Troubleshooting
Why an S7-1200 download in run demands a STOP transition
Short answer
Download in Run on the S7-1200 works only when the physical CPU runs firmware 2.2, the CPU in the project's hardware configuration is also set to 2.2, and TIA Portal is V11 SP2 or higher. The usual culprit is the configured firmware: the project still describes an earlier CPU, so the preview demands STOP even for a small FC edit. Set it to 2.2, recompile, and the edit loads with the run light green.
On this page
When TIA Portal demands a STOP transition for nothing more than a modified segment in an existing FC, the controller on the rail is usually innocent. Download in Run on the first-generation S7-1200 needs three versions aligned: the physical CPU at firmware 2.2, the CPU in the project's hardware configuration also set to 2.2, and TIA Portal at V11 SP2 or higher. The one that gets missed is the middle one. A project that still describes an earlier CPU forces the STOP prompt no matter what firmware the controller actually runs. Check the configured firmware first, correct it, recompile, and the same edit transfers with the run light green.
What Download in Run covers #
Download in Run means transferring an eligible change while the CPU stays in RUN; the controller never leaves that mode, so its run indication stays green through the transfer. It never meant that every offline modification can land without a stop. The documented split is plain: modified code in a block that already exists on the CPU, such as an FC, is the eligible case, while downloading OBs or DB structure changes requires STOP. Everything here is stated for the first-generation S7-1200 as published in the firmware 2.2 delivery release on Siemens Industry Online Support, entry 57027057.
Three versions decide, and each check is independent #
| Check | Where you read it | Required |
|---|---|---|
| Online CPU firmware | the connected controller, in the online view | 2.2 |
| Configured CPU firmware | the CPU object in the project's hardware configuration | 2.2 |
| Engineering software | the installed TIA Portal | V11 SP2 or higher |
The engineering system evaluates the device declared in the offline project, not only the controller on the rail. The configured firmware selection decides which CPU functions are exposed and which download rules get applied, which is why a CPU already running the new firmware still draws a STOP prompt when the project describes the old one. The two firmware values are separate tasks: editing the project entry does not update the controller, and updating the controller does not correct the project. An upload refused between engineering versions is a different fault, covered in why an S7-1200 upload fails across TIA Portal versions.
Read the symptom before the fix:
| What you see | Likely cause | Next check |
|---|---|---|
| STOP demanded for a small FC edit | the project describes an earlier CPU | the configured firmware in the hardware configuration |
| Configured 2.2, still no run-mode transfer | the CPU or the software sits below its minimum | the online firmware and the installed version |
| Some edits transfer in RUN, others demand STOP | the change set touches an OB or a DB structure | the changed-object list in the load preview |
| CPU stays green through the transfer | all three checks passed | confirm the edited logic executes |
Working the case: an FC edit demands STOP on V11 SP2 #
Inputs, with where each comes from:
- Online CPU firmware: 2.2, read from the connected controller; this CPU had already been updated.
- Configured CPU firmware: an earlier level, 2.1 in this example, read on the CPU in the hardware configuration, untouched since before the update.
- Engineering software: V11 SP2, the installed TIA Portal version.
The rule: the run-mode transfer is offered only when all three inputs meet their minimum, meaning both firmware values at 2.2 and the software at V11 SP2 or higher. Each check stands alone; one failure withholds the transfer.
The check, written out:
- Online CPU firmware: 2.2 against a minimum of 2.2, pass
- Configured CPU firmware: 2.1 against a minimum of 2.2, fail
- Engineering software: V11 SP2 against a minimum of V11 SP2, pass
- Two of three checks pass, so Download in Run is withheld and the preview demands STOP
The configured firmware is the only failing input; the controller and the software already qualify. Set the configured CPU firmware to 2.2, recompile, and download the FC edit on its own: the preview then offers the transfer without STOP and the CPU stays in RUN. The threshold cuts both ways. Any firmware value below 2.2, or software below V11 SP2, forces the stop prompt, so fix that input before touching the download again.
Which changes can transfer in RUN #
Version alignment opens the door; the change set decides whether a given download may walk through it.
| Change in the download | Run-mode expectation | Action |
|---|---|---|
| Modified logic in an existing FC | eligible once the three versions align | compile, read the preview, transfer in RUN |
| DB structure change | requires STOP, because the memory layout moves | plan value handling and a stop window |
| OB download | requires STOP | find it in the changed-object list |
| Mixed set | the strictest object wins and the whole download demands STOP | split the logic edit into its own download |
Fix the configured firmware first #
- Read the online firmware of the connected CPU and continue only when it meets the required level; an earlier CPU takes the vendor's documented firmware update first.
- Confirm the installed engineering software is V11 SP2 or higher; the package question is covered in software needed to program an S7-1200 PLC.
- Open the hardware configuration, select the CPU, read its configured firmware and, where it names an earlier level, set it to 2.2.
- Compile hardware and software, and clear every compile error before any transfer; a clean compile separates version problems from program errors.
- Reduce the download to the intended edit, modified logic in an existing FC, with no DB structure, OB or hardware change riding along.
- A run-mode transfer takes effect the moment it lands, so make it only when the process tolerates the new logic acting immediately, and keep safety-function changes inside their own validated procedure.
- Start the download with the CPU in RUN, read the preview and the mode prompt, and confirm only when no STOP is requested.
Checks that close the case #
- The online firmware meets the required level.
- The configured firmware in the project matches it.
- The installed software is at the required service pack or newer.
- The preview offered the transfer without a STOP request; had it demanded one, the right move was to cancel and read the changed-object list.
- The CPU stayed in RUN, run light green, through the transfer.
- The edited network executes: monitor it online and watch the affected outputs or internal values follow the new path.
All six hold and the symptom is closed. Versions aligned but the preview still demanding STOP means the change set carries a structural object: return that object to the stop-window list and transfer the FC edit alone. A CPU below the required level makes the download question premature; update the controller first, then align the project.
Questions asked
How do I update the physical CPU to firmware 2.2?
Get the firmware update file from Siemens Industry Online Support, load it onto a SIMATIC memory card, insert the card into the CPU and power-cycle, or run the update from the CPU's online and diagnostics tools. Either way the controller is offline for the update, so schedule it as an outage. Once it reports the new version online, align the project's configured firmware, recompile, and the run-mode path opens.
Does a newer TIA Portal than V11 SP2 support Download in Run on this CPU?
Yes. The requirement is V11 SP2 or higher, so any later engineering version satisfies the software check while the two firmware conditions stay the same. Download in Run arrived with the firmware 2.2 delivery release of December 2011, which also brought SCL and an AS-Interface master communication module to the first-generation CPU.
What should I do before a download that needs STOP for DB or OB changes?
Copy the current program from the CPU first so the running version can be restored, then book a stop window for the structural download. Only logic inside blocks that already exist belongs in a run-mode transfer; OB and DB structure changes keep their STOP requirement regardless of how the versions are set.
Can several edited FCs go into one run-mode download?
Yes. Eligibility follows the changed objects, not their count, so several existing FCs with modified code can go in one transfer as long as no OB, DB structure or hardware configuration change rides along. Keep the set small enough that you can verify every edited network online right after the CPU accepts it.