Fix a PowerFlex 70 start inhibit that mimics a comm fault

Drives and motion Published 7 min read

Short answer

A PowerFlex 70 that answers RSLinx property requests but ignores PLC commands is start-inhibited, not offline: the recorded fix was bit 5 of parameter 277 [Start Mask], cleared from 1 to 0. Read parameter 214 [Start Inhibits] and compare parameter 277 between the running and inhibited axes — a difference of exactly 16 — before replacing the 20-COMM-E or touching DataLinks.

On this page
  1. Separate the layers before you blame the network
  2. What RSLinx proves and what it does not
  3. Read parameter 214, then the start mask in 277
  4. Isolating the start-mask bit on the cart axis that will not run
  5. Swap one variable at a time
  6. Restore the bit through a controlled procedure
  7. Check DataLinks only after the drive starts
  8. Questions asked

A PowerFlex 70 that browses cleanly in RSLinx but ignores the PLC's commands is not losing its network — it is refusing to start. The case that defines this symptom ended at parameter 277 [Start Mask], where the fifth bit from the right had changed from 1 to 0 and removed the start permission for the commanded source; the adapter kept answering property requests the whole time. Read parameter 214 [Start Inhibits] first, then compare parameter 277 between the running axis and the silent one, before you replace a 20-COMM-E, rewrite ladder, or rework DataLinks.

Separate the layers before you blame the network #

The path from a CompactLogix to a PowerFlex 70 on EtherNet/IP is a stack, and a fault anywhere above the layer you are testing can imitate a fault below it:

  • Physical link and addressing: cable, switch, unique static IP addresses.
  • Explicit messaging: RSLinx browse and property reads, issued on demand.
  • Cyclic I/O connection: the controller's output words (command, reference) and input words (status, feedback, enabled DataLinks), exchanged on a schedule.
  • Command ownership and start permission: which source is allowed to start the drive, set by parameter 277 [Start Mask].
  • Drive permissives: start inhibits and stop conditions, reported in parameter 214 [Start Inhibits].

A browse exercises the first two layers only. Explicit requests and cyclic I/O are separate services, and proof in one says nothing about the other — that separation is exactly why explicit and implicit EtherNet/IP messaging do not interwork. The drive-side layers sit behind the network entirely: Ethernet can deliver a start command perfectly and the drive can still refuse it.

What RSLinx proves and what it does not #

The recorded installation was a two-axis cart, both drives on 20-COMM-E adapters behind one switch, both with static IPs. Read each observation for what it actually proves:

  • Both drives appear in RSLinx and answer property requests. The switch path, the addressing, and each adapter's explicit server work. That is all it proves.
  • One axis runs, the other ignores commands. The shared PLC program, the switch, and the adapter type are functioning; whatever differs lives in the silent drive.
  • The STS indicator does not react to the command. The drive is not acting on the command; read its own inhibit and status data locally instead of inferring from the indicator.
  • Module correlation fails on both axes. In this case the Connect to drive browse failed for the running axis too, so it discriminated nothing. A test that fails on the good axis is not a test.
  • The user-defined input words sit at zero. Symptom, not cause: judge them after the drive accepts a start.

Read parameter 214, then the start mask in 277 #

The PowerFlex 70 Adjustable Frequency AC Drives User Manual (publication 20A-UM001) points you there by design: when a start inhibit exists, the drive cannot be started, and parameter 214 [Start Inhibits] shows the active inhibit conditions as set bits. Bit parameters read 0 when a feature is off or a condition is false, and 1 when it is on or true.

Parameter 277 [Start Mask] is the configuration half of the same permission chain: it controls which adapters can issue a start to the drive. These cart drives are commanded entirely through their DPI connection (port 5 in this installation), so a cleared mask bit removes the network's permission to start the axis while leaving every message path intact. That is why the failure presented as a comm fault: the command arrived and was refused, and the drive returned no feedback for the controller to see.

Isolating the start-mask bit on the cart axis that will not run #

Inputs. From the machine: the bad axis ignores commands, its STS indicator holds steady, and its input words never update, while the second axis runs and reports normally. From the resolution of this installation: parameter 277, fifth bit from the right, changed from 1 to 0. From the drive: parameter 277 read on the running axis with the HIM as the comparison value.

Rule in words. Number a bit parameter's bits from the right with 1 as the first bit; bit n contributes 2 raised to the power of n minus 1 to the decimal reading. Clearing a set bit lowers the reading by exactly that weight.

Arithmetic.

2 to the power of (5 − 1) = 2 to the fourth = 2 × 2 × 2 × 2 = 16

So when that single bit is the whole difference:

parameter 277 on the running axis − parameter 277 on the inhibited axis = 16

Result. The inhibited axis reads 16 counts below the running axis. Note what 16 is: a difference, not a value to write. The absolute readings come from your drives' start configuration; the arithmetic buys you a single-bit test made of two HIM reads and one subtraction.

Decision. A difference of exactly 16, with parameter 214 reporting an inhibit on the bad axis, convicts the fifth bit: restore parameter 277 to the running axis's full value — only after confirming both axes are meant to share one start arrangement — then drop the start bit in the controller and re-issue it. Any other difference means more than one bit moved; compare the complete values against the manual's bit list before writing anything.

