How-to

Converting PROFIBUS to PROFINET on an S7-300 retrofit

PLC programming Published 7 min read

Short answer

A PROFIBUS-to-PROFINET gateway can keep a CU320-2 DP servo on the existing DP segment behind an S7-1500, but it adds a transfer delay and cannot provide isochronous synchronization, so it suits non-synchronized axes only. Split the migration into controller, drive, SIMOTION and HMI projects, and handle each one separately.

On this page
  1. What is on the DP segment today
  2. What a gateway does and does not do
  3. Example: judging gateway suitability for one CU320-2 DP axis
  4. Three architectures for the drive segment
  5. Migration sequence: four separate projects
  6. The decision for each part of this retrofit
  7. Questions asked

Yes: a PROFIBUS-to-PROFINET gateway can keep the CU320-2 DP servo on its existing DP segment behind an S7-1500, but only if the axes do not need isochronous synchronization, because a gateway adds its own transfer delay and cannot carry synchronization services across. The clean answers to the six questions: keep the drive behind a gateway for non-synchronized operation, expect an added transfer delay on the DP side, select the S7-1500 against the real I/O and program demands rather than by name, migrate the STEP 7 project through TIA Portal's migration workflow, keep the SIMOTION program as a separate engineering decision, and rebuild or convert the HMI from its ProTool source. This article works through each of those decisions in order.

What is on the DP segment today #

The installed controller is a CPU 314C-2DP, order number 6ES7 314-6CG03-0AB0, with 24 digital inputs, 16 digital outputs, five analog inputs and two analog outputs on board, plus one additional analog output module. Its PROFIBUS network carries an S120 control unit identified in the project as S120_CU320_2_DP with order-number string 6SL3 040-1MA00-0xxx, three Phoenix field I/O modules and one Festo module. The drive order-number string is incomplete; read the full nameplate on the control unit before selecting a gateway or a replacement, because the trailing digits fix the firmware and option set.

Opening the project in SIMATIC Manager V5.7+SP1+HF1 reported missing SIMOTION and ProTool software. Installing SIMOTION SCOUT V5.4.3.0 cleared the SIMOTION part and left the ProTool warning. Neither error means PROFIBUS communication has failed: they are engineering-software dependencies of the project, not faults on the network.

What a gateway does and does not do #

PROFIBUS DP exchanges cyclic process data on a serial fieldbus; PROFINET IO exchanges process data on industrial Ethernet. A DP/PROFINET gateway connects the two by holding a DP-master role toward the retained devices and a PROFINET-device role toward the new controller, transferring mapped data between the two independently scheduled networks.

It does not turn a DP interface into a native PROFINET interface. Check before committing:

  • The gateway provides the DP-master function the old CPU provided, and the correct PROFINET IO role toward the S7-1500.
  • The configured telegram, the agreed layout of cyclic control and feedback words, matches on both sides: length, word order, control and status words, setpoint and actual values, and any consistency requirement.
  • Acyclic access used for parameter services and diagnostics still reaches the drive through the gateway.
  • The gateway's device-description file describes its interface, not compatibility with every drive function; a matching GSD alone proves nothing about timing.

The transfer delay is the deciding number. The gateway must wait out the PROFIBUS cycle, buffer the data, then forward it; a faster Ethernet link on the PROFINET side does not shorten the DP cycle or the gateway's processing. A speed or pressure reference tolerates that added delay. Synchronized multi-axis operation does not: a gateway cannot provide isochronous synchronization across the conversion, so speed/position-referenced axes need either the drive moved to a PROFINET control unit or the DP segment retained under a DP master the new controller reaches. Decide where motion actually executes first, in the PLC, in a SIMOTION controller, or inside the drive; the answer determines whether the gateway is acceptable at all.

Example: judging gateway suitability for one CU320-2 DP axis #

Take one speed-controlled axis on the DP segment. Suppose the PROFIBUS DP cycle for the segment is 4 ms and the configured telegram carries a 4-word control block and a 4-word feedback block. The gateway adds its own processing and buffering, so the S7-1500 sees setpoint changes that are at least one DP cycle plus the gateway stage old, roughly 4 ms plus the gateway's internal transfer before the new value even leaves the PROFINET side, call it 8 ms end to end for this example.

