Explainer
Why RS-485 Partlow controllers cannot join a DH-485 network
Short answer
RS-485 is only an electrical interface, while DH-485, ASCII and Modbus are message protocols; the 1761-NET-AIC changes the medium, not the message, so a Partlow 1160 cannot join a DH-485 network. The fix is a PLC with a dedicated ASCII or Modbus serial channel, such as a MicroLogix 1100 polling the controllers on its serial port with programming kept on Ethernet.

On this page
No, a Partlow 1160 temperature controller with an RS-485 port cannot join a DH-485 network through a 1761-NET-AIC. RS-485 is only the electrical interface; DH-485, ASCII and Modbus are message protocols, and the 1761-NET-AIC converts RS-485 to RS-232 without translating a single message. The fix is a PLC channel dedicated to ASCII or Modbus, not more converters.
Can RS-485 run over a DH-485 network with a 1761-NET-AIC? #
No. RS-485 is only the electrical interface; DH-485, ASCII and Modbus are message protocols, and the 1761-NET-AIC converts RS-485 to RS-232 without translating a single message between them.
The symptom is easy to recognize: the MicroLogix keeps talking to its PanelViews and other PLCs on DH-485, but the Partlow 1160 temperature values never arrive, and adding the interface converter changes nothing. The converter's documented modes are point-to-point isolator, RS-232 to RS-485 isolator and RS-232 to half-duplex RS-485; none of them rewrites frames. The same media-versus-protocol confusion appears in other serial faults, for example when a Modbus RTU drive poll on one serial port is slow for timing reasons rather than protocol ones.
Which name is the medium and which is the protocol? #
RS-485 and RS-232 are electrical interfaces; DH-485, ASCII and Modbus RTU are protocols that decide what the bytes mean, and only the protocol has to match at both ends of a conversation.
Put the four names in the right boxes:
- RS-485: the differential multidrop signaling used by both the DH-485 network and the Partlow port.
- DH-485: a token-passing network protocol for Allen-Bradley controllers, documented for up to 32 nodes; only devices that speak it can hold a node address.
- ASCII or Modbus: the two protocols the Partlow 1160 lets you select for its serial port.
- 1761-NET-AIC: an interface converter between RS-485, RS-232 and DH-485 physical connections; the vendor's own user manual lists isolation and media conversion modes, not protocol translation.
Because the Partlow never transmits DH-485 frames, wiring it onto the DH-485 cable with matching terminators produces no readable data and can disturb the bus for the devices that do belong there.
Why does the MicroLogix 1000 fail even before wiring? #
The MicroLogix 1000 serial channel speaks DF1 or DH-485 only: it has neither the ASCII instructions and string data files nor Modbus RTU support needed to talk to the controllers.
Its user manual describes exactly those two protocols for the serial port. So even with a perfect converter and cable, there is no instruction to send an ASCII command or a Modbus request, and no string file to parse a reply into. The controller has to change, not the wiring.
Which controller arrangement actually works? #
Use a MicroLogix 1100 with the serial port dedicated to the Partlow controllers and Ethernet kept for programming and monitoring; that is the cleanest single-processor answer for this job.
The decision per case:
- MicroLogix 1000: reject, for the reason above.
- MicroLogix 1100: serial channel to the temperature controllers in ASCII or Modbus RTU, Ethernet for upload, download and online monitoring. The engineering path survives because it is a different port.
- MicroLogix 1200 Series B: Channel 0 can run ASCII or Modbus, but it is the only port; once switched, that channel no longer serves DF1 or DH-485. The Communications Toggle push button restores the default communications mode on Channel 0, but recovery means walking to the panel, and there is no remote monitoring while the port runs the device protocol.
- MicroLogix 1500 LRP: separate channels, so the controller link never consumes the programming or DH-485 path.
- SLC 500: ASCII only in this selection path; it has no Modbus RTU support, so it fits only if you choose the Partlow's ASCII mode.
The same one-port, one-protocol rule is why an S7-200 cannot share one RS-485 port with a PC and Modbus on this library.
How do you set up the working path? #
Configure the Partlow mode, the PLC channel and the serial format as one matched set, then poll one controller before adding the rest.
- Select ASCII or Modbus at the Partlow 1160 and note its serial format and addressing from its documentation.
- On the MicroLogix 1100, configure the serial channel for that protocol; a Channel 0 Modbus RTU setup is covered step by step in Configure MicroLogix 1100 Channel 0 for Modbus RTU, and the drive-side version in Connect a MicroLogix 1100 to a PowerFlex 4M over Modbus.
- Build a separate serial segment with only the controllers on it, following the manuals for polarity, reference conductor, shield, biasing and end-of-line termination.
- Match baud rate, data bits, parity and stop bits at both ends, and give each multidrop controller a unique address where the protocol requires one.
- Read the Partlow data representation before scaling: decide from its register map whether the PLC needs integer scaling, an implied decimal point or a float.
How do you verify each layer separately? #
Test from the wire upward: controllers first, then the PLC value, then the DH-485 side, so a failure tells you which layer owns it.
Confirm the existing DH-485 devices still communicate with the Partlow equipment disconnected. Poll one controller and watch the instruction's error and status bits or receive buffer. If a value arrives but is wrong, check register selection, word order, sign and decimal scaling against the controller's display; if nothing arrives, the fault is protocol or serial format, not scaling. Then go online over Ethernet, upload and monitor while the polling runs, and only map the value to the PanelViews after the serial link is stable.
Questions asked
Can a Modbus gateway translate between DH-485 and a Partlow controller?
Only if the gateway explicitly lists DH-485 and Modbus or ASCII on both sides, which most Modbus gateways do not. A device that converts DH-485 to Modbus RTU is a protocol gateway, a different product class from the interface converter, and the MicroLogix would then appear to the controllers as a Modbus master through that gateway rather than over a shared cable.
What does the MicroLogix 1200 default communications button actually restore?
It toggles Channel 0 between your configured communication settings and the default communications mode, giving a local way back to programming after the channel was set to ASCII or Modbus. It requires physical access to the processor, so it recovers the port but does not give remote upload, download or monitoring while the port runs the device protocol.
Why does the MicroLogix 1000 fail here beyond the protocol issue?
Its serial support covers DF1 and DH-485; it offers neither the ASCII instructions and string data files needed to build controller command frames nor Modbus RTU slave or master support. Even with correct wiring and an interface converter, there is no instruction set in the controller to send a request or parse a reply, so the hardware choice fails before any code is written.