Choosing how a CLICK PLC commands VFD speed safely
Short answer
Keep the proven RS-485 link as the speed reference and let the drive's acceleration and deceleration ramps enforce the motion limit, with the encoder supervising. A 0-10 V analog reference is an equally safe alternative; a pulse train is only a frequency reference and is unconfirmed on this drive. None of the three is a personnel-safety function.
On this page
Keep the RS-485 link you already proved. Write the frequency target to the drive when it changes, let the GS31-22P0's acceleration and deceleration ramps enforce the motion limit, and use the encoder to verify the platform actually stayed inside it. A 0-10 V analog reference does the same job one way; the pulse train buys you nothing here and its function on this drive is unconfirmed. None of the three interfaces is a personnel-safety function — that is decided by a risk assessment, not by the command path. The general five PLC-to-VFD interfaces compared article covers the field broadly; this one commits for a C2-03CPU, a GS31-22P0 on a 2 hp induction motor, and a revolving stage that carries actors.
What each interface actually carries #
The GS31-22P0 cut sheet lists its input signals as 4-20 mA, voltage, potentiometer or pulse train, at 12-bit resolution, with current input ranges of 0-20 mA and 4-20 mA. All three of your candidates exist on paper. What separates them is what each one carries, not how fast it carries it.
| Interface | What it carries | What it depends on | What it is not | Call |
|---|---|---|---|---|
| RS-485 (Modbus RTU) | Frequency target, start and stop commands, plus status and fault words in the other direction, on one wire pair | The wiring you already proved; register addresses from the drive's Modbus map | An instantaneous control signal; a safety function | Use it |
| 0-10 V analog (or 4-20 mA) | A one-way frequency reference, 12-bit | An analog output on the PLC side, common reference, scaling and filtering verified; signal-loss behavior decided | A status channel; proof the requested speed was reached | Valid substitute |
| Pulse train | Pulses as a frequency reference, where the drive supports it | Terminal assignment, accepted pulse range and scaling from the drive manual — currently unresolved | A position command; the VFD closes no position loop on the pulses | Drop it |
For this stage the call is RS-485, for two reasons you have already paid for: the link works, and it is the only one of the three that returns drive status and faults on the same pair of wires. Its "not for real-time" reputation comes from servo-cycle control, where a torque or position loop closes at kilohertz rates. A stage reference is a target that changes when the operator changes it, and the drive ramps to the last target it received.
Analog is an equally safe substitute if you want the reference hard-wired. Over the documented 4-20 mA range a broken wire reads under-range instead of zero command, which the drive can be configured to fault on — decide that before anyone stands on the platform. Voltage mode gives you no such tell.
The ramp enforces the limit, not the loop #
Sort the variables first: desired speed and desired position are setpoints; encoder-derived speed and position are measured variables; the frequency written to the drive is the manipulated output. A PID loop will not conjure an acceleration limit out of any of them. A PID's correction is bounded only by its output limits, so a position error becomes an instantaneous frequency step the platform has to follow. The limit belongs upstream, in the trajectory — here, the drive's acceleration and deceleration ramp parameters, defined in this drive class as the time from zero to maximum output frequency.
For a speed-controlled revolve you do not need a speed PID at all. The VFD holds the commanded frequency, slip makes platform speed mildly load-dependent, and the encoder's job is supervision: alarm when differentiated speed exceeds the assessed limit, alarm when commanded frequency produces no motion. Add closed-loop position correction only after you have measured how the platform stops open loop, and rate-limit that correction to the same ramp.
The pulse-train question, settled #
The GS31-22P0 cut sheet lists pulse train input, and, as you found, the manual does not document the terminal assignment, the accepted pulse range or the pulse-to-frequency scaling. A cut-sheet line is not a commissioning input: until the manual names those, the path is unverified on this drive, which is reason enough to drop it.
It is also the wrong instrument where it does work. In the GS30 series the documented pulse input is one of seven digital inputs rated to 33 kHz, and it serves as a frequency command. That is what pulse input means on this drive class: pulses set output frequency, and the drive's ramp and the motor's slip stand between the command and the shaft. A servo in pulse-train mode is a different contract — the drive closes a motion loop on the pulses.
The CLICK PLUS side encourages the confusion. Its pulse-train output motion is well supported, down to limit-switch inputs assignable to any input pin, and the software will profile velocity and acceleration for one-axis moves. Those profiles describe the pulses, not the platform. The gap between a controller emitting step and direction and a drive that consumes only a velocity reference is exactly the subject of driving step and direction inputs from a controller velocity output.
Decision: no pulse train on this stage. It offers nothing over RS-485 or analog, and its function on this specific drive is unconfirmed.
Sizing the ