Adding a second redundant S7-400H system to WinCC SCADA

SCADA and data logging Published 7 min read

Short answer

Yes — one WinCC SCADA can run two independent redundant S7-400H systems. Inventory the installed WinCC version, channel and licensed external tag count, add a redundancy-aware connection set for the new pair instead of copying the first system's connections, and accept the work with a forced switchover test before go-live.

On this page
  1. Will a second redundant controller system work on the same WinCC SCADA?
  2. What do I need to record from the running installation before I start?
  3. How does WinCC stay connected to a redundant controller pair through a switchover?
  4. What licenses and tag capacity does the second system need?
  5. What network path and hardware does the second pair need?
  6. How do I add the second system's connections and tags to the WinCC project?
  7. How do I prove the second system before it goes live?
  8. Questions asked

Yes — an existing WinCC SCADA project can communicate with a second independent redundant S7-400H system. The work is not a copy of the first pair's configuration: it is an inventory of what you run today, a new redundancy-aware connection set for the second pair, a tag-count check against your license, and a forced switchover test before go-live. This article walks through that sequence and the decision points where installations differ.

Will a second redundant controller system work on the same WinCC SCADA? #

Yes — one WinCC SCADA runtime communicates with two independent redundant controller systems when the installed WinCC version and its SIMATIC S7 channel support the second system, the licensed external tag count covers the added tags, and each pair uses the redundancy-aware connection pattern its documentation specifies. Two such systems are two separate control systems: each has its own master/standby relationship, and the WinCC channel handles each pair on its own. The first decision is what "the same SCADA" means for you — the existing WinCC runtime talking to both systems, or a redundant WinCC server arrangement on top. Those are different projects with different licensing; this article covers the first case, which is what most additions need.

What do I need to record from the running installation before I start? #

Record the exact WinCC product and version, the channel type in use, the licensed external tag count and current usage, the CPU and communication module identities in each rack, and which CPUs belong to which redundant pair — before you order licenses or edit the project. Concretely, write down:

  • The WinCC product, version, runtime architecture (single station, server, clients) and active licenses, so you have a software identity rather than just the name WinCC.
  • The working channel and its existing connection configuration as commissioned.
  • The CPU, communication module and rack identities of the first pair — for example CP443-1 (6GK7443-1EX30) modules on a UR2-H rack, as in the documented configuration tutorial — plus the engineering software versions used to maintain both the PLC and WinCC projects.
  • Which controllers belong to which redundant system and which process each one runs, so the boundaries between the two pairs are unambiguous.
  • A network drawing showing every path from the WinCC station to each CPU interface.

With that inventory in hand you can check your exact combination against the manufacturer's configuration documentation instead of guessing from a generic answer.

How does WinCC stay connected to a redundant controller pair through a switchover? #

WinCC keeps one redundancy-aware S7 connection to the pair, and the channel tracks which CPU is master and follows the switchover — which is exactly what two plain connections to two IP addresses do not do, no matter how many pings they answer. A channel is the WinCC component that exchanges process data with a controller; a connection is one configured communication relationship that channel uses. Reaching both CPUs on the network is not redundancy-aware communication; the channel must be told the two partners form one logical system so it follows the switchover without operator intervention.

In classic WinCC projects maintained from SIMATIC Manager, the documented route for that arrangement is a redundant S7 connection configured in NetPro and handed to WinCC through the REDCONNECT mechanism, with the connection data exported as an XDB file. Use the arrangement documented for your installed WinCC version and S7-400H firmware, not a pattern from another combination. On the I/O side of the H system, PROFINET devices that support system redundancy, such as ET 200M stations, are assigned to the H system in the documented S7-400H PROFINET configuration example. The same separation between controller redundancy and SCADA reachability shows up in other redundant controller families too — the work of linking Modbus RTU BMS SCADA to a redundant S7-1500R fails for the same reason when only reachability is configured.

What licenses and tag capacity does the second system need? #

No universal add-on list exists: the purchase depends on the installed WinCC product and how it counts licensed capacity, and the deciding number is your external tag count after the second system is added, measured against the entitlement you already hold. Worked example with example figures: suppose the installed runtime is licensed for 2,048 external tags, the first S7-400H system uses 1,500, and the second system's tag list adds 700. Then 1,500 + 700 = 2,200 external tags, which is 2,200 − 2,048 = 152 over the example entitlement, so this project needs the next capacity class. Read the real entitlement from your installed license and the real counts from your expanded tag list; internal variables and archived values follow their own counting rules in the installed product, so check how your product counts each category before you buy.

Two more license checks: first, the engineering station needs software that can open and edit the existing project at its version, with the channel options the redundant connection requires. Second, if the plant wants server-level availability, the WinCC Redundancy option is licensed and configured separately from anything this controller addition touches.

