Why a WinCC RT Advanced PC cannot bridge Profibus to Profinet

Industrial networks Published 8 min read

Short answer

A WinCC RT Advanced PC station cannot itself convert Profibus DP into Profinet traffic. It opens either a Profibus DP channel through a Profibus CP in the PC, or an Ethernet channel to the PLC through onboard Ethernet or the IE General module. The translation has to sit in an S7 CPU that owns both interfaces or in an IE/PB Link PN IO, never in the visualization PC.

On this page
  1. Can a WinCC RT Advanced PC convert Profibus into Profinet?
  2. Which channels can a WinCC RT Advanced PC station actually use?
  3. How different are Profibus DP and Profinet frames?
  4. Where does the Profibus-to-Profinet conversion have to sit?
  5. How do you connect the PC when the PLC owns both networks?
  6. What if the PLC is Profinet-only and the machines are Profibus DP?
  7. When does the WinCC PC actually need a Profibus CP?
  8. Which setup should you choose for each case?
  9. Questions asked

A WinCC RT Advanced PC cannot bridge Profibus to Profinet — the conversion has to sit in a controller or a link module, never in the visualization PC. The runtime opens exactly one kind of channel to each network: a Profibus DP channel that needs a Profibus CP fitted in the PC station, or an Ethernet channel that runs on the PC's onboard network card or the IE General module. Profibus DP and Profinet are different networks at every layer below the tag, so no WinCC setting, driver or channel type turns one into the other. This article gives you the two channel options a PC station actually has, the reason software cannot do the conversion, where the converter belongs, and the decision for each plant case: a PLC with both ports, a Profinet-only controller with Profibus devices, and a DP-only PLC.

Can a WinCC RT Advanced PC convert Profibus into Profinet? #

No: WinCC RT Advanced is a supervisory runtime, and its PC station can open either a Profibus DP channel through a Profibus CP or an Ethernet channel to a PLC, but it never translates Profibus DP telegrams into Profinet frames.

There is no configuration trick behind this, either. Profibus DP is a polled RS-485 bus run by a DP master at 9.6 to 12 Mbit/s, while Profinet is real-time traffic on standard switched Ethernet, so the frames do not even share a format. A WinCC channel is a client on exactly one of these networks: it reads and writes tags in a controller and never forwards traffic between them. The engineering tools draw the same boundary — in a PC station's device configuration, Profibus arrives only when you insert a Profibus CP into a slot, Ethernet arrives with onboard Ethernet or the IE General module, and no component exists whose function is to sit between the two.

Which channels can a WinCC RT Advanced PC station actually use? #

Two: a Profibus DP channel that needs a Profibus CP in the PC, and an Ethernet channel that runs over the PC's onboard network card or the IE General module in the PC station.

The WinCC engineering documentation in TIA Portal states the Profibus prerequisites directly: the HMI device needs a PROFIBUS interface, and in the "Connections" editor you select the "MPI/DP" interface under Parameters > Interface and set the "DP" profile. On a PC station that PROFIBUS interface is a card you insert into the station's configuration — a PCI or PCIe Profibus CP such as the CP 5612 A2 or CP 5622, or the USB CP 5711.

The Ethernet channel usually needs no card at all. Add the "IE General" module from the hardware catalog under PC systems > Communication modules > PROFINET/Ethernet, and the runtime binds the PC's normal onboard network interface. The connection to the controller is then created in the same "Connections" editor with the driver matching the CPU family — for example the "SIMATIC S7 1200" driver — pointed at the CPU's address. When the controller offers Ethernet, take the Ethernet channel: it adds no hardware to the PC and no PC communication software.

How different are Profibus DP and Profinet frames? #

Different enough that a converter has to repackage every byte: Profibus DP moves up to 246 bytes of I/O data per polling telegram over RS-485 at 9.6 to 12 Mbit/s, while Profinet moves Ethernet frames with up to 1500 bytes of payload at 100 Mbit/s.

Each side also runs a different traffic pattern. A DP master polls each slave in a fixed cyclic order, so Profibus carries short, deterministic telegram pairs; Profinet sends addressed Ethernet frames through a switch. A converter therefore cannot route between them — it terminates the DP cycle on one side and generates Profinet IO updates on the other, satisfying both cycles independently. That terminate-and-generate function lives in the converter's hardware and firmware, which is exactly the function no WinCC channel contains.