For a speed reference on a conveyor, an 8 ms added latency against a drive that ramps over seconds is harmless: commit to the gateway. For two axes geared to each other where the application needs position updates locked to the same clock, 8 ms of uncontrolled skew between the networks breaks the synchronization: do not use a gateway for those axes; put the drive on a PROFINET control unit or keep the DP segment under a DP master. The numbers move with your actual DP cycle and the gateway's documented delay, so substitute your own telegram configuration and check both before ordering, but the decision rule stands: tolerance in milliseconds of latency keeps the gateway, clock-locked axes do not.

Three architectures for the drive segment #

Architecture What remains on PROFIBUS Deciding constraint
S7-1500 plus DP/PROFINET gateway CU320-2 DP and compatible DP field devices Gateway roles, telegram support, acyclic parameter access, added transfer delay, no isochronous synchronization
S7-1500 with a supported DP master interface or module The whole existing DP segment directly Controller or module compatibility with the existing devices and their functions
Replace every DP endpoint with PROFINET devices Nothing; DP removed completely New interfaces compatible with the application, full re-engineering of drive and I/O configuration

The first architecture modernizes the controller while keeping the drive on DP. The second does the same without introducing a gateway at all. Only the third removes PROFIBUS, and it requires converting or replacing every endpoint: the CU320-2 DP would become a PROFINET control unit, verified against the complete drive configuration including power modules, feedback and firmware, and each Phoenix and Festo module checked individually for a supported PROFINET variant or replacement.

An S7-1500 replacement is a functional redesign, not a one-for-one substitution. Match the CPU 314C-2DP's integrated 24 DI, 16 DO, 5 AI and 2 AO plus the extra analog output module with suitable channels, and compare electrical characteristics, not just counts. Size program capacity, execution and communication interfaces against the application. For the controller-side conversion itself, the steps are the same as in migrating an S7-300 project to TIA Portal, and Siemens documents the whole route in the Migration Guide: SIMATIC S7-300/400 to SIMATIC S7-1500.

Migration sequence: four separate projects #

Replacing the network does not convert the engineering projects automatically. Split the work:

  1. Preserve the baseline. Archive the complete STEP 7 project, drive parameter backups, HMI files, hardware configuration and GSD files. Expected result: every installed programmable device has an identified backup or a documented recovery gap.
  2. Convert the controller project. In TIA Portal, use the Migrate project workflow to convert the STEP 7 V5.x project, then review the migration report, replace unsupported hardware in the hardware configuration and adapt addressing and instructions. Expected result: a compiling target project with every conversion exception reviewed; the report is the proof, not the absence of a dialog box.
  3. Assess SIMOTION separately. SCOUT engineers SIMOTION applications, and its presence in the project does not prove the servo program belongs to SIMOTION. Identify the SIMOTION controller, its runtime version and the application objects, then decide retain, convert or re-engineer. There is no automatic one-step SCOUT-to-TIA conversion; expected result is an explicit decision per motion application.
  4. Recover or rebuild the HMI. The remaining ProTool warning maps to a legacy HMI project. Find the panel it belongs to and locate the editable ProTool source: with the source, the project converts to WinCC in TIA Portal; without it, rebuild screens, tags, alarms and scripts in WinCC. Legacy intermediate software needed for conversion comes through official vendor channels only.
  5. Reconfigure communications. Point the HMI connection, addressing and tags at the new controller, and configure the gateway or DP master in the S7-1500 hardware configuration.

If the migration reaches the point where you need a computer at the machine to run the engineering station or a SCADA client during commissioning, an industrial panel PC mounted at the console serves that role.

The decision for each part of this retrofit #

  • Servo (S120_CU320_2_DP): gateway-retain it if the axes are speed-referenced and unsynchronized; move it to a PROFINET control unit or keep a DP master if the application needs isochronous synchronization. Read the full order number from the nameplate first.
  • Phoenix and Festo field I/O: check each module individually for a PROFINET variant or replacement; manufacturer identity alone does not establish interchangeability.
  • Controller: migrate to an S7-1500 selected against the integrated I/O count and the program's demands, not against the CPU naming.
  • STEP 7 project: migrate in TIA Portal and review the migration report line by line.
  • SIMOTION program: keep as a separate engineering decision; no automatic conversion exists.
  • HMI: recover the ProTool source and convert it, or rebuild in WinCC; the ProTool warning clears only when that project is resolved.

One safety note: before first download on the new controller, verify that every drive safety function and emergency stop path still acts through the new network architecture exactly as validated on the old one, and re-validate the safety function as a whole; a network change that passes process data can still change safety-relevant behavior.

Questions asked

Will a PROFIBUS-to-PROFINET gateway affect the speed between the S7-1500 and the servo?

Yes, by adding a transfer stage. The gateway must complete a full PROFIBUS DP cycle, buffer the data, then forward it over PROFINET, and the faster Ethernet link does not shorten the DP side. For a speed or pressure reference this added delay is usually tolerable; for multi-axis synchronization it is not, because a gateway cannot carry the isochronous synchronization services the axes need.

Can the CU320-2 DP control unit be kept as it is behind a gateway?

Only for non-synchronized operation. The CU320-2 DP (order number family 6SL3 040-1MA00-0xxx) keeps its PROFIBUS interface, and the gateway acts as DP master toward the drive and PROFINET device toward the S7-1500. Verify the gateway supports the configured telegram length, control and status word layout, acyclic parameter access, and diagnostics before committing. For synchronized axes, convert the drive to a PROFINET control unit or keep a DP master on the new controller.

Can a SIMOTION SCOUT program be migrated into TIA Portal?

There is no automatic one-step conversion of a SCOUT application into TIA Portal. Treat the motion program as a separate engineering artifact: identify the SIMOTION controller and runtime version, check the supported migration route for that version, and decide to retain, convert or re-engineer. The SCOUT version documented in the notes, V5.4.3.0, resolved the missing-software error in SIMATIC Manager V5.7+SP1+HF1, but the motion application still needs its own migration decision.

How do I fix the remaining ProTool missing-software error?

The warning means the STEP 7 project references a legacy HMI project engineered with ProTool. Find which panel in the project tree needs it, then locate the editable ProTool source. With the source you can convert the project to WinCC in TIA Portal; without a source, rebuild the screens, tags, alarms and scripts in WinCC. Installing SIMOTION SCOUT does not clear this warning, because it is an HMI engineering dependency, not a motion one.

Can the whole SIMATIC Manager program be migrated to TIA Portal V17 in one step?

The controller project converts through the Migrate project workflow in TIA Portal, and Siemens documents the route in the S7-300/400 to S7-1500 migration guide. But one migration does not carry everything: HMI objects need the ProTool source, the SIMOTION application needs SCOUT-based engineering, and unsupported hardware must be replaced in the hardware configuration. Read the migration report line by line and review every conversion exception before downloading.

Keep reading

  • Selection guide

    How to choose an S7 PLC family for a machine

    For a new machine, pick the S7-1200 when the job is standalone control with modest I/O and one or two axes, and the S7-1500 when you need coordinated motion, controller-integrated safety, a fast scan or a large I/O count. Use S7-300 and S7-400 only to extend plants that already run them. Program both current families in TIA Portal.

    PLC programming

  • How-to

    Migrating S7-300 projects from STEP 7 v5.5 to TIA Portal

    You can migrate an S7-300 project from STEP 7 v5.5 into TIA Portal with the migration tool, but the converted project goes online without showing online blocks: timestamps in the CPU no longer match, so TIA treats the program as inconsistent and wants a full transfer after any change. Keep the classic toolset for large programs and firmware updates; use TIA for small S7-300 projects that gain a unified project with an HMI or an S7-1200.

    PLC programming

  • Troubleshooting

    Fix STEP 7 V5.5 warning after TIA Portal wrote an S7-300

    Download the hardware configuration and blocks from a freshly created SIMATIC Manager project and the warning clears; a CPU 313C-2DP recovered exactly this way. Formatting the MMC with the mode switch (MRES held roughly 9 s until the STOP LED stays lit) does not clear the TIA-written state, so use it only when you also want the card empty.

    PLC programming