How-to
Replacing a PowerFlex 753 on RSLogix 5000 v20 with a newer revision
Short answer
Keep the replacement at revision 14 and change the engineering workstation, not the project: RSLogix 5000 v20 offers only the revisions in its installed drive database, which stops at 13 until that database is updated. Back up every port of the old drive with Connected Components Workbench or the HIM CopyCat function first, set electronic keying to compatible so cyclic I/O connects even while the AOP rejects the firmware, and recreate the I/O-tree module under the identical name so existing tags resolve.

On this page
- Why the project cannot see the newer revision
- Back up every port before you remove anything
- Update the workstation drive database
- Set keying so the connection does not depend on the AOP
- Recreate the module with the identical name
- Settle the scope before ordering
- Prove the replacement before the first run under load
- Questions asked
Keep the replacement at revision 14 and change the engineering workstation, not the project. RSLogix 5000 v20 can offer only the PowerFlex 753 revisions held in the drive database installed on that PC, and the database that ships with v20 stops at revision 13, so no edit inside the project can define the new drive. Update the workstation's drive database, recreate the I/O-tree module under the identical name, and set electronic keying so the cyclic I/O connection does not depend on the AOP accepting the firmware. Before any of that, upload every port of the old drive with Connected Components Workbench or the HIM CopyCat function, because option-module parameters live on their own ports and a single-port copy drops them.
Why the project cannot see the newer revision #
The revision in a drive module's definition is never typed in; it is picked from a list the designer builds from the drive databases on the workstation. Logix designer releases through version 30 read DriveTools databases, meaning DriveExecutive and DriveExplorer, while version 31 and later read Connected Components Workbench databases. A v20 install therefore offers exactly what its DriveTools database holds, and here the project, on a CompactLogix 1768-L45, tops out at revision 13 while the physical replacement reports 14. The outgoing unit reports revision 9, so the swap jumps 14 − 9 = 5 revisions.
Two failures look alike at this point and must be diagnosed apart. A red X in the AOP, or a profile that will not merge, is a database-versus-firmware problem on a drive that may be perfectly healthy on the network. An I/O connection that will not establish is a keying or identity problem, settled in the module's properties.
Worked example: the module is defined at revision 13, the drive reports 14, so the difference is 14 − 13 = 1 revision. Under exact keying any nonzero difference blocks the connection and the module faults; under compatible keying the same difference is accepted for cyclic I/O while the AOP editor still refuses the drive. One revision is the whole distance between a faulted module and a running machine, and a keying choice settles it, not wiring.
Back up every port before you remove anything #
While the old drive still communicates, take everything off it:
- Open it in Connected Components Workbench and upload the complete configuration, selecting all ports: the control port and every option module's port. Option parameters belong to their own ports, and a single-port upload leaves them behind.
- If no workstation route exists, copy the parameters with the HIM CopyCat function and confirm the stored set is selectable as a source before the old unit is powered down. CopyCat has cross-revision compatibility limits of its own, covered for a sister drive in HIM CopyCat firmware compatibility troubleshooting.
- Open the DeviceLogix editor, reachable from Connected Components Workbench, DriveExplorer, DriveExecutive or the AOP, and record whether logic exists, whether it is enabled and which inputs it uses. Controller ownership does not prove DeviceLogix is unused; Appendix D of the 750-series programming manual covers DeviceLogix and the HIM CopyCat function.
- Write down the commissioning values you will verify after the swap: motor data, command source, reference source, acceleration and deceleration times, limits, digital input functions and the communication settings.
- Save a separate copy of the controller project before the I/O tree is touched.
This is a 300 hp drive: lock out its feeder and let the DC bus discharge by the drive manual's procedure before any power wiring is opened.
Update the workstation drive database #
- In the existing project, open the properties dialog of the drive, go to the Overview tab and press the Device Definition button. Record the configured revision and the electronic keying selection; these are the two settings the replacement must satisfy.
- Close the project. From Rockwell Automation's Product Compatibility and Download Center, whose PowerFlex 753 pages list the firmware versions and revisions on the Versions tab, install the drive database and AOP release that covers revision 14, as a matched pair rather than one without the other.
- Reopen the project and check the Device Definition list again: the new revision must now be selectable. Pick it and the module definition matches the hardware.
