SCADA and data logging Published 6 min read By IMDHMI controls team

Short answer

#COM on a CJ1M variable tag means Citect's I/O server has no working device behind it, even though ping and CX-Programmer succeed. On the v6 DVD set the working chain is the Citect FINS driver (not OMFINS), Omron FINS Gateway 2003 running on the PC, and a CX-Integrator routing table that places the ETN21 at FINS network 1, node 1, with FINS/TCP on port 9600.

On this page
  1. What #COM is telling you
  2. Why the CS1 Ethernet 2 pick is right and still dead
  3. The fix, in order
  4. A worked mapping from PC to DM500
  5. If the display still shows #COM
  6. The serial Host Link alternative
  7. Questions asked

#COM on a Citect display is the I/O server's report that the variable tag has no live device behind it. Your evidence already clears the usual suspects: ping, your own socket programs and CX-Programmer all reach the CJ1M, so the cable, the ETN21 and the PLC are good. What is missing is the Citect side of the FINS chain. On the v6 DVD set, three pieces must exist before DM500 will move: the Citect FINS driver installed (OMFINS is not it), Omron FINS Gateway 2003 running on the PC with an Ethernet unit entry, and a routing table transferred from CX-Integrator that places the ETN21 at FINS network 1, node 1. FINS/TCP then runs on port 9600.

What #COM is telling you #

Citect prints #COM when the I/O server cannot get a value for a variable tag. The tag, the DM500 address and the page are all fine: a wrong address on a healthy device returns a wrong or rejected value, while a device that never opens puts #COM on every tag it serves. Read the placeholder as a missing I/O device, not a network fault.

The device you defined on the Omron CS1 Ethernet 2 driver has no complete path to the CPU, because the chain has three links and your bench has none of them yet:

  • The Citect FINS driver. The driver that lets a Citect I/O device speak FINS to CS1 and CJ1 Ethernet units. It comes from Citect's driver download.
  • FINS Gateway 2003. Omron's middleware on the Citect PC that carries FINS between the Citect driver and the ETN21. On v6, the driver's data path runs through it.
  • The PLC routing table. Built and transferred with CX-Integrator so the CPU can route FINS frames to the Ethernet unit in its rack.

Why the CS1 Ethernet 2 pick is right and still dead #

Two things are true at once. The CJ1M never appears by name in Citect's driver list, the reason is covered in why Citect 6.10 does not list the Omron CJ1M as a driver, and the CS1 and CJ1 families share one FINS Ethernet driver path, so the CS1 entry you chose is the correct family. But on the v6 DVD that path carries data only when the Citect FINS driver package is installed and FINS Gateway 2003 is running underneath it. With either piece missing, the I/O server has nothing to open, every poll fails, and the page shows #COM.

OMFINS is the trap worth naming. It is Omron's FINS component library for custom programs to call, not a Citect I/O device driver: installing it registers a library and adds nothing the I/O server can load, so the display stays at #COM. The Citect FINS driver is a separate download from Citect, and it is the one this path needs.

The fix, in order #

  1. Install FINS Gateway 2003 on the Citect PC. The installer is part of the CX-One distribution. Its configuration tool holds the Ethernet unit entries, and the runtime runs as a Windows service that must be started; a saved entry over a stopped service looks exactly like your current #COM.
  2. Install the Citect FINS driver. Download it from Citect's driver download and install it into Citect. Keep OMFINS out of the I/O server entirely.
  3. Build and transfer the routing table. In CX-Integrator, connect online to the PLC and open Routing table − Settings. Create the FINS local network table entry that puts the ETN21 at network number 1, node number 1, then transfer the table to the CPU. Building the table and never transferring it is the most common way to stay at #COM with everything else right.
  4. Configure the gateway's Ethernet unit. In the FINS Gateway configuration, add an entry for the ETN21 with the same network and node numbers as the routing table, its IP address, protocol FINS/TCP, and port 9600, the documented FINS/TCP default. Save and restart the gateway service.
  5. Point the Citect I/O device through the chain. Keep the device on the CS1 Ethernet driver entry with network number 1 and node number 0: node 1 on that network is the ETN21 itself, node 0 behind it is the CPU. Recompile the project and restart the I/O server.

A worked mapping from PC to DM500 #

Example addresses for the bench; substitute your own.

Side FINS network FINS node Address
Citect PC (gateway local node) 0 (local) 10, from the PC IP's last octet 192.168.1.10
ETN21 1 1 192.168.1.20, FINS/TCP port 9600
CJ1M CPU 1 0 reached through the ETN21

Check the subnet arithmetic first. PC: 192.168.1.10 AND 255.255.255.0 = 192.168.1.0. ETN21: 192.168.1.20 AND 255.255.255.0 = 192.168.1.0. Same network on both ends, no router in the path, which is why ping succeeds and why ping tells you nothing about FINS. The FINS network number and the IP subnet are separate numbering systems; they meet only in the gateway's Ethernet unit entry.

The proof is your own ladder. Poll the tag once per second (an example poll time), and a healthy display advances with the program: 1 count per second × 60 s = 60 counts per minute. Watch DM500 in CX-Programmer at the same time. If CX-Programmer steps while Citect shows #COM, the PLC side is proven and the fault is in the five steps above; if both freeze, your timer stopped, not the comms.

