Short answer
Citect 6.10 communicates with the Omron CJ1M even though no CJ1M entry appears in the driver help. The CJ1 family shares the CS1 communications selection, so configure the device as a CS1; where the installed driver offers no matching selection, commission the Omron FINS Gateway route. Prove the link with one read-only tag at a known CJ1M address before adding the rest of the database.
On this page
- Can Citect 6.10 connect to an Omron CJ1M?
- Why does the driver help list no CJ1M entry?
- Which device type do you select instead of CJ1M?
- Which serial port settings does the CJ1M need?
- When do you need the Omron FINS Gateway instead?
- How do you prove the link before adding the whole tag database?
- What makes a good connection read the wrong value?
- Questions asked
Citect 6.10 communicates with the Omron CJ1M, and the missing driver entry is not a blocker. The CJ1 family uses the same communications selection as the CS1 in Citect, so you configure the I/O device as a CS1 and the driver frames the FINS requests the CJ1M answers. Where your installed driver gives no matching selection, the documented alternative is the Omron FINS Gateway route that Omron's own Citect serial setup guide uses. This article walks the decision in the order you meet it: why the CPU is absent from the help file, which device type to pick, which serial settings the CJ1M supports, when the FINS Gateway is the right path, and how one read-only tag proves the link before you add the rest of the tag database.
Can Citect 6.10 connect to an Omron CJ1M? #
The CJ1 family and the CS1 family are the same as far as Citect's driver is concerned, so Citect 6.10 talks to a CJ1M through the CS1 device type, and Omron's own serial setup guide for Citect connects a CJ1 CPU through the FINS Gateway drivers. A missing CJ1M label therefore does not block the connection.
What the driver codes against is the protocol, not the CPU catalog number. Both families answer the same FINS service messages, so a driver entry written for the CS1 frames requests the CJ1M handles unchanged. You have two independent confirmations here: Omron publishes a Citect-to-Omron serial setup guide built around a CJ1 PLC and the FinsGateway drivers, and engineers who have commissioned this exact pair select CS1 for the communications and report no difference at the Citect end.
Why does the driver help list no CJ1M entry? #
The driver help organizes entries by CPU family and protocol path rather than by every catalog number, and CJ1 serial communication is FINS encapsulation that the existing Omron driver entries already carry, so the CJ1M rides a selection that has been there all along.
FINS is Omron's Factory Interface Network Service protocol, and it runs over both serial transports and Ethernet as UDP/IP. Because the CJ1M speaks FINS on every port it exposes, the driver decision reduces to which transport your wiring uses, not to which CPU sits at the far end. That is why the help file can omit the CJ1M by name without the pair being unsupported: the family-level entry and the protocol are the things the software actually needs.
Which device type do you select instead of CJ1M? #
Select the CS1 device type in the I/O device configuration: for the Citect driver the CJ1 family presents itself exactly as a CS1, and in most projects this one change is the entire fix.
The equivalence covers the communications path only. Memory capacities, option slots and the PLC program remain CJ1M-specific, so the addresses you enter must still be valid on this CPU and this application. An address copied from an example project written for another controller can be wrong here even though the connection comes up, so take the test address from the CJ1M's own project rather than from a sample.
Which serial port settings does the CJ1M need? #
Serial work on the CJ1M runs between 38.4 kbps and 115.2 kbps, so set both ends inside that documented range and match the CPU's DIP switch settings to the port and protocol you actually use.
The range comes from Omron's datasheet for CJ1M CPU units, which states that the CJ-Series supports serial communications from 38.4 kbps to 115.2 kbps. On the CJ1M, the peripheral port runs the Toolbus protocol when its DIP switch 4 is on, so check the switch before blaming the cable. The SCADA computer's serial port must mirror the CPU settings exactly, bit rate, parity and stop bits together.
