Industrial networks Published 8 min read

Short answer

Use DH+ for the ten-controller peer backbone: every PLC-5/30 has the link on its 3-pin connector and the MSG instruction is the native mechanism, while Profibus DP is a master/slave bus for decentralized peripherals. Add Profibus only as a device-level segment where an instrument demands it.

On this page
  1. Which network should ten PLC-5/30s use for peer-to-peer messaging?
  2. Is Profibus DP actually a peer-to-peer network?
  3. What does each controller need before the DH+ messages work?
  4. How many message paths does a ten-controller network need?
  5. Can the DH+ trunk carry ten controllers plus HMIs and programming terminals?
  6. Where do Profibus-only scales, recorders and HMIs fit?
  7. Does choosing DH+ lock the plant into one vendor?
  8. What should the final design be for these ten controllers?
  9. Questions asked

Run the peer-to-peer backbone on DH+. Each of the ten PLC-5/30 processors already carries a DH+ interface on its 3-pin connector, the MSG instruction is the built-in mechanism for peer data exchange, and Profibus DP is a master/slave bus for decentralized peripherals rather than a controller-messaging network. The decision that shapes the plant is not which name to give the network but how the message paths are owned and scheduled on it, and where any Profibus devices get a segment of their own.

Which network should ten PLC-5/30s use for peer-to-peer messaging? #

DH+, without qualification for this machine: the link is built into all ten processors, peer messaging is a native service, and the only things you buy are cable, connectors and termination, while Profibus DP would need a module in every chassis and still would not be a peer network.

On DH+ the ten controllers share one trunk and any station can initiate a message to any other — that is what peer-to-peer means on this architecture. The interface is on the processor itself: publication 1785-6.8.5, Connecting PLC-5 Processors and SLC, documents the 3-pin connector and the requirement that the port be configured for DH+ operation before the link carries anything. Profibus, by contrast, means a scanner-class module in each chassis and a network that still organizes itself as masters polling slaves.

What the choice gives you DH+ Profibus DP
Who can start an exchange Any station, token passing A master; slaves answer polls
Interface on a PLC-5/30 Built-in 3-pin processor port Scanner module in each chassis
Controller-to-controller mechanism MSG instruction Not a protocol service; a master relays it
Physical layer Twinaxial trunk RS-485 two-wire
Top documented rate 230.4 kbps 12 Mbps
Stations per link 64 126
Designed role Controller messaging Decentralized peripherals and I/O

Is Profibus DP actually a peer-to-peer network? #

No: DP stands for decentralized peripherals, and the protocol defines masters that poll and slaves that answer, so two controllers on a DP bus exchange data only through a master's scan, never directly with each other.

A Class 1 master polls its configured slaves cyclically for I/O data, a Class 2 master reads, writes and diagnoses acyclically, and each slave device is described to the tooling by its GSD file. Two controllers that both hold master roles still have no direct data path between them: whatever one PLC needs from another must be scanned in by one master and written back out by the other. That scanner-to-slave pattern is exactly what configuring S7-300 PROFIBUS control for an MM420 drive shows end to end on a Siemens platform, and it is the right pattern — for drives and remote I/O, not for controller peer data.

The 12 Mbps figure is real but misdirected. It speeds the poll cycle between one master and its slaves; it does not create a service in which any of your ten PLC-5s hands a block to any other whenever its logic decides to.

What does each controller need before the DH+ messages work? #

Per PLC-5/30: the 3-pin DH+ connector on the processor wired to the trunk, a unique station address in the channel configuration, one baud rate matched across all ten stations, and MSG instructions in the programs — nothing else.

Setting Where it lives Commissioning check
Station address Channel configuration of each processor Unique across all ten; recorded in one schedule
Baud rate Same channel configuration Identical on every station, HMI and bridge on the trunk
Termination and shield Both physical ends of the trunk Installed to the drawing before energizing the segment

A duplicate station address produces unpredictable reachability that mimics a cable fault; a baud mismatch produces no communication at all. Because the medium is shared, bring the stations up progressively and confirm every earlier station stays reachable after each addition — a defect introduced with the sixth node shows up as more than a node-six problem.