The wire-time numbers make the difference concrete. Illustrative example, not a measured result: take one DP polling exchange with 32 bytes sent to the slave and 32 bytes returned. Profibus transmits each character as 11 bits (1 start, 8 data, 1 parity, 1 stop), so the I/O data alone is 64 bytes × 11 bits = 704 bits. At 1.5 Mbit/s that is 704 / 1,500,000 bit/s ≈ 0.47 ms per cycle; at the 12 Mbit/s top of the Profibus range it is 704 / 12,000,000 bit/s ≈ 0.06 ms, and real DP cycles add telegram headers and the master's polling order on top. The comparable Ethernet figure: a full 1500-byte payload frame at 100 Mbit/s takes 12,000 / 100,000,000 bit/s = 0.12 ms. Different format, different cycle discipline — nothing maps one onto the other byte for byte, which is what a "bridge" would have to do.

Where does the Profibus-to-Profinet conversion have to sit? #

In hardware that owns both interfaces: an S7 CPU with a Profibus module such as the CM 1542-5 on an S7-1500 or the CM 1243-5 on an S7-1200, or a dedicated link such as the IE/PB Link PN IO — never in the WinCC PC.

The first converter is the controller itself: a CPU that owns both interfaces, natively like the integrated DP interface of an S7-300-class CPU, or by adding a DP module to the rack. The CPU runs the DP master cycle, and its program copies values between the DP process image and the data its Profinet side serves to clients. The retrofit workflow for exactly this pattern is in converting PROFIBUS to PROFINET on an S7-300 retrofit.

The second converter is a dedicated link. The IE/PB Link PN IO is a Profinet IO device toward the controller and a DP master on its Profibus side, so the DP slaves are configured under the Link and appear in the controller's process image as Profinet submodules. The same rule holds for a generic converter: a PROFIBUS to EtherNet/IP gateway configuration for HMI and PLC terminates one protocol and serves the other, and the HMI talks only to the serving side.

How do you connect the PC when the PLC owns both networks? #

Give the WinCC PC the Ethernet channel and connect it to the CPU: the PLC already holds data from both subnets, so the runtime reads one S7 connection on Profinet and never sees Profibus at all.

Configure the DP side in the PLC project — the integrated DP interface or the added DP module as DP master, slaves attached, process image mapped — and leave the PC alone. In the WinCC project, create one S7 connection in the "Connections" editor to the CPU's Ethernet address, with the driver matching the CPU family. Every tag then reads the merged data through that one connection, and the acquisition cycle you set per tag decides how fresh the values are.

The failure mode worth knowing in advance: if values show bad quality on this path, the cause is almost always the connection to the CPU or the tag addressing, not the DP bus. The article on why HMI values show question marks: PLC comms timeouts walks that diagnosis.

What if the PLC is Profinet-only and the machines are Profibus DP? #

Put the converter between them and keep the WinCC PC Ethernet-only: the IE/PB Link PN IO, or the DP module in a CPU you add, terminates Profibus, and the PC reads everything through Profinet.

Configure the Link as a Profinet device of the controller with its device name and IP address, then set its Profibus side up as DP master with baud rate and the slave list. The DP slaves appear in the controller's process image, and the WinCC PC stays exactly as in the previous case: one Ethernet channel to the CPU.

Resist the tempting alternative of fitting a Profibus CP into the PC to reach the DP subnet directly. That gives the PC a channel on the wrong network: the CP terminates Profibus on the PC side, the PLC still speaks Profinet, and the two channels cannot exchange anything. You would add hardware and PC software without moving one byte of data, because the conversion exists only in the CPU or the Link.

When does the WinCC PC actually need a Profibus CP? #

Only when the PLC it must read offers a Profibus DP port and no Ethernet route you are allowed to use: then fit a Profibus CP in the PC station and build the connection as a DP connection with the MPI/DP interface and the DP profile.