If the display still shows #COM #

Each item here is a complete cause on its own:

  • The gateway service is not running. Saving an entry in the configuration tool is not the runtime; check the Windows service list and start it.
  • The routing table was never transferred. In CX-Integrator the table lives in the project until you transfer it to the CPU.
  • Network and node swapped. The gateway's Ethernet unit entry is the one for the ETN21; the Citect device is the one for the CPU. Reversed, every poll misses.
  • Protocol mismatch. A FINS/UDP entry against a driver set for FINS/TCP, or the reverse, polls into silence.
  • A firewall on a newer Windows. Allow the gateway's FINS traffic through, or ping keeps working while #COM stays, since ping proves only ICMP. For a frame-level check on this exact pair, work through a FINS/TCP connection troubleshooting walkthrough for the CJ1M and ETN21.
  • OMFINS installed in place of the Citect FINS driver. Remove it from the equation and install the Citect driver.

Once #COM clears, a tag that updates but logs FINS errors under load is a different fault, with its own checks in fixing Citect SCADA FINS errors to an Omron NX1P2. The chain also transfers across Omron's Ethernet units: the same FINS route to a CP1 with its CP1W-CIF41 board is covered in connecting Citect SCADA to a CP1W-CIF41 over FINS.

Serial does not rescue the Ethernet setup, but it is a valid training path on its own. Wire the PC's COM port to the CJ1M's peripheral port and select a CS1 Series Serial Protocol (Sysway) driver for the I/O device; the FINS Gateway can act as the serial FINS bridge on the same principle as the Ethernet side. Typical Host Link line settings are 9600 bit/s, 7 data bits, even parity, 2 stop bits, unit number 0, so match whatever the PLC port is set to. Addressing does not change: the same variable tag keeps DM500, and the same logic holds, since a serial device that never opens shows the same placeholder.

Decision for this bench: on v6, Ethernet means the Citect FINS driver, FINS Gateway 2003 and the routing table, in that order of likelihood to be missing; Sysway is the fallback; and #COM always means one of those links is absent, never a proven network fault.

Questions asked

Can CX-Programmer and Citect talk to the CJ1M at the same time?

Yes. Set CX-Programmer's own connection to go through FINS Gateway as well, so both tools share one managed FINS path to the ETN21 instead of contending for it. The same arrangement lets CX-Programmer and Citect connect to CX-Simulator through the gateway, which makes a SCADA test bench with no PLC attached, useful for training before you touch the CJ1M.

Do later Citect releases still need FINS Gateway?

No. Later releases let the I/O device reach a CS1 or CJ1 Ethernet unit directly over TCP/IP or UDP, which removes the gateway and its service from the PC. The PLC routing table does not go away, though: the CPU still needs the entry that maps its Ethernet unit before it answers Citect's FINS frames. Your v6 DVD set predates the direct option, so on it the gateway path is the one that works.

What timeout should the Citect I/O device use?

Set 5000 ms on this bench. A healthy FINS exchange across one subnet answers in well under a second, so the timeout exists to cover gateway startup and an occasional retried frame, not slow hardware. Much shorter and you get false #COM flicker while FINS Gateway initializes; much longer only delays the verdict when the chain is broken. It is a workable bench figure, not a Citect requirement.

How do I address other CJ1M memory areas from Citect?

The prefix selects the area and the number is the word address: DM500 is data memory word 500, W covers the work area, HR the holding relays and AR the auxiliary relays, all through the same variable-tag mechanics. Match the data type to how the ladder uses the word, an INT for a counter like yours. A wrong prefix on a healthy device returns a wrong or rejected value; #COM always means the device itself is down.

Keep reading

  • How-to

    Connecting Citect SCADA to a Modbus RTU gateway over MODNET

    Yes — MODNET is Citect's driver for Modbus over TCP/IP, and a true RTU-to-TCP converter presents standard Modbus TCP on its Ethernet side, so the combination works. Success then rides on two things: the gateway's operating mode, and carrying the RTU slave address and register offsets into Citect correctly, proved by reading one register whose value you can see at the device.

    SCADA and data logging

  • Troubleshooting

    Why Citect 6.10 does not list the Omron CJ1M as a driver

    Citect 6.10 communicates with the Omron CJ1M even though no CJ1M entry appears in the driver help. The CJ1 family shares the CS1 communications selection, so configure the device as a CS1; where the installed driver offers no matching selection, commission the Omron FINS Gateway route. Prove the link with one read-only tag at a known CJ1M address before adding the rest of the database.

    SCADA and data logging

  • How-to

    How to connect Citect SCADA to an S7-300 over Ethernet

    Yes — Citect reaches an S7-300 over Industrial Ethernet through either the S7NT driver, which requires licensed Siemens communication software on the I/O server, or the PSDIRECT driver, a paid direct driver that needs only an Ethernet interface on the PLC. Configure the device with the PLC's IP address plus rack 0 and slot 2; a wrong slot or rack is the usual reason a ping succeeds while no data comes back.