Explainer
Why PZD1 and PZD2 are fixed in a PPO2 telegram
Short answer
PPO2 carries four PKW words and six PZD words, 20 bytes per direction. The first two PZD words are fixed by the PROFIdrive profile: word 1 is the control or status word, word 2 the speed setpoint or actual value, and only words 3 to 6 are assignable, in the drive's parameter set rather than in TIA Portal. Values scale as signed integers with 16384 equal to 100 percent.
On this page
- What does a PPO2 telegram contain?
- Which PZD words are fixed and which can you assign?
- Can the actual speed be moved to PZD word 3?
- Why do the PZD input addresses differ from the output addresses?
- How do you assign PZD3 to PZD6 in the drive?
- How do PZD values scale?
- How do you verify the mapping at startup?
- Questions asked
In a PPO2 telegram the first two PZD words are fixed by the PROFIdrive profile and only words 3 to 6 are assignable, and that assignment lives in the drive's parameter set, not in the TIA Portal hardware configuration. Four PKW words plus six PZD words make 20 bytes per direction. Torque limit, actual torque and DC link voltage go in the free words. This article gives the word map, the input and output addresses that catch people out, the scaling arithmetic, and the startup checks that prove each word in both directions.
What does a PPO2 telegram contain? #
A PPO2 telegram carries four PKW words followed by six PZD words in each direction, so 8 bytes of parameter channel plus 12 bytes of process data equals 20 bytes per direction. PKW is the parameter channel: a four-word mailbox that reads and writes drive parameters inside the cyclic frame, one parameter per handshake. PZD is the process data: the cyclic setpoints and actual values. PPO is the pairing of the two areas. If the split is new to you, how PZD and PKW telegrams divide PROFIBUS drive communication is the background to have before you map a single address.
Because the PKW handshake runs across all four words at once, it needs data consistency over the full 8 bytes; single word accesses give no such guarantee. Read and write the PKW area with your controller's consistent-access instructions against the module start address, and use direct word access only for PZD. That handshake requirement is also why PKW words stay empty while cyclic PROFIBUS data works on some setups.
Which PZD words are fixed and which can you assign? #
PZD word 1 and word 2 are fixed: word 1 is the control word outbound and the status word inbound, word 2 is the speed setpoint outbound and the actual speed inbound, and only words 3 to 6 are yours to assign. The profile requires the leading pair in every telegram; what the drive lets you change are the interconnections behind words 3 and up.
| PZD word | Output, PLC to drive | Input, drive to PLC |
|---|---|---|
| 1 | Control word, fixed | Status word, fixed |
| 2 | Speed setpoint, fixed | Actual speed, fixed |
| 3 | Assignable, typically torque limit | Assignable, typically actual torque |
| 4 | Assignable | Assignable, typically DC link voltage |
| 5 | Assignable | Assignable |
| 6 | Assignable | Assignable |
Decision: if your data list stops at control, status, speed setpoint and actual speed, words 3 to 6 can stay unassigned and the telegram still works. If you need torque or DC link values, keep PPO2 and fill words 3 to 6 in the drive; you never obtain those signals by renumbering words 1 and 2.
Can the actual speed be moved to PZD word 3? #
No: every PPO type keeps the same leading pair, so PPO3 carries exactly the control or status word and the speed setpoint or actual value in its two PZD words, and every larger PPO puts the free words behind them. The structures stay coherent across the whole family, and that coherence is what lets one master program handle several drive sizes. The drive keeps sending its status word on word 1 and its actual speed on word 2 whatever your program believes.
A program written for actual speed on word 3 reads whatever connector sits there, often an unassigned word, while the drive answers words 1 and 2 correctly the whole time. Decision: if an existing program expects the actual value on word 3, rewrite the program to read word 2. Do not rebuild the telegram around a program; the telegram is the fixed side.
Why do the PZD input addresses differ from the output addresses? #
TIA Portal allocates the PKW and PZD submodules independently, so a PPO2 slot commonly starts its PZD outputs at byte 276 and its PZD inputs at byte 280, which puts PZD3 outbound and PZD1 inbound on the same word number 280. The allocation is legal, but it is a trap for anyone who reads the input map and reuses the number on the output side.
| Area | Direction | Byte range | Word accesses |
|---|---|---|---|
| PKW | In and out | 256 to 263 | 4 words each way |
| PZD | Output, PLC to drive | 276 to 287 | PQW276 to PQW286 |
| PZD | Input, drive to PLC | 280 to 291 | PIW280 to PIW290 |
The hazard in one line: PQW280 is PZD3 outbound while PIW280 is PZD1 inbound, so a torque limit meant for word 3 lands in the control word if you copy input numbers to outputs. Decision: edit the two PZD start addresses in the device overview so both begin at the same byte, for example 280 in and 280 out, then shift every output access in the program by the four bytes you moved. The rest of this article keeps the default allocation so its addresses match what the device overview shows before that edit.
How do you assign PZD3 to PZD6 in the drive? #
You assign words 3 to 6 inside the drive's parameter set: on a MASTERDRIVES with a CBP2 board that means BICO interconnections set with DriveMonitor, not anything in the TIA Portal hardware configuration. DriveMonitor V5.5 SP2 connects over the board's serial service interface or an existing bus connection, and the wider sequence for configuring drives: PKW, PZD and AC motor commissioning sits either side of this mapping.
