Troubleshooting
Why RSLogix 500 reports target node is not SLC or MicroLogix
Short answer
The target node is not SLC or MicroLogix error means the controller answered, so the cable and port settings are already good. Two conditions produce it: the RSLinx DF1 driver and the controller sit on the same DF1 node, or the firmware revision is newer than your RSLogix 500 build recognizes. Change the driver station number first, because that fix costs nothing; if the node pair is clean, the software needs an upgrade.
On this page
- Read the link state before you touch anything
- A duplicate DF1 node: the driver hears itself
- Firmware newer than the software build
- Example: a driver on node 1 answering a controller on node 1
- Example: dating a controller against the May 2005 processor table
- Rebuild the driver in the right order
- Pitfalls that eat a day on legacy serial links
- The decision for each case
- Questions asked
The message reads like a cabling fault. It is the opposite: "target node is not a SLC 500 or MicroLogix controller" is a reply, not a timeout. Bytes went out, something answered, so the cable pinout, COM port and baud rate are already correct, and rebuilding the cable wastes an afternoon. Two conditions produce this exact text, and both are documented. The first is a duplicate DF1 node: the RSLinx driver and the controller sit on the same node number, so the driver parses its own traffic. The second is firmware newer than your RSLogix 500 build recognizes: the software reads an identity code its processor table has never seen. Test the node numbers first, because that fix costs nothing; then date the firmware against the software version.
Read the link state before you touch anything #
Separate "no link" from "link, wrong answer". The fixes do not overlap and neither does the diagnosis.
- Nothing browses in RSWho and Auto-Configure fails at every baud rate: wrong COM number, another program owning the port, or virtual serial redirection. That is a link problem, and the target-node error is not part of it.
- The controller appears in RSWho but RSLogix 500 rejects the go-online with the target-node message: duplicate DF1 node or firmware unknown to the software build. This is the case this article fixes.
- Driver diagnostics show packets sent climbing while received stays at zero: port, adapter or redirection again, not addressing.
If you have the target-node message, the cable is fine. Leave it alone.
A duplicate DF1 node: the driver hears itself #
DF1 full-duplex carries a destination node byte and a source node byte in every frame, even on a simple point-to-point serial cable. Give the RSLinx driver the same station number as the controller and the driver accepts traffic aimed at that node as its own. It then tries to decode a processor identity out of a frame that carries none, and RSLogix 500 reports the error. The documented case is exactly this: a driver set to node 1 talking to a controller also on node 1, and moving the driver to a different node cleared it.
Most MicroLogix and SLC processors answer on node 0, so a driver on node 1 is the usual working pair. The only rule is that the two numbers differ. If the controller sits on 1, put the driver on 0; any unused node works as well.
Firmware newer than the software build #
RSLogix 500 matches the controller's catalog and firmware identity against a processor table compiled when that software version was built. Version 7.00.00 shipped in May 2005. Any controller series or firmware revision issued after that build is absent from the table, and the software reports the same message because it genuinely does not know what answered. This failure appears over serial and over Ethernet alike, which removes wiring from the discussion entirely.
The fix is an RSLogix 500 upgrade through official channels, and it is also a licensing question: which PLC software you actually need to buy sorts out the editions and what each one supports.
Example: a driver on node 1 answering a controller on node 1 #
DF1 full-duplex puts two node bytes in every frame, destination first, source second. Set the driver station to 01 and the controller answers on 01. Your request leaves with destination 01; the reply comes back destination 01, source 01. The driver compares the reply's destination byte, 01, against its own station number, 01, the comparison matches, and the driver treats the frame as its own traffic. It accepts a response it never requested, finds no processor identity in it, and RSLogix 500 reports the target-node error. Now set the driver station to 00: the reply reads destination 00, source 01, so 00 names the driver, 01 names the controller, the response pairs with the outstanding request, and the link goes online. Two node numbers, one comparison, and the whole fault clears in the time it takes to open the driver configuration.
