How-to
Connecting PROFINET VFDs to a redundant H-system CPU
Short answer
No one PROFINET part replaces the PROFIBUS Y-Link. Drives with PROFINET system redundancy connect directly to both H-CPUs, holding two application relationships with one active as primary; drives without it go behind a Y-switch. The NETPRO dual-connection scheme gated by user logic is a program switchover and does not meet a hardware-redundancy requirement.
On this page
- Is there a PROFINET equivalent of the PROFIBUS Y-Link?
- Which drives connect directly to both redundant CPUs?
- How do you configure a system-redundancy drive on the H pair?
- How do you connect drives without system redundancy?
- Is the NETPRO dual-connection scheme hardware redundancy?
- What happens to a single-owned drive when its CPU stops?
- How do you prove the switchover with the drives running?
- Which connection does each drive get?
- Questions asked
The concrete fix is three-way. A drive whose PROFINET interface declares system redundancy, the S2 device class in its GSD description, connects directly to both CPUs of the S7-1500H pair and holds two application relationships (ARs), one per CPU, with exactly one active as primary. A drive without S2 support goes behind a Y-switch, the documented device being the XF204-2BA DNA, with one uplink toward each CPU's PROFINET network and the drives downstream on its device-side ports. The NETPRO scheme, separate connection IDs per CPU gated by user logic reading the CPU RUN/STOP state through SFC51, is a program-level switchover and fails any requirement that says hardware redundancy only. So the route is chosen per drive: classify it in TIA Portal against its GSDML description, then configure whichever of the three it gets.
Is there a PROFINET equivalent of the PROFIBUS Y-Link? #
No one-to-one part exists: the equivalent depends on the drive, because a drive with PROFINET system redundancy connects directly to both CPUs of the H pair, while a drive without it goes behind a Y-switch.
The Y-Link worked because one coupler sat in front of the single-sided DP slave segment and presented itself to both redundant masters; slaves and masters never saw each other's redundancy. A standard PROFINET IO device does not work that way. It accepts one IO controller through one application relationship (AR), and a second controller trying to open an AR is refused, because two masters writing one drive control word would collide. PROFINET therefore moves the Y-Link logic into either the device itself, which is system redundancy with the S2 device class, or into a hardware coupler placed in front of the drives that lack it: the Y-switch.
Which drives connect directly to both redundant CPUs? #
Only a drive whose PROFINET interface supports system redundancy connects to both CPUs at once; it holds two application relationships, one per CPU, and the pair keeps exactly one active as primary while the other stands by.
Some SINAMICS VFDs support this and some do not; the communication module and firmware of the specific drive decide, so classify every drive before you order hardware or pull cable. Both relationships run through the drive's single PROFINET interface, so the drive needs no second port.
- Open the drive's catalog entry or GSD description in the engineering tool and look for system redundancy, the S2 class, in the device description.
- In the H project, try to assign the second CPU's PROFINET interface as a second IO controller of the device. TIA Portal documents multiple assignment of IO controllers for I-devices, but a VFD accepts the second controller only when its description declares system redundancy; the tool refuses it otherwise.
- Record the result per drive: S2-capable, or not. A refusal is the device's capability limit, not a project error, so do not hunt for a setting that changes it.
How do you configure a system-redundancy drive on the H pair? #
Assign the PROFINET interface of each CPU as IO controller of the same drive in one H project, keep one device name, one IP address and one telegram for that drive in both CPU views, and download to both CPUs in the sequence the H system prescribes.
- Place the drive once in the redundant project and assign the PROFINET interface of each CPU as its IO controller.
- Give the drive one identity in both CPU views: the same device name, the same IP address, the same telegram.
- Compile and download to both CPUs in the order the H system prescribes.
- Confirm the drive's actual device name matches the project before you judge anything; a mismatch leaves the drive in the device list while it never reaches data exchange.
- Read the diagnostics: each drive shows one connection per CPU, a primary and a standby, live status words in the process image, and no device failure in either diagnostic buffer.
If the same pair must also serve an OPC UA client directly, the conditions for that role are in when an S7-1500R/H can serve OPC UA directly.
How do you connect drives without system redundancy? #
Put a Y-switch between the drives and the two CPU networks, with one uplink toward each CPU; the documented device for an S7-1500H is the XF204-2BA DNA Y-switch, and the drives hang behind it as a single-sided segment, exactly as slaves did behind a Y-Link.
A Y-switch is a network path, not a protocol converter, a distinction this explanation of the PROFINET Y-switch as a network path rather than a Y-Link sets out. The S7-1500R/H manual collection shows the Y-switch inside a PROFINET ring, and the vendor's configuration guide for the XF204-2BA DNA with an S7-1500H gives the step-by-step project.
- Take the device-side port count, the uplink topology and the supported engineering-tool version from that configuration guide, never from assumptions carried over from the PROFIBUS Y-Link.
- Cable one uplink toward each CPU's PROFINET network, following the guide's topology drawing.
- Configure the drives as downstream devices of the Y-switch, importing the switch's GSDML where the guide calls for it.