Worked example, line time per poll: at 38.4 kbps with 8 data bits, no parity and one stop bit, each byte takes 10 bits on the wire, so the line carries 38,400 bits/s ÷ 10 bits/byte = 3,840 bytes/s. A single FINS poll-and-response exchange of an illustrative 70 bytes then uses 70 ÷ 3,840 ≈ 18 ms of pure line time; add the CPU's scan and turnaround and a poll period of 50 to 100 ms per device is a realistic starting point. At 115.2 kbps the same illustrative frame costs 70 ÷ 11,520 ≈ 6 ms, which is why faster serial rates buy you tag count before they buy you anything else.
When do you need the Omron FINS Gateway instead? #
You need Omron FINS Gateway when your installed driver offers no selection matching the physical connection, or when the serial path is the FinsGateway-based route Omron's Citect setup guide documents for CJ1 projects.
FINS Gateway is software on the SCADA computer that carries FINS between the Citect driver and the port, so it is an alternative architecture to commission, not an automatic add-on: installing it does not make every driver use it. License it through Omron's normal channel and check its operating-system requirements before changing a working computer. Commission it PLC-side first: where a gateway diagnostic read is available, read the same known CJ1M address you planned for the Citect test. If the gateway reads and Citect does not, the fault sits between the application and the gateway; if neither reads, the route to the CPU is the problem, and no amount of Citect tag editing will fix it.
How do you prove the link before adding the whole tag database? #
Configure one read-only tag at an address you have confirmed live in the PLC programming software, run the project, and judge the link by tag quality plus one controlled value change rather than by the number on the screen.
A displayed number alone proves nothing, because a screen can hold a stale or configured substitute value. Work the first tag in this order:
- Record the installed driver, its revision, and the device type you selected.
- Trace the physical path end to end: Ethernet or serial, and any gateway sitting in between.
- Pick a known CJ1M address and confirm its contents in the programming software; the checks in fixing an Omron CJ1M serial connection that will not go online cover that side of the link.
- Enter the address with the driver's documented syntax and a data type matching the PLC value.
- Compile, update the runtime under the site's normal procedure, and read quality first.
- Change one safe, nonhazardous value at the PLC and watch Citect follow it with good quality.
Keep that first tag read-only, so a communications investigation can never write a machine command or setpoint by accident. When quality stays bad and the diagnostics show timeouts, the fault is in the route, and the method in fixing Citect SCADA FINS errors to an Omron NX1P2 transfers directly, because both faults are FINS paths that never answer.
What makes a good connection read the wrong value? #
Good quality with a wrong number is a tag problem, not a link problem: check word versus bit addressing, signed interpretation, scaling and multiword storage before touching the driver, because a display can also hold a configured substitute value.
Compare the Citect value against the live value in the programming software at the same moment. If they disagree, change one thing at a time, the address form first, then the data type, then any scaling, so each test still tells you something. Once one tag reads correctly, save the working device configuration with its driver revision and route noted, add a small representative set of tags covering every data representation the application uses, and only then expand to the full database. Changing the driver selection, route, address and data type together throws away the diagnostic value of every test you just ran.
Questions asked
Can Citect 6.10 reach the CJ1M over Ethernet instead of serial?
Yes, on CJ1M CPUs that carry Ethernet function, such as the models with the -ETN suffix. FINS runs over Ethernet as UDP/IP just as it runs over serial, so the same FINS-facing driver selection applies. You assign the CPU an IP address and the FINS node address its documentation specifies, and cross-network destinations need the routing tables set on the controller side. Confirm the Ethernet details against the datasheet for your exact CPU unit before committing the project.
Which Citect driver handles FINS over a serial line?
Serial communication with CJ-series CPUs is based on the FINS encapsulation protocol, and the Citect driver built for it is the OMFINS family; installations in the field carry the OMFINS3 revision. If your Citect 6.10 install lists an OMFINS-family driver, serial FINS to the CJ1M runs through it, so check that driver's own help for the device types and connection methods it supports rather than adding anything new.
Does selecting CS1 change anything on the CJ1M itself?
No. The CS1 device type only tells the Citect driver how to frame and address its FINS requests, so the CJ1M's PLC program, I/O assignments and memory map are untouched. The addresses you type into Citect must still be valid on this CPU, and their data types must match what the PLC program actually stores there, exactly as with any other Omron tag.