Why Telegram 111 does not carry SINAMICS S210 digital input status
Short answer
Telegram 111 is a fixed telegram with no word for r722, so the S7-1500 cannot receive S210 digital input status through it. Read r722 acyclically with the SINA_PARA function block for indication and monitoring; move to a user-defined telegram only when the input status must be current within the same scan the logic acts in.
On this page
- Why does Telegram 111 not carry the S210 digital input status?
- Can I add a word to Telegram 111 in TIA Portal?
- How do I read r722 from an S7-1500 with SINA_PARA?
- What does the returned r722 value mean?
- How much slower is an acyclic r722 read than the cyclic words?
- When is a user-defined telegram the better answer?
- How do I test the read path before trusting it?
- Questions asked
You cannot add the S210's digital input status to Telegram 111: the telegram's process-data layout is fixed, and it has no word for r722, the drive parameter that mirrors its physical digital inputs. Read r722 acyclically instead, with the SINA_PARA function block (FB286) that the S7-1500 libraries provide, and treat the result as monitoring data. Move to a user-defined telegram only when the PLC must act on an input within the same scan it runs in, and understand that this leaves the standard telegram the position-control configuration expects. This article explains why the telegram cannot be extended, walks through the acyclic read, decodes an example value, sets the timing expectations, and ends with the decision rule for both paths.
Why does Telegram 111 not carry the S210 digital input status? #
Telegram 111 has no process-data field for r722: its layout is fixed, and the words it does carry — including STW2 and ZSW2, which cyclically exchange a sign of life between controller and drive — leave no room for input status, so the PLC cannot receive it over this telegram.
Telegram 111 is the standard telegram for the EPos position-control interface between a SIMATIC controller and a SINAMICS drive: control and status words travel cyclically on every bus cycle, and the configuration documentation for position control from an S7-1200 or S7-1500 requires a standard telegram 111, 112 or 113 to be selected. The S210's physical digital inputs appear in the drive as r722, but r722 is a drive parameter, not part of that process data. Nothing written in the PLC program creates a process-data field the selected telegram does not define, so the input status never reaches the PLC's cyclic image. The decision follows: stop looking for a hidden word in the telegram and read the parameter through its own access path.
Can I add a word to Telegram 111 in TIA Portal? #
No, you cannot add an extension word to Telegram 111: the process-data layout of a standard telegram is a fixed contract between drive and controller, and the position-control configuration requires a standard telegram, so an extension word is not an option the device configuration offers.
A user-defined telegram is a different telegram, not a widened Telegram 111. Selecting one moves every control word, setpoint and status word in the cyclic data, which is why a telegram change always needs its own configuration work on the PLC side — the same lesson as why Telegram 750 torque control needs its own example. If the cyclic layout on the two sides does not match, the drive refuses the connection and reports a cyclic-connect fault; the article on the A08526 no-cyclic-connection fault shows what that looks like. Decision: treat the telegram as untouchable while it carries the position-control interface, and use parameter access for input status.
How do I read r722 from an S7-1500 with SINA_PARA? #
Insert FB286, SINA_PARA, from the Siemens function-block library for the S7-1500, configure it as a single-parameter read of parameter number 722 with parameter index 0, and latch the returned word into a tag you own each time the block completes a request.
- Insert the block from the library that matches your controller, and follow walk-through on configuring SINA_PARA FB286 for acyclic drive parameter reads for the setup details.
- Give the block the drive's hardware identifier from the S7-1500 device configuration, so the acyclic request goes to the S210's PROFINET interface and nowhere else.
- Set the block's read/write selector to a read, its parameter-number input to 722 and its parameter-index input to 0, the access for a single-value parameter such as this status word.
- Trigger the request on a rising edge at the start input for single-parameter requests, keep calling the block every scan while the request runs, and copy the returned word into your own tag — for example
diStatusWord, declared as a Word and initialized to 16#0000 — only when the block reports completion, never while a request is still in flight. - Group reads when it helps: a multiple-parameter request carries up to 16 arbitrary SINAMICS drive parameters, so the status word can travel with other status parameters; notes on running SINA_PARA FB286 for several drives concurrently cover one call per drive with its own request.
What does the returned r722 value mean? #
r722 is the drive's digital-input status word, one bit per physical input, so an example read that returns 16#0005 — binary 2#0000_0000_0000_0101 — says the inputs behind bit 0 and bit 2 are active and the input behind bit 1 is not.