What network path and hardware does the second pair need? #

The second pair needs a supported path from the WinCC station to each CPU's communication module — a CP443-1 (6GK7443-1EX30) in each rack in the documented tutorial — with free switch ports on both sides, because one shared switch is a single failure that can cut supervision of both pairs at once. Assign unique addresses to the second pair's interfaces and check them against the first pair's scheme so nothing conflicts. Before connecting, confirm the CPUs and communication modules still have free connection resources with both systems attached; the documented resource limits of your modules decide that, and both pairs drawing from the same SCADA station makes the budget tighter than a single-system design. Evaluate availability separately from connectivity: a controller pair stays operational while a failed shared switch or cable stops the SCADA from seeing it. If the upgrade also replaces or adds the computer that runs the WinCC runtime beside the controller, the machine category for that job is an industrial panel PC.

How do I add the second system's connections and tags to the WinCC project? #

Back the working project up first, then build the second system as its own connection set with its own tag prefix — never by copying the first system's connections, because a copied connection carries the old pair's controller references and can show valid-looking data from the wrong plant. The sequence:

  1. Archive the working WinCC project so you have a known-good fallback.
  2. In the channel configuration, create a new connection set for the second pair using the redundancy mechanism documented for your installed WinCC version; in classic WinCC projects that is the REDCONNECT route with connection data exported from NetPro as an XDB.
  3. Give every new connection and tag a second-system prefix, for example SYS2_, so nothing inherits the first system's names.
  4. Map the second system's external tags to its DB addresses and verify each address against the second controller project, symbol by symbol.
  5. Check that the CPUs and communication modules still have free connection resources with both systems connected.
  6. If server redundancy is required, set up the WinCC Redundancy option on both servers and enable it in the option's own dialog; that is a separate work package from this controller change.
  7. Save, compile and load the changed project to a test station before the running system.

How do I prove the second system before it goes live? #

Test switchover, not reachability: force a master change on the second pair while its screens are updating, confirm the channel follows without a flood of tag-quality alarms, then pull each network path in turn — a successful ping test alone is not the acceptance criterion. Repeat the forced switchover on the first pair to confirm the two systems do not interfere, and watch the channel diagnostics to see each connection's state per CPU. Where the WinCC Redundancy option is installed, its own system messages appear on its system messages tab, and clearing those is part of acceptance too. For the complete commissioning method on any SCADA you touch, work through what a SCADA system does and how to verify it works.

The decision, case by case: add the second system to the same WinCC SCADA when the inventory shows a supported WinCC version and channel, the expanded tag count fits the license, and you build an independent redundancy-aware connection set — accept it on a forced switchover. Copying the first system's connections, or calling two pingable addresses a redundant link, is the failure mode to refuse in every case.

Questions asked

Does S7-400H controller redundancy give me redundant SCADA servers too?

No. Controller redundancy keeps control running when one CPU of a pair fails; SCADA availability is a separate layer. If the visualization must survive a server failure, that is the WinCC Redundancy option: its own component with its own dialog, licensing and system messages, configured on both servers. Adding a second PLC system neither creates nor requires it.

Can I copy the first pair's WinCC connection and just change the IP addresses?

You can, and it is the most common way to end up with data from the wrong plant. A copied connection carries the original connection's controller references and tag associations, and one missed reference shows plausible values from the first system. Build the second pair's connections from the documented redundancy pattern with their own names and tag prefix instead.

How many WinCC connections does one redundant controller pair need?

The channel's documented redundancy arrangement decides it, and it is commonly one configured connection to each CPU of the pair, with the channel's switchover logic choosing which one carries data. The exact count for your combination lives in the configuration documentation for your installed WinCC version, alongside the free connection-resource budgets on the CPUs and their communication modules.

Do I need a second WinCC server for the second PLC system?

No. One WinCC runtime communicates with both S7-400H systems; two controller pairs are two connection sets inside the same project, not two servers. Add a server only if the plant's availability requirement says the visualization itself must survive a server failure, and then it is the WinCC Redundancy option: separate hardware, licensing and configuration.

Keep reading

  • How-to

    Connect an S7-1500 to SCADA over OPC UA from TIA Portal

    The S7-1500 has a built-in OPC UA server from firmware V2.0, deactivated by default. Enable it in the CPU device properties in TIA Portal, select the installed server license, copy the endpoint URL, and download. Paste the opc.tcp address into any OPC UA SCADA client, trust the certificates on both sides, then browse the PLC variables and map them to SCADA tags.

    SCADA and data logging

  • How-to

    Connecting a CODESYS HMI on Windows to an S7-1500 PLC

    Yes, it works. Use OPC UA with the S7-1500 as server and the CODESYS HMI as client when the PC only supervises; use a CODESYS Control Win runtime with target visualization over a PROFINET controller/device link when the PC must also run logic. The PROFINET path adds one single-device license on top of the runtime; the OPC UA path adds none.

    SCADA and data logging

  • Troubleshooting

    Fixing CODESYS OPC DA memory growth stopping SCADA reads

    The reads stop because WinCoDeSysOPC.exe, a 32-bit OPC DA server process, climbs to its 2 GB memory ceiling over weeks and then stops serving tags; killing it only resets the clock. The resolution that held was installing the current, licensed CODESYS OPC DA server — 3.5.22.40 in place of the CODESYSV35SP10Patch2 install — and proving it through the old failure window.

    SCADA and data logging