- Download, then power-cycle the segment once; the drives must re-establish data exchange without the engineering tool.
- Check with both CPUs in RUN: the switch reports the active CPU and every drive's communication fault stays clear.
Is the NETPRO dual-connection scheme hardware redundancy? #
No: the NETPRO scheme is a user-logic switchover, not hardware redundancy, because each CPU opens a separate connection with its own connection ID and your program decides which block runs; the drive never holds a cyclic PROFINET IO relationship to both CPUs.
The scheme itself is simple. Add a connection for each CPU by hand in NETPRO, call the communication blocks for both CPUs with different connection IDs, and gate them with logic that reads the CPU RUN/STOP state through SFC51, so only the block belonging to the running CPU is enabled. That works for acyclic, message-style traffic such as parameter reads and diagnostics.
It does not create a cyclic IO relationship, and the changeover takes whatever your program scan plus the connection re-establishment takes. Both block sets enabled at once would write the same drive data twice, which is a fault, not redundancy; keep exactly one set active. When the requirement says hardware redundancy only, this scheme fails it, so take the S2 route or the Y-switch. On an S7-400H the same pair usually also serves the SCADA, a pairing covered in adding a second redundant S7-400H system to WinCC SCADA.
What happens to a single-owned drive when its CPU stops? #
A drive owned by one CPU loses its application relationship when that CPU stops, and the drive's telegram-failure reaction then decides the output: fault trip, or the configured fallback. That is a single point of failure, and no project setting turns it into redundancy.
This is the state of every PROFINET VFD that was simply wired into the plant network beside an H pair: it belongs to the CPU that opened its AR, and when that CPU stops the motor coasts or trips according to the drive's fault configuration. Any drive that must ride through a CPU failure needs S2 support or a seat behind the Y-switch.
How do you prove the switchover with the drives running? #
Stop the primary CPU with the drives at a low speed reference and time how long each drive's status word stays stale; the topology passes when that stale window is shorter than the drive's telegram-failure monitoring time.
Run the test with the drives uncoupled from the mechanics or the machine in a safe state, because a switchover briefly interrupts control.
- Baseline: both CPUs in RUN, redundant link synchronized, live status words on every drive, clean diagnostic buffers.
- Apply a low, non-hazardous speed reference from the process image.
- Stop the primary CPU or remove its power; the standby becomes primary and the drives should hold the reference. Record how long each status word stays stale.
- Compare each stale window with that drive's telegram-failure monitoring time. Worked example with illustrative inputs: a measured stale window of 350 ms against a monitoring time set to 1000 ms leaves 1000 - 350 = 650 ms of margin, so no trip is expected and the topology passes for that drive. The same 350 ms window against a monitoring time of 200 ms runs 350 - 200 = 150 ms past the limit, so that drive trips; raise its monitoring time within the range the drive manual allows, or change the topology.
- Restart the stopped CPU and let it resynchronize; redundant mode returns with no drive fault and no change in drive output.
- Repeat from the other CPU, then pull one network uplink at a time. Every single failure must give the same result, with the diagnostic buffer logging each event.
Which connection does each drive get? #
Give every S2-capable drive the direct two-controller connection, put every non-S2 drive behind the Y-switch, and reserve the NETPRO scheme for diagnostics and parameter traffic only.
- Drive with S2 support: direct to both CPUs over its one PROFINET port, no extra hardware between drive and pair.
- Drive without S2 and a hardware-redundancy requirement on the table: behind the Y-switch, one uplink to each CPU's network.
- Drive without S2 that only carries parameter or diagnostic data: the NETPRO scheme is acceptable, with exactly one block set enabled at any moment.
- Drive on neither mechanism: owned by one CPU, and that CPU is a single point of failure for its motor; label it that way in the documentation.
Questions asked
Can redundant-capable and non-redundant drives share one H system?
Yes. Each device is classified on its own, and the redundant-system manual describes PROFINET rings that mix directly connected drives with a Y-switch segment. Put the S2 drives on the pair directly, hang the others behind the Y-switch, and run the switchover test for each group separately; a pass on the direct drives proves nothing about the drives behind the switch.
Do both CPUs write the drive at the same time?
No. The drive keeps both application relationships open but applies only the primary connection's output data; the standby connection is present without controlling anything. The changeover when the primary CPU fails is a role change inside the device, not a fresh connection setup, so no reconnection delay is added to the stale window you measure.
Does a firmware update add system redundancy to an existing drive?
Only when the vendor documents S2 support for that exact drive, communication module and firmware combination in its catalog or GSD description. If it does, update and repeat the classification. If it does not, no parameter or project setting creates the second application relationship, and that drive belongs behind the Y-switch.
Where is the telegram-failure monitoring time set?
In the drive's own parameter set, not in the PLC project. The two settings that decide whether a switchover trips the drive are the drive's telegram monitoring time and its fault reaction, both read and changed with the drive commissioning tool. Set the monitoring time above the stale window measured in the switchover test, within the range the drive manual allows.