Swap one variable at a time #

The adapter swap in this installation looked decisive: the fault appeared to move with the 20-COMM-E, so a new adapter was bought and fitted — and changed nothing. The swap had also moved the motor leads, the digital inputs, and the DPI port 5 wiring, so it changed the drive's command conditions at the same time as the card. A multi-variable swap cannot locate a fault, and the real cause was the drive-side bit all along. Run the discipline instead:

  1. Stop the machine in a safe service state and record both drives' configurations before disconnecting anything.
  2. Label the adapter, motor leads, digital-input connector, encoder link, and every DPI connection on both axes.
  3. Move one item only. Testing the adapter means moving the adapter alone and restoring its intended static IP.
  4. Repeat the identical PLC command and watch the same evidence each time: STS, drive status, and the input tags.
  5. Return the item to its own axis before starting the next test.

A fault that follows an adapter moved alone points at adapter configuration or its cyclic connection. A drive that stays inhibited through every single-variable swap is telling you the fault is inside it — go read 214 and 277.

Restore the bit through a controlled procedure #

  1. Remove the start command and put the axis where an unexpected start cannot move the machine; start-permission parameters are written in a safe state, never with the axis able to run.
  2. Read parameter 214 on the inhibited axis and note every set bit; the manual's inhibit list names the condition each one reports.
  3. Read parameter 277 on both axes and record the full values, not just the bit.
  4. Confirm in the documentation which start source the fifth bit permits before writing anything.
  5. Write the running axis's value only after confirming both axes are meant to share the same start arrangement; otherwise write the value documented for this axis.
  6. Drop the start bit in the controller and re-issue it — the drive acts on a fresh rising edge of the start bit, the same handshake used to start and stop a PowerFlex 700 over EtherNet/IP from CompactLogix.
  7. Save or upload the corrected configuration so the next unexplained change is a diff against a known file.

If 214 still reports an inhibit after the mask is restored, that inhibit is real: chase the condition it names, such as a missing permissive input or an active stop condition. The mask grants permission; it does not override an inhibit.

DataLinks extend the cyclic connection two 16-bit words at a time: you put the number of the parameter you want transmitted into a DataLink Out selection (A1, A2, B1, B2, C1, C2, D1, D2), then enable the DataLink and include it in the I/O connection. In this failure the controller's user-defined input words — Cart_Drive:I.UserDefinedData[2] and Cart_Drive:I.UserDefinedData[3] in that program — sat empty, and the impulse was to rebuild them. They were a symptom: the inhibit blocked the drive's feedback along with its response, and the words repopulated once the start mask was corrected.

Only after the drive starts on command and the words stay empty does the DataLink chain deserve work: selection, enablement, and the controller-side mapping, which is what configuring 20-COMM-E DataLinks in a ControlLogix project walks through.

Questions asked

What cleared the start-mask bit in the first place?

Nothing proved it in the recorded case; the crew attributed it to a supply disturbance. A configuration bit does not clear itself: it changes when a parameter is written from the HIM, from connected drive software, or when a stored configuration is loaded over the live one. Treat one changed bit as evidence of a write, and keep an uploaded copy of the corrected configuration so the next unexplained change is a comparison, not an investigation.

How do I read one bit of a parameter at the drive?

PowerFlex 70 bit parameters are read and edited bit by bit, and the manual's convention is that 0 means the feature is off or the condition is false, while 1 means on or true. When a note says fifth bit from the right, count from the right with 1 as the first bit; that bit carries a decimal weight of 16. If your tool shows only the whole decimal value, subtract the two axes' readings and use the difference to identify the moved bit.

Why did swapping the adapters make the fault look like it followed the card?

Because the swap moved more than the card: motor leads, digital inputs, and the DPI port 5 wiring were transferred along with it, so several variables changed at once and the conclusion was invalid. The adapter also carries its own settings, including its IP address, so unless two cards are configured identically the swap moves those differences too. Re-address a swapped adapter to its intended IP and repeat the same command before judging the hardware.

Should I rebuild the DataLinks if the input words are empty?

Not while the drive refuses its start command. In this failure the user-defined input words were empty because the drive was inhibited, and the data came back once the start mask allowed the network to start the axis. Rebuild the DataLink chain only after the drive runs on command and the words stay empty: the DataLink Out A1 parameter must select the value to send, and the DataLink must be enabled and included in the I/O connection.

Keep reading

  • Troubleshooting

    Fix a PowerFlex 40P opto output that will not turn on

    The opto outputs on PowerFlex 40P terminals 17 and 18 are always sinking NPN transistor outputs rated 30 VDC at 50 mA, and the drive's sinking/sourcing switch configures only the digital inputs. Fix it with a sourcing PLC input wired between +24 V and the output terminal, an interposing relay, or the drive's form C relay output.

    Drives and motion

  • Comparison

    How a PLC controls a VFD: five interfaces compared

    A PLC controls a VFD through one of five interfaces: discrete I/O, an analog speed reference such as 0-10 V or 4-20 mA, Modbus RTU or TCP, EtherNet/IP or BACnet/IP, or PROFIBUS or DeviceNet. Discrete and analog wiring carry commands only; the network interfaces also return status and fault data. Pick by how much the PLC must know about the drive, not by brand.

    Drives and motion

  • How-to

    Bridging a PLC-5/15 DH+ network to a Kinetix 300 servo drive

    Yes, a DH+-to-EtherNet/IP gateway exchanges command and feedback words between a PLC-5/15 and a Kinetix 300, but it only moves data: the drive must execute the motion profile locally. Replace the stepper controller, pulse expander, and encoder-counter functions with an eight-word map that carries a 32-bit position as two 16-bit words behind a data-valid handshake. If the machine needs trajectory points streamed per scan, migrate the controller instead of bridging it.

    Drives and motion