Troubleshooting
Why RSLinx throws PIC Driver Init Failed on DH485
Short answer
PIC Driver Init Failed means the 1747-PIC/AIC+ driver could not take over a real serial port on the PC; the DH485 network, the converter and the PLC are not involved yet. The driver runs only on a built-in COM port and fails through every USB, PCMCIA, ExpressCard or Ethernet serial adapter. Clear the port and the Windows XP service-pack issue first, then give DH485 a real interface: a 1747-PIC or 1761-NET-AIC, or a 1747-UIC on USB with the DF1 Full Duplex driver.

On this page
- What the message rules out first
- The port rule: built-in COM1 or COM2 only
- The computer checks, in order
- Why a generic converter may stay silent
- Working your case: built-in port, Windows XP SP3, generic converter
- Three gates that prove the fix
- Fixes that waste the afternoon
- The decision for each case
- Questions asked
PIC Driver Init Failed is a PC-side failure. RSLinx raises it while the 1747-PIC/AIC+ driver is still trying to claim a serial port on your computer, before a single DH485 frame leaves the machine. The converter, the DH485 pair and the SLC processor are not in the circuit yet, so rewiring them is wasted motion. The order of work follows from that: prove the COM port is built into the motherboard, clear anything else that holds it, test the operating system, and only then judge whether your RS-232/RS-485 converter can carry DH485 at all. If a step fails, the answer is a real interface: a 1747-PIC or 1761-NET-AIC, or a 1747-UIC on USB with the DF1 Full Duplex driver.
What the message rules out first #
Initialization is the driver taking over the PC's serial hardware: opening the port, setting it up, claiming it. The PLC does not have to answer for that to succeed, which means its node address, its program and the DH485 wiring cannot cause this message. Match the exact symptom to the fault domain before you pick up a screwdriver:
- PIC Driver Init Failed at driver start: the computer, the port or the operating system. Everything downstream is innocent until the driver runs.
- Driver starts, no DH485 nodes appear: now it is the interface. Converter handshake, wiring, termination and node address are the suspects.
- DF1 driver starts, the processor never appears: a protocol mismatch. RS-232 signaling on your end of the link does not make the far end a DF1 device.
- SLC500 (DH485) Emulator Driver runs, no physical node: the wrong tool. It simulates nodes inside the PC and never touches a port.
The port rule: built-in COM1 or COM2 only #
The installation instruction for the SLC 500 RS-232 to RS-485 interface converter, publication 1747-IN024A-EN-P, is blunt: the 1747-PIC works only with built-in COM1 and COM2 serial ports. It does not work through USB-to-serial adapters or extender boards that add ports, and the same refusal is reported for PCMCIA, ExpressCard and Ethernet serial interfaces. The reason is access: the driver needs low-level control of the motherboard's own serial hardware, and every adapter inserts a translation layer. A COM number in Device Manager proves nothing, because a USB adapter gets one too.
So the first test needs no tools. If the connector hangs off USB, a card slot or the network, the 1747-PIC/AIC+ driver will not initialize on it, and no setting changes that. Moving a PCMCIA serial card into an ExpressCard to PCMCIA adapter for industrial fieldbus cards changes the slot, not the rule. Once the port question is settled, the connector and cable side is covered in how to connect a laptop to an SLC 500 serial port.
The computer checks, in order #
- Identify the port. Motherboard connector, or an adapter presenting itself as a COM port? If it is an adapter, stop here and switch to the 1747-UIC route described below.
- Match the number. In Device Manager, confirm the port exists and note its COM number, then configure the 1747-PIC/AIC+ driver in RSLinx 2.42 against exactly that number.
- Free the port. Close anything that can hold it, such as a second RSLinx copy, a serial monitor or a driver left open since boot, then restart the driver.
- Note the service-pack level, because the field pattern ties this message to Windows XP machines after Service Pack 3 went on.
- If the port is clean, built in and correctly numbered and the message persists, run the operating-system test.
The field reports are specific: XP laptops with working built-in ports threw this error once Service Pack 3 was installed, and a separate XP installation recovered DH485 communication after the service pack was removed through Control Panel. That makes the service pack the prime suspect once steps 1 to 3 pass. Treat the removal as a controlled compatibility test, not a repair: run it on a dedicated legacy laptop or an approved maintenance image with recovery media at hand, because you are rolling back security updates to perform it.
Why a generic converter may stay silent #
Once the driver starts, attention moves to the converter, and the honest engineering is this: a label reading RS-232 to RS-485 is not a promise of DH485. RS-232 and RS-485 describe electrical interfaces; DH485 is the protocol and link behavior riding on them. The 1747-PIC and the 1761-NET-AIC steer their RS-485 transmit and receive circuits with specific RS-232 handshaking that the DH485 driver expects. Common converter designs instead control translation direction through the RTS signal or with automatic direction control, which is a different behavior, and the DH485-side timing belongs to the protocol and is not published, so you cannot configure your way past the difference. If the handshake differs, no RSLinx setting repairs the path.
Give DH485 an interface built for it, in one of two ways:
- A 1747-PIC or a 1761-NET-AIC on the built-in port, driven by the 1747-PIC/AIC+ driver. The AIC+ user manual, publication 1761-UM004, describes that converter as replacing the 1747-PIC.