Decode it like any status word. For an example machine that wires its reference cam to the first input, its table clamp to the second and its guard-latch position to the third: 16#0005 is 4 plus 1, which is bits 2 and 0 set — cam detected, clamp open, guard latch engaged. Re-trigger the read after the clamp closes and expect 16#0007, which is 4 plus 2 plus 1, all three bits set. The mapping of terminal to bit comes from the drive's wiring documentation; prove it once by toggling each input in turn and watching the matching bit move. Keep this word in its own tag: it arrives by a different path than the cyclic process data, so it must never be mixed up with the drive status word traveling in Telegram 111.
How much slower is an acyclic r722 read than the cyclic words? #
The two are different classes of traffic: Telegram 111 process data is current on every bus cycle, while an acyclic read returns the value as of the moment the request was served, so the freshness of the status word in your program is exactly the request interval you choose.
That makes the update rate a design input rather than a mystery. Trigger the request from a timer and the value can be no older than that timer: an example 100 ms trigger gives input status at most 100 ms old, ample for operator indication, fault context and non-safety interlocks whose latency budget exceeds the request interval. What acyclic access is not is per-scan motion data: a logic step that must see the input in the same scan it acts in needs the value in cyclic process data. Keep the acyclic word out of every stop path too — a safety or emergency-stop function belongs in the drive's or machine's safety circuit, and a parameter read over the network is monitoring, never a safety channel. Decision: indication, diagnostics and slow logic use SINA_PARA; scan-critical gating needs cyclic data.
When is a user-defined telegram the better answer? #
Switch to a user-defined telegram only when the PLC must act on an input within the same scan window and you accept the cost: you leave the standard Telegram 111 interface the position-control configuration expects and must match a new process-data layout on both sides.
Confirm the option exists for your drive and firmware before designing around it: the standard position-control documentation covers telegrams 111, 112 and 113, and whether the S210 offers a user-defined telegram with spare process-data words is a function-manual fact for the firmware you run. A device-description import does not create a process-data word either. If you do move to a user-defined telegram, budget the work: the PLC program's process-data mapping is rewritten, the standard block interface assumptions no longer hold, and every word must match on both sides before the cyclic connection comes up. Decision: stay on Telegram 111 plus SINA_PARA for monitoring; accept a telegram change only for a scan-critical input, verified against the drive's function manual.
How do I test the read path before trusting it? #
Prove the path with the inputs themselves: toggle one physical input at a time, request the read, and require the returned bit to match the drive's own input status display before any PLC logic consumes the word.
- Record the status word from the drive's display or the online parameter view with all inputs at rest.
- Actuate the first input, trigger a SINA_PARA read, and check that the matching bit in the returned word sets; repeat for the released state.
- Do the same for every input the application uses, in both states, and record the results.
- Watch the block's completion and error indications during the tests, and use SINA_PARA acyclic parameter read error walk-through when a request fails; the usual causes are a wrong hardware identifier or a request issued before the previous one finished.
- Measure request-to-completion time in the running application, so the latency budget for the non-safety logic rests on a measurement rather than an assumption.
- Exercise a normal motion step afterwards to confirm the Telegram 111 control path is untouched.
Questions asked
Does SINA_PARA work from an S7-1200 as well as an S7-1500?
Yes. Siemens provides separate SINA_PARA libraries for the S7-300 and S7-400, the S7-1200 and the S7-1500, so the same acyclic read of the digital input status works from an S7-1200 project. Insert the block from the library that matches your controller and keep the request structure identical: read the parameter, wait for completion, then consume the value.
Does the S210 web server change what the telegram can carry?
No. The web server is a browser-based diagnostics and commissioning service; it does not edit the process-data layout. What the cyclic telegram carries is fixed by the telegram selected in the drive and controller configuration, so input status reaches the PLC either through acyclic parameter access or through a verified user-defined telegram, never through the web server.
What error handling belongs around the acyclic read?
Wrap each request with the block's completion, busy and error indications. Issue a new request only after the previous one completes, treat an error status as a failed read rather than a stale value, and decide in the logic what the consuming step does while the status word is not fresh. A watchdog that flags an aging value is usually enough for monitoring use.
Can I write a drive digital output the same way?
You can command a drive digital output through acyclic parameter access, and the timing caveat applies with more force than for a status read: an output command that arrives one request interval late switches later than a cyclic control bit or a hardwired terminal. Keep time-critical outputs on the cyclic telegram or the drive's own terminals, and reserve parameter writes for setup and slow switching.