Example: dating a controller against the May 2005 processor table #
This scenario shows how the second cause wins even with a clean node pair. A MicroLogix 1200 bought secondhand is put on the desk with RSLogix 500 v7.00.00 and connected eight years after that build. The arithmetic is 2013 minus 2005, which is 8 years of processor and firmware revisions the software's table cannot contain. The node numbers check out as different, the controller browses in RSWho, and the target-node message still appears on serial and on Ethernet. That combination points at the software: no amount of driver work fixes a processor table that predates the controller. The decision rule is that a clean node pair plus a browsing controller plus the same error on both transports means the RSLogix 500 build is the remaining variable.
Rebuild the driver in the right order #
- Press DCOMM on the MicroLogix so channel 0 ignores the loaded program and comes up on its default DF1 settings, and confirm the DCOMM indicator lights. Treat this as a temporary override; you will correct channel 0 in the program before releasing it.
- Close RSLogix 500. One process may own the serial port.
- In RSLinx, delete every configured driver, DF1 and DH-485 alike, including anything left from a previous attempt.
- Reboot Windows. A removed DH-485 driver can hold the port until you do, and a DF1 driver added before the reboot fails silently.
- Check the actual COM number under Ports in Device Manager. USB-to-serial adapters land wherever the enumerator puts them, and it is not always the lowest number.
- Add the RS-232 DF1 Devices driver, select the port and run Auto-Configure, then wait for the success message. Whatever the port properties say about baud and parity does not matter; Auto-Configure sweeps them.
- Set the driver station number to a node the controller is not using: 0 if the controller answers on 1.
- Browse in RSWho and confirm the controller icon appears, then read the catalog number, series letter and firmware revision from its device properties. That revision is what tells you whether the software build is too old.
If Auto-Configure still fails at every baud rate, the problem is the port or its owner, not this error, and how to connect a laptop to an SLC 500 serial port covers the cable and adapter side step by step.
Pitfalls that eat a day on legacy serial links #
- Virtual machine serial redirection. Legacy DF1 and DH-485 drivers do not tolerate a redirected COM port under XP Mode or a hosted virtual machine, and the redirected port re-enumerates and drops packets. The same cable, controller and software connect on a native machine. Move the work to real hardware instead of debugging the VM.
- Port sharing. RSLinx will not share the serial port with a terminal emulator, an HMI transfer utility, modem software or a second configured driver. Remove the competitor, reboot, retry.
- Stale drivers. Deleting a driver without rebooting leaves it holding the port, and the replacement DF1 driver then fails for reasons that look like hardware.
- Upload direction. Upload copies controller to PC and the controller keeps running. Download is the direction that overwrites.
The decision for each case #
- Driver station equals controller node: change the driver station number to any unused node. It is free, immediate, and the documented fix.
- Node numbers differ, the controller browses in RSWho, and the error appears on serial and Ethernet: the software build predates the firmware. Upgrade RSLogix 500.
- No packets in either direction: fix the port, its owner or the virtual redirection first. The target-node error is not in play yet.
- If you used DCOMM: correct the channel 0 configuration in the program, download it, then release the override, or the link drops the moment the override clears.
On the bench question: practicing on the MicroLogix 1200 is not a waste of time. The driver, node and version checks carry directly to the MicroLogix 1500, and once that controller is on the desk, serial SCADA reads to both an SLC 5/03 and a MicroLogix 1500 are set up much as the MicroLogix side is here. One boundary holds once you are online: do not drive the machine by writing the panel's data-table bits from the PC. That bypasses the operator panel handshake, and on a machine that moves, it is a safety problem, not a debugging technique.
Questions asked
Does this error mean the cable is wired wrong?
No. The message is a reply from the controller, so bytes travelled in both directions and the framing matched. A wiring or baud rate fault produces timeouts and an empty RSWho instead. Keep the cable, check the DF1 node numbers on the driver and the controller, and then compare the firmware revision against your RSLogix 500 version.
Does an upload keep the program running in the controller?
Yes. Upload copies the program from the controller to the PC and the controller keeps running what is loaded. Only a download overwrites the controller. Save the uploaded file as a read-only master copy and edit a duplicate, so you can download the as-found program back if one of your changes misbehaves.
Can RSLogix 500 Micro starter connect to an SLC 500?
No. The Micro edition of RSLogix 500 supports only MicroLogix family processors, not the SLC 500 family. If a Micro edition project refuses to go online with an SLC, no driver or node setting will fix it; you need a full edition of the software that supports the SLC 500 family.