- A 1747-UIC on USB: RSLinx reaches it with the DF1 Full Duplex driver on its USB serial port, and the interface does the DH485 work onboard. DF1 names the PC-to-interface side only; your SLC500-L40B still speaks DH485 and never becomes a DF1 device.
The near-side-versus-far-side lesson is general. It is the same reason why a DF1 driver cannot reach an SLC 5/04 through a DH+ gateway: the protocol must match what the processor answers, not what the first connector carries.
Working your case: built-in port, Windows XP SP3, generic converter #
The inputs, each with its source:
- Path attempted: laptop, then a generic RS-232/RS-485 converter, then DH485 to an SLC500-L40B, to upload the existing program before the processors are swapped out (your setup).
- Port: a built-in COM port (your report).
- Operating system: Windows XP Professional at Service Pack 3 (your report).
- Software: RSLinx 2.42 with the 1747-PIC/AIC+ driver selected (your report).
- Symptom: PIC Driver Init Failed at driver start (your report).
- Governing rule: the message is PC-side until the driver initializes, and the 1747-PIC/AIC+ driver runs only on built-in COM1 or COM2 (publication 1747-IN024A-EN-P).
The rule in words: test port type, then port ownership, then operating-system level; judge the converter only at the network gate; a completed upload is the only proof of the whole path. Work it in that order:
- Port type: built in, so the port rule passes. The adapter limitation is not the cause.
- Port ownership: the port is present in Device Manager and nothing else holds it, so ownership passes.
- Operating system: XP at SP3, which matches the reported failure pattern, so the service pack is the remaining PC-side suspect.
- OS test: remove the service pack on a maintenance image and retest. In the reported field case, a separate XP installation recovered DH485 communication after this removal.
Result: when the driver initializes without the message, the computer side is cleared, and the generic converter faces its first real test at the network gate.
Decision: if the SLC500-L40B shows in the RSLinx browse and the upload completes, the path is proven; save the uploaded project under its own name and proceed with the swap. If the driver runs but no node ever appears, the converter has failed the network gate, so stop debugging it and put a 1747-UIC on the USB port. If the node appears and disappears, correct direction control, the reference conductor and termination before blaming the interface.
Three gates that prove the fix #
- Driver gate. RSLinx adds and starts the selected driver without PIC Driver Init Failed. This proves the PC side only, nothing more.
- Network gate. The browse shows the physical SLC node and it stays visible. Leave the browse open long enough to tell a stable node from a flickering one; flicker points back to direction control and wiring.
- Application gate. The programming software identifies the processor and completes the upload. Record any processor-identity prompt before answering it, and never download to a processor whose program you do not already hold.
Fixes that waste the afternoon #
- Choosing the DF1 driver because your end of the link is RS-232. The processor still speaks DH485.
- Selecting the SLC500 (DH485) Emulator Driver to find real hardware.
- Plugging in a USB-to-serial adapter and matching its COM number. The number exists; the access the driver needs does not.
- Rewiring the DH485 pair or changing node addresses while the message still reads PIC Driver Init Failed. The driver has not reached the network.
- Tweaking a generic converter's switches as if its label promised DH485 compatibility. The handshake behavior is the specification that matters, and it is not printed on the case.
The decision for each case #
- No built-in COM port on the machine: the 1747-UIC route on USB, and stop arguing with adapters.
- Built-in port, XP at SP3, init fails: remove the service pack on a maintenance image or a dedicated legacy laptop and retest; the field record says that restores the driver.
- Driver starts, no node: the converter is not carrying DH485, so replace it with a 1747-UIC or a 1761-NET-AIC. If the node flickers instead, correct termination and the reference conductor first.
- Node visible, upload fails: a different fault entirely. Record the exact software message and the processor identity it reports before touching anything else.
Questions asked
What is the SLC500 (DH485) Emulator Driver actually for?
It presents simulated DH485 nodes inside RSLinx so a configuration can be tested with no hardware attached. It never opens a serial port, so a physical processor will not appear under it however the wiring is set. Use it to rehearse a browse or a screen, then close it and select the 1747-PIC/AIC+ driver for the real machine.
Is the DH485 connection really just one pair?
One twisted pair carries the data, but that is not the whole connection. The interfaces also need the signal common carried through, and the shield treatment and end termination come from the interface documentation, not from the wire. Follow the terminal designations on the 1747-PIC or 1761-NET-AIC instead of wire colors, and terminate at the physical ends of the link.
What if the laptop must stay at Service Pack 3?
Skip the 1747-PIC/AIC+ route entirely. The 1747-UIC enumerates as its own USB device and RSLinx reaches it with the DF1 Full Duplex driver, so the PIC initialization step that fails on that service pack never runs. The machine stays patched, and the interface still handles the DH485 link to the processor onboard.
How do I prove a COM port is built in rather than virtual?
Unplug every USB device and card, then reboot. A built-in port is still there afterwards because it sits on the motherboard; an adapter's COM entry disappears with the adapter. On a laptop the connector is part of the chassis with no dongle or card involved. The 1747-PIC/AIC+ driver needs the port that survives that test.
Does PIC Driver Init Failed mean the 1747-PIC interface is damaged?
No. The message is raised while the driver claims the PC's serial port, before the interface is exercised at all. A dead 1747-PIC or 1761-NET-AIC shows a different symptom: the driver starts cleanly and the browse simply stays empty. Suspect the interface only after the computer side passes and the network gate still fails.