That is the legacy case: a DP-only controller, or a cabinet where the Ethernet side belongs to a separate network. Insert the Profibus CP into the PC station's configuration, give the CP its own station address on the DP subnet, and build the connection with the "MPI/DP" interface and the "DP" profile as the documentation prescribes. Budget for the CP's PC communication software as part of the change — the card's driver alone does not create the WinCC channel.

One guard rail while you commission this channel: the PC joins the DP subnet as its own station and must never take the master role away from the PLC that controls the machines, or the polling cycle that runs the process is at risk.

Which setup should you choose for each case? #

Choose the Ethernet channel to a CPU that owns both networks, add an IE/PB Link PN IO or a DP module when the controller is Profinet-only, and reserve a Profibus CP in the PC for DP-only PLCs.

  • Controller with both a DP port and Profinet: Ethernet channel from the PC to the CPU, one S7 connection, no converter to configure.
  • Profinet-only controller with Profibus DP machines: IE/PB Link PN IO, or a DP module in a CPU, as the converter; the PC reads the CPU over Ethernet.
  • DP-only controller: Profibus CP in the PC station, connection built with the "MPI/DP" interface and the "DP" profile, the CP as its own station on the subnet.

If a proposal ever shows runtime software converting between these networks, treat it as a sign the converter is missing from the drawing — put it in the CPU or in the Link, and the WinCC project becomes an ordinary Ethernet client.

Questions asked

Can one WinCC PC run a Profibus channel and an Ethernet channel in parallel?

Yes. A PC station can hold a Profibus CP and the IE General module at the same time, one channel per subnet, and tags on each network are read through their own channel. That is still not a bridge: the two channels never exchange telegrams with each other, and data that must move between the subnets is copied by the program in the CPU that owns both interfaces.

Does a Profibus CP in the PC need extra software before WinCC can use it?

Yes. The CP's Windows driver alone is not a WinCC channel; the SIMATIC NET PC software matched to the card, for example the SOFTNET-DP product class for a PCI or USB Profibus card, has to be installed with its own license before the runtime can bind the channel. The Ethernet path avoids this entirely, because WinCC RT Advanced talks to an onboard network card through the IE General entry with no extra PC software.

Does this rule also apply to WinCC RT Professional and Unified PC stations?

As far as the network technology goes, yes. The channel model lives in the PC station configuration, not in one runtime product: a Windows visualization PC reaches a Profibus network only through a Profibus CP and reaches Profinet through onboard Ethernet or the IE General module, and conversion between the two still happens in a CPU or a link module, never in runtime software.

WinCC values stay bad after adding the converter — what do I check first?

Check the converter before the HMI: confirm the CPU or link module is online on both subnets, that its DP slaves are configured and not reporting diagnostics, and that the WinCC connection points at the CPU rather than at the converter's Profibus address. Only then open the runtime's channel diagnosis; if the channel shows connected but values stay bad, the fault is usually in the tag addressing or on the DP side.

Keep reading

  • How-to

    Measure PLC to SCADA command response time end to end

    Timestamp the button press and the observed status change with one monotonic PC clock, then split the interval into PC write handling, the PROFIBUS DP bus cycle, the PLC scan and tag acquisition with rendering. A healthy DP bus cycle is 1–10 ms, so a round trip of hundreds of milliseconds is almost all SCADA tag update cycles and screen redraw. Shorten the tag cycles you measured as the bottleneck, not the network.

    Industrial networks

  • Troubleshooting

    Reaching PLC-5 and SLC 500 data through a ControlLogix DH+ bridge

    Yes. An OPC UA server reaches PLC-5 and SLC 500 processors through a ControlLogix Ethernet-to-DH+ bridge when its Allen-Bradley driver documents routed legacy access. Confirm the driver, inventory the bridge modules, build each connection path to the DH+ node, and prove one read — the 1756-DHRIO carries 32 connections per DH+ channel.

    Industrial networks

  • Troubleshooting

    Why an Ignition S7-400 device stays disconnected by CPU slot

    The device stays Disconnected because the S7-400 driver's CPU slot defaults to 2 while this CPU sits in slot 3 of its rack: the IP address names the CP 443-IT, and the rack and slot name the CPU. Set the CPU slot to the STEP 7 hardware-config position (3 here, rack 0) and the device connects; a later Bad_ReadOnly write error is a tag-access fault, not a slot fault.