- Keep the drive at revision 14. Downflashing it to the outgoing revision 9 is a last resort: it works only where the firmware documents the path and the drive's authorization rules permit the transition, some firmware cannot go back, and you would give up the fixes the newer revision carries. Take that route only if the workstation can never be updated, using the vendor's documented downgrade procedure.
Decision: with the database updated, define revision 14 in the project and use exact keying; the cyclic connection and the AOP then both work.
Set keying so the connection does not depend on the AOP #
If the workstation cannot be updated before the machine has to run, leave the module at revision 13 and set the keying selection to compatible: the cyclic I/O connection then establishes against the newer drive even though the AOP editor still rejects the firmware mismatch. That split is the point, because a working connection does not prove AOP access, and a refused AOP does not mean a failed network or a bad drive.
Two commitments come with it. Changing the keying selection requires a controller download, so if the existing module sits at exact keying, the value recorded under Device Definition, schedule that download; without it the replacement will not connect at all. And for as long as the AOP refuses the revision, drive-side editing moves to Connected Components Workbench.
If the connection still will not establish with revision and keying right, the causes are the ordinary ones for a Logix drive connection; work through why a PowerFlex 755 connection times out in RSLogix 5000 before blaming the replacement.
Recreate the module with the identical name #
- Delete the old drive object from the I/O tree and add the replacement with the discovery tool, keeping the same network address so the controller finds it where the project expects it.
- Name the new module exactly as the deleted one, character for character. Controller tags bind to that name, and a renamed module orphans them; the reuse trade-offs are laid out in why buffered I/O tags beat aliases when reusing Studio 5000 logic.
- If the controller owns the drive's parameters, inhibit the I/O connection, go offline, replace or synchronize the drive definition, download the project, then download or synchronize parameters from the drive tab. The AOP changed across designer versions, so accept on the connection and synchronization status, not on where the buttons sit.
- Open the replacement in Connected Components Workbench and compare the live parameters, port by port, against the upload taken before removal.
Settle the scope before ordering #
A designation such as 753-NET-E does not say whether the power unit, the 20-COMM-E communication adapter, or both are being replaced. Read the full catalog identity of the drive and of each installed option from the HIM, and confirm lifecycle status per catalog number rather than per family. If the adapter changes to a 20-750-ENETR, the controller profile must be rebuilt as a 753 reached through that adapter: delete and re-add, not an in-place edit. Decision: swap like for like unless modernizing the network interface is engineered as its own step.
Prove the replacement before the first run under load #
- Compare parameters port by port, then confirm DeviceLogix: same logic, same enable state, same referenced inputs.
- Verify the I/O connection, command the drive from the PLC and watch the status and feedback tags the old module fed.
- Check motor data, command source, reference source, ramp times and limits against the values written down before removal.
- Jog or run the motor and verify rotation and the acceleration and deceleration behavior before the first run under load.
Questions asked
Every revision disappeared from the Device Definition list after I updated the drive AOP. What fixes it?
The profile and its drive database are a matched pair, and installing one without the other has been reported to empty the revision list. Close the project, install both from the same release, and reopen. If the list is still empty, repair the drive database before saving anything, because a project saved against an empty list loses its module definition and the tags behind it.
The old drive failed before I saved its parameters. Can the replacement still be configured?
If the controller owns the drive, the parameter set lives in the controller project: install the replacement with the same module name and network address, then download or synchronize from the drive tab once the connection is up. Without ownership and without any saved file, commission from the machine documentation, and record motor data, command source, reference source, ramp times and input functions as you set them, so the next replacement has a file.
Is the whole PowerFlex 753 discontinued, or only the communication adapter?
Lifecycle status follows the catalog number, so check the complete drive code and the adapter's code separately in the manufacturer's current lifecycle listing; an adapter can reach end of life while the drive frame remains current, and the reverse is also possible. Confirm both before ordering, because replacing only the adapter forces a rebuild of the controller profile, while replacing only the drive keeps it.
Do I need Connected Components Workbench if RSLogix 5000 v20 is already on the engineering PC?
For a revision the installed drive database lists, the AOP alone is enough. A revision 14 drive on a v20 workstation can run cyclic I/O while the AOP editor still refuses it, and Connected Components Workbench is then the supported route into the drive for parameter work and DeviceLogix. Install it before the removal so the upload of the old drive and the commissioning of the replacement follow one toolchain.