- Set the board's basic parameters from the CB parameter list in the Compendium: bus address, number of process data words, telegram failure time. The word count must equal the PPO configured in the master.
- Point the control word source selection at the board's received word 1 and the main setpoint source at received word 2, so the fixed words stay fixed. Received PZD words appear as drive connectors; the connector numbers for the CB interface are tabulated in the Compendium's communication chapter.
- Set the torque limit source to the connector that represents received PZD3. A value written to the output word with no destination selected sits in the connector and does nothing.
- In the board's actual-value assignment parameter, leave index 1 and index 2 at status word and actual speed; set index 3 to the torque actual value connector and index 4 to the DC link voltage connector.
- Store the parameter set to non-volatile memory and power cycle the drive so the board re-initializes with the new word count.
How do PZD values scale? #
PZD values are 16-bit signed integers with 16384, written 16#4000, equal to 100 percent of the reference quantity, and the drive's reference speed, reference torque and reference voltage parameters define what 100 percent means. Worked example with the reference speed parameter at 6000 rpm: to command 3000 rpm, compute 3000 rpm ÷ 6000 rpm × 16384 = 8192, which is 16#2000, and write that to the setpoint word. On the way back, a returned 8192 means 8192 ÷ 16384 × 6000 rpm = 3000 rpm. A readback at half or double the expected value means the reference speed parameter differs from the base your scaling assumed.
One gate sits in front of the scaling: the drive accepts a serial setpoint only when the control word bit that grants control to the automation system is set. Send 16#047E and then 16#047F and that bit is included; a hand-built control word without it leaves the drive on its terminal or keypad source no matter how correct the address map is. The same gate is usually behind missing setpoint and control word writes to a PROFIBUS drive.
How do you verify the mapping at startup? #
Verify in order: GSD variant, node address, configured length, a raw status word, one PKW read, then the enable sequence with the motor safe to move. Each check has one expected result, so a failure tells you which layer to fix before you touch the program.
- GSD variant. Three GSD files exist for the MASTERDRIVES family; confirm the device name in the hardware catalog matches the CBP2 board actually fitted. Expect the station to reach data exchange after download. A mismatch leaves the station flagged in the online view and the drive reporting a board configuration or initialization fault; read the fault number from the drive fault list, do not guess it.
- Node address. Compare the drive's PROFIBUS address parameter with the address in the hardware configuration; expect identical numbers and the CBP2 bus LED indicating cyclic exchange rather than search or fault state.
- Configured length. In the device overview, expect exactly 8 input bytes plus 12 input bytes and 8 output bytes plus 12 output bytes for PPO2. Any other total means the wrong PPO was dragged in.
- Raw status word. Put PIW280 in a watch table with the drive energized and no enable applied: expect a non-zero value that changes when you remove an OFF2 or OFF3 signal at the terminals. A constant 16#0000 means no data exchange, or that the board's send word 1 has been reassigned away from the status word.
- Parameter channel. Issue one parameter read over PKW: the response echoes the requested parameter number in the first PKW word.
Then run the drive, on the default allocation and with the machine clear and the motor safe to drive at reference speed, because a wrong reference parameter sends the shaft to full speed at a command you meant to be half:
- Write 16#047E to PQW276. Expect the status word to report ready to switch on.
- Write 16#047F with PQW278 at 16#0000. Expect the drive to energize at zero speed and the status word to report operation enabled.
- Write 16#4000 to PQW278. Expect acceleration to the reference speed and the same normalized value back at PIW282.
- Write 16#C000, minus full scale. Expect reverse rotation and a negative value at PIW282.
- Write 16#2000 to PQW280 with the motor loaded. Expect the drive's torque limit display to read 50 percent of reference torque and PIW284 to track actual torque up to that ceiling.
- Compare PIW286 with the drive's DC link voltage display. Expect the scaled percentage to match within display resolution; zero means index 4 of the actual-value assignment was left unset.
When every step returns its expected value, the mapping is done: words 1 and 2 carry what the profile says, words 3 to 6 carry what you assigned, and the program can be trusted with the machine.
Questions asked
What changes if I select PPO3 instead of PPO2?
PPO3 keeps only the two fixed process data words, four bytes per direction, and drops the PKW area entirely. You lose parameter access over the bus and the four assignable words, and the address areas shrink to match. Choose it when the drive is commissioned from its own tools and the PLC needs nothing beyond control word, status word, speed setpoint and actual speed; keep PPO2 whenever torque or DC link values must travel cyclically.
Does a second CBP2 board in the same drive need its own mapping?
Yes. Each board is a separate PROFIBUS slave with its own node address, its own telegram setting and its own parameter set, so the word structure repeats per board and the master allocates a separate address area for each. Give the two boards distinct node addresses, assign words 3 to 6 separately on each board that carries process data, and verify each board with the same startup sequence.
How do I convert actual torque and DC link voltage into engineering units?
Apply the same normalization as the speed word: divide the returned signed integer by the full-scale count and multiply by the drive's reference torque or reference voltage parameter, which is the base the drive used when it scaled the value. Those reference parameters are listed in the Compendium; record them during commissioning, because the raw word alone does not reveal the base it was scaled against.
Is the different input and output start address an error I must correct?
No. The split is only how TIA Portal allocated the two submodules, and the drive sees an identical telegram either way; a program addressed to the default map runs correctly. Equalizing the start addresses is a readability edit for the programmer, not a repair for the drive. If you make it, move every output access in the program by the same offset in the same session, or control word writes will land one word off.