Troubleshooting
Studio 5000 reports host revision was not found for a drive
Short answer
Studio 5000 shows "Host revision 6.1 was not found" for two different reasons. A revision list that went blank after installing the drive AOP means a blocked registry pointer to the moved database files: rerun the installer with the permissions your workstation policy requires, or have the administrator repair the database location. If only the requested revision is missing, set the drive IP from its HIM and use Match Drive to upload the definition from the drive itself, with no download needed.

On this page
- Separate the blank list from the missing revision
- When the AOP install empties the revision list
- When only the requested revision is missing
- Give Studio 5000 a reachable drive first
- Pull the definition from the drive itself
- Worked example: a v30 project asking for 6.1 after AOP v15.00.01
- Verify before the machine runs again
- If the drive was swapped instead
- Questions asked
The message "Host revision 6.1 was not found" splits into two different faults, and the fix depends on which one you have. If the revision list was populated and went completely blank right after installing AOP v15.00.01, the drive databases moved on your computer and the registry pointer to the new location never landed: rerun the installer with the permissions your workstation policy requires, or have the administrator repair the database location. If the list is intact and only the requested revision is missing, you do not need any download. Set the drive IP address from its HIM, browse to it, and use Match Drive, or Upload in the Device Definition dialog in version 32, to pull the definition from the physical drive itself. Everything below works that split out.
Separate the blank list from the missing revision #
Open the drive's device definition in Studio 5000 and look at what the revision list shows. The four cases need different work:
- Revisions 1 through 5 were listed before the AOP install and no revisions appear after it: the workstation's database-location pointer is wrong. Skip firmware changes and database downloads for now.
- The list is populated and only 6.1 is absent: the installed database set lacks the requested host revision. Read the revision from the physical drive and match it.
- The drive can be browsed over EtherNet/IP but its definition will not open: the network path works and the workstation-side database is the fault.
- The drive does not appear in a browse at all: fix the IP configuration and the network path first, because no database repair restores communication.
When the AOP install empties the revision list #
AOP for PowerFlex Drives and SMCs (all Logix versions) v15.00.01 moves the drive databases on the computer. Its installer also tries to write a registry entry that points the software to the new location, and workstation security can block exactly that write while letting the rest of the installation finish. The package then reports as installed while Studio 5000 still reads a location that is now empty. Installing the All CCW and Logix Database Files package again does not help while the pointer is wrong, because the files land where the software is not looking.
Work the pointer branch in this order:
- Close Studio 5000 and any drive-configuration software.
- Confirm that AOP v15.00.01 is registered as installed.
- Check the installer result and the workstation security records for a blocked registry modification.
- Rerun the installer with the permissions your workstation policy requires, or have the administrator permit the registration action.
- Reopen Studio 5000 v30 and inspect the revision list.
A second virtual machine failing the same way does not rule this out: identical security controls or the same installation sequence blocks the same registry write in both environments. If the list stays empty after a clean rerun, do not guess the registry key or copy a value from another computer. The database-location entry is a vendor-supported fix, and the administrator should get the exact entry from the vendor's documented support channel rather than from memory.
When only the requested revision is missing #
Read the exact revision string from the drive, at the HIM or through a live network browse, and record it exactly. The distinction matters because the project message reports 6.1, while drive firmware on the download site is published as three-part tokens such as 6.001 and 7.001. Treat those as different revisions, not as spellings of one value.
The host database tells Logix Designer how to represent the drive definition for a given revision, and model, frame size, horsepower, voltage and firmware all shape that definition. A manually picked entry can therefore look plausible and still fail to match the physical drive.
The decision: if the drive reports the revision the project asks for, keep that firmware and obtain or upload the matching database. If the drive reports a different revision, correct the project's device definition by matching the real drive instead of scheduling a flash just to clear the dialog.
Give Studio 5000 a reachable drive first #
The match and upload route needs live EtherNet/IP communication, so prove the path before opening any dialog. Set or confirm the drive IP address at the HIM keypad; if the keypad pulls up a menu instead of entering digits, the page on PowerFlex HIM number keys opening a menu instead of an input covers that fault. Connect the drive to the intended network and browse to it from the engineering workstation. If the browse finds the drive, continue to the match. If it does not, the fault is the configured address, the workstation interface, the subnet relationship or the physical link, which is a communications branch rather than a database branch.
When you are online with the Logix project, right-clicking the network and choosing Discover Module finds the drive and adds it like an I/O module, with no chassis entry to create. Use discovery after the drive has a reachable address, not as a substitute for one.
Pull the definition from the drive itself #
Use the physical drive as the authority once it is reachable. That avoids reconciling revision, frame size, power rating and voltage by hand:
- Open the project and start the add-hardware workflow on the applicable network.
- Select the PowerFlex 525 device type.
- In version 30, choose Match Drive; an RSWho browse window opens.
- Select the physical drive and upload the database from it.
- Review the definition the upload produced before accepting it into the project.
In version 32 the dialog is named Device Definition and the resolving action is named Upload; follow the controls your installed version presents instead of hunting for a button name from another release. If the upload completes and the properties open, go to verification. If the drive is reachable but the upload will not start, return to the database-pointer branch, because the workstation still cannot see its own database set.
Worked example: a v30 project asking for 6.1 after AOP v15.00.01 #
The inputs, all from the case this fault came from: Studio 5000 v30 running in a virtual machine; a revision list that showed 1 through 5 before the install; AOP for PowerFlex Drives and SMCs (all Logix versions) v15.00.01, installed from the vendor's site; a project with three PowerFlex 525 drives on EtherNet/IP that reports "Host revision 6.1 was not found"; and the All CCW and Logix Database Files package, downloaded and installed with no change to the list.
The rule: count the revision entries before and after the event that changed the behavior, and let that count pick the branch. Before the install the list held 5 entries. After the install it held 0 entries. A drop from 5 to 0 across one event, the AOP installation and nothing else, puts this case in the blank-list branch. Had the count gone from 5 to 4 with only 6.1 absent, the same project would sit in the single-missing-revision branch instead, and the drive HIM would be the next stop.
The result: v15.00.01 moved the databases on the computer and the registry write that points Studio 5000 at the new location never landed, so the software reads an empty location. The project's 6.1 token is not the fault, and chasing a 6.1 or 7.001 download only changes the drive while the workstation fault stands.
The decision: stop trying firmware updates and database downloads. Rerun the installer with the permissions the workstation policy requires; if the list is still empty, have the administrator repair the database-location registry entry from the vendor's documented support. Once the list is populated, set each drive's IP from its HIM and use Match Drive to pull the definition from all three physical drives.
Verify before the machine runs again #
Do not stop when revisions merely reappear. Check the full engineering path:
- The properties open without the "host revision" message and the revision list is populated.
- The revision read from the physical drive matches the uploaded or matched definition exactly.
- The project keeps the matched device after you close and reopen it.
- A fresh browse resolves the project device to the intended physical drive.
A download into a drive stops it, so put the machine in a safe state before you accept any project change into the drive.
If the drive was swapped instead #
When the fault arrived because the drive hardware was replaced and the project's module definition no longer matches the firmware now installed on it, that is a replacement-firmware mismatch rather than a database problem. The walk-through of replacing a PowerFlex 753 on RSLogix 5000 v20 with a newer revision covers that case and how to bring the project definition onto the new drive.
Questions asked
How do I know which AOP version my drive and Logix Designer need?
The drive vendor publishes an AOP requirements document that maps each PowerFlex drive family and each Logix Designer or RSLogix release to the AOP version that supports it. Check that mapping before you install, because installing an AOP newer than your workflow expects is what moved the database files and emptied the revision list in this case.
Studio 5000 shows an internal state error while I work with the drive. Is that the same fault?
No. The vendor documents the internal state error as another client already accessing the drive over Ethernet. Disconnect the other external sessions to the drive and retry. It is a connection-ownership fault and has nothing to do with the revision database or the AOP installation.
Should I flash the drive to 7.001 to clear the message?
Not as a first step. Flashing changes a working device while the workstation may be the real fault, and a download into a drive stops it. Read the exact revision from the drive HIM first: if it matches what the project asks for, the missing piece is the workstation database, not the drive firmware, and Match Drive or Upload fixes it without touching the drive.
Do all three drives in my project need this repair?
One repair fixes the workstation, and each physical drive then gets its own definition. Once the revision list is populated, match each drive in turn: every upload takes the revision, frame size and configuration from that drive itself, so you never have to reconcile three sets of parameters by hand.