How many message paths does a ten-controller network need? #

Not 90: a full mesh in which every PLC-5 sends to all nine others creates 10 × 9 = 90 directed MSG paths, and almost no line needs that — give each data block one owner and the count collapses to a planned handful.

The arithmetic first. Ten stations each sending to nine others is 10 × 9 = 90 directed paths to program, document, tune and troubleshoot. The fix is ownership.

Worked example, hub pattern: nine producing stations each own one 20-word status block and write it to the tenth station, a hub that assembles a 60-word line block and writes it back to the other nine. Inbound paths: 10 - 1 = 9. Outbound paths: 10 - 1 = 9. Total: 18 MSG paths instead of 90, a reduction of 72 paths, exactly 80%. Loading at a 2 s cycle: 9 × 20 words + 9 × 60 words = 180 + 540 = 720 words = 1,440 bytes per 2 s, which is 720 bytes/s, about 5.8 kbps of payload, roughly 2.5% of a 230.4 kbps trunk. The wire is not the constraint; what bounds your update rate is each processor servicing its message instructions within scan and the token rotation under real traffic, so measure received-data age rather than assume it.

Messaging pattern Directed MSG paths Arithmetic
Full mesh, everyone to everyone 90 10 × 9
Hub collects and republishes 18 (10 - 1) + (10 - 1)
One producer, nine consumers 9 1 × 9

Put a rolling heartbeat or sequence count inside every transmitted block so a receiver can tell fresh data from a value left behind when communication stops, and let that staleness decision — hold, degrade, stop — drive the application's response.

Can the DH+ trunk carry ten controllers plus HMIs and programming terminals? #

Yes, with a budget: DH+ is a shared token-passing trunk, so every station — HMIs and online programming sessions included — waits its turn, and the practical limit is token rotation time under real traffic, not address space.

Peer capability says who may initiate, not how soon a transfer lands. Each station transmits when the token reaches it, so rotation time grows with the number of active stations and with what they send; an HMI polling ten controllers and an online editing session ride the same rotation. The mechanism behind why online editing slows a DH+ network and how to fix it applies here: keep online edits off the production trunk when possible, and schedule peer transfers from the data age the process needs rather than how fast the program can retrigger.

A PC HMI joins the same link as one more station — the access routes are laid out in how to reach a PLC-5/30 DH+ network from a PC HMI driver — and a single bridge to the plant network keeps heavier supervisory traffic off the trunk entirely.

Where do Profibus-only scales, recorders and HMIs fit? #

On their own Profibus DP segment behind one scanner-class module in whichever chassis is nearest: the device list decides that, not the backbone — the peer network stays DH+, and DP exists in the plant only where a specific instrument forces it.

Device-level Profibus availability is real, and it is an argument about peripherals, not about the controller backbone. Where such instruments cluster, put one DP segment behind a scanner module in the nearest PLC-5 chassis: the scanner is the master, devices are configured from their GSD files, and their data lands in that controller's table and rides DH+ to whoever needs it.

Third-party scanner modules were built for the PLC-5 chassis because the processor itself has no Profibus port — an added module, added configuration and an added spare part per site that goes this way. Before buying any instrument, check its actual interface options: a scale, recorder or HMI that also offers DH+, serial or Ethernet connectivity never needs the DP segment at all.

Does choosing DH+ lock the plant into one vendor? #

For controller messaging on this installed base, yes — DH+ is a proprietary link, and that cost is real but smaller than the cost of forcing a peripheral bus to do peer messaging badly; the escape is a bridge, not a redesign.

Treat the question as migration planning rather than network selection. The native speakers of DH+ are a legacy controller family, so separate two decisions: what the ten PLC-5/30s use today, which is DH+ because it is built in and fits the job, and how the plant reads that data from the Ethernet side tomorrow, which is one bridge or gateway with message routing configured through it. New controllers join at the Ethernet layer and read the same data across the bridge; the trunk keeps working until each controller is replaced on its own schedule. Instruments never have to follow the backbone, so the lock-in never spreads beyond the controller family already installed.

What should the final design be for these ten controllers? #

Ten stations on one terminated DH+ trunk at the highest baud the route supports — 230.4 kbps on a short run, 115.2 or 57.6 kbps as it lengthens per the documented cable table — with one recorded address schedule, owned data blocks carrying heartbeats, and Profibus only where an instrument demands it.

Requirement Build Basis
Production data between the ten PLC-5/30s One DH+ trunk, MSG paths with owned blocks and heartbeats Native peer service; no module per station
An instrument that only offers Profibus DP One DP segment behind a scanner module in the nearest chassis DP's designed role is decentralized peripherals
A PC HMI or data station over the line Same trunk as a station, or one bridge to the plant network Keeps supervisory traffic reachable and bounded
Growth past 64 stations or controller replacement Bridge to the plant network now, migrate controllers one at a time Protects the backbone decision already made

Commission in this order:

  1. Confirm the address schedule and baud on all ten channels before any message logic runs.
  2. Terminate both trunk ends and check shield treatment against the installation drawing.
  3. Bring stations onto the trunk progressively, confirming reachability after each addition.
  4. Prove one MSG pair in a designated test area: change a value at the sender and confirm it, and only it, at the receiver.
  5. Add the remaining paths in groups, then measure received-data age under representative traffic with an HMI session active.
  6. Pull the test path under controlled commissioning conditions with the machine in a safe state, verify the heartbeat staleness response, then restore.

Questions asked

Can a PLC-5 write to another PLC-5's data table without the target running matching logic?

Yes. A peer DH+ message can be a read or a write: the initiating controller's MSG names the target station and data-table address, and the receiving PLC-5 needs no matching logic for the value to land. The receiver does need its own logic to know the data is fresh, which is why the heartbeat belongs inside the transmitted block.

How many more stations can join the DH+ trunk after the ten controllers?

The link is documented for 64 stations, so ten controllers leave 54 addresses for HMIs, programming terminals, bridges and future nodes. Addresses run octal 00 through 77, so record them as octal in one schedule. Every added station also lengthens token rotation, so spare addresses are cheaper than spare traffic.

Is Profibus DP at 12 Mbps a faster way to move data between the controllers?

No. The 12 Mbps speeds a master's poll of its assigned slaves, and controller-to-controller exchange is not one of those polls. PLC-5 peer data over DP would be collected by one master and reissued by another, adding scan latency and a second configuration to every transfer that DH+ performs with one MSG instruction.

What should the receiving controller do when a peer message stops arriving?

Treat the last value as stale, not as data. Check the heartbeat or sequence count in each received block on a timer, and drive the application's response, whether hold last state, degrade or stop, from that staleness decision. At the sender, read the message's done and error status before retriggering so failures are observed rather than overwritten.

Should instrument availability push the whole network toward Profibus?

No. Profibus-ready scales, drives and recorders argue for one DP segment where those instruments cluster, behind a scanner module in the nearest chassis, not for rebuilding the controller backbone around a bus that has no peer service. Buy each instrument for its measurement first and then match its interface; devices that also offer DH+, serial or Ethernet never need the segment.

Keep reading

  • Selection guide

    How to choose between Modbus, Profibus and CANopen

    Match the protocol to the PLC master that already exists, not to the datasheet that impressed you. Then fit the cable run to the bit rate, because CAN-based trunks shorten as speed rises, and mix protocols one segment at a time through gateways or the PLC itself. A fourteen-device example shows the arithmetic.

    Industrial networks

  • How-to

    How to route a ControlLogix MSG to a PLC-5 over DH+

    The CIP path is 1,5,2,10.60.28.60,1,2 and it ends at the 1756-DHRIO: out the local backplane to the ENBT/A in slot 5, over Ethernet to the bridge ENBT/A at 10.60.28.60, then across the bridge backplane to the DHRIO in slot 2. DH+ carries no CIP, so Channel A and DH+ node 67 are set on the message's communication tab, never appended to the path.

    Industrial networks

  • How-to

    Reach a safety PLC over EtherCAT EoE from a Windows PC

    Enable IP forwarding on both XF10 and eoe0 on the ctrlX CORE, activate the gateway's Virtual Ethernet port in the EtherCAT configuration, and add a persistent Windows route to 172.31.0.0/16 with the CORE's PC-side address as next hop. The safety tool then reaches the gateway over the EtherCAT cable with no separate service connection.