields and the termination at each end of the trunk. A daisy-chained trunk is the intended topology; unintended branches and damaged connectors are the defect.
- Lower the rate only during a coordinated outage, and change every station together — controllers and PC interface alike. Transfers that succeed at the lower rate prove the physical layer is marginal; the slow rate masks the defect without naming it, so keep hunting for the bad connection.
Prove the repair and file the settings #
- Read back the node address and baud rate and compare them with the plan.
- Go online, confirm the intended program is present, clear any processor fault, and validate the machine's inputs, outputs and interlocks under its restart procedure before it goes back to service.
- Repeat the download under normal network conditions, then confirm the other nine controllers still answer.
- If retention was ever part of the complaint, run a separate controlled power-cycle test and compare what comes back.
- Record whether the correction fixed the transfer, the reconnection, or both — a rebuilt route is not a repaired network. File each controller's current project with its channel settings noted, so the next download comes from the right file.
Questions asked
Does an SLC 500 processor lose its DH+ node address when power is removed?
Not while its memory retention is healthy. The node address is part of the channel configuration held in battery-backed memory, and processors that are powered down every shift keep their addresses for years. If a plain power cycle, with no download involved, erases the address or the program, retention has failed: replace the processor battery, then prove the fix with a controlled power-cycle test. That is a separate fault from losing access after a download, and the two should not share one investigation.
Can first-scan ladder logic write the node address back after a failed download?
No, and it cannot be made to. The DH+ node address is a channel configuration setting, not a data-table word, and no ladder instruction rewrites channel configuration while the processor runs. A first-scan bit is also useless after a failed download, because first-scan logic only executes when a valid program is running, exactly what the failed transfer may have removed. Put the correct address in the project's channel configuration and in the PC's route; logic is the wrong layer for this repair.
Can I slow only the PC interface and leave the ten controllers at their current rate?
No, because DH+ is a token-passing network and the token itself travels at the configured baud rate. Stations set to different rates do not communicate poorly; they do not communicate at all, so the production-monitor traffic from the other controllers would stop along with your programming access. A rate change is an all-stations change, every controller and the PC interface, switched together during one coordinated outage.
What does a duplicate node address look like on the trunk?
Erratic. Both stations answer to one octal address, so token passing stumbles, connections open intermittently or against the wrong processor, and the rest of the network sees unexplained gaps. Because your uploads worked before the download, a duplicate that appears immediately after one almost always arrived inside a copied project file that kept its old address. List the addresses of all ten stations before the next download and confirm the target's address is the only one of its kind.
The target is silent on DH+ now, so how do I reach it again?
Through a different door. If the download changed the processor's baud rate, the controller is alive but deaf to a trunk running the old rate, and no amount of browsing will show it. Connect with a supported alternate programming path for that exact processor, read the channel configuration it now holds, write the planned address and rate back, and reconnect on DH+. Do not keep downloading over the route that just failed; each attempt rewrites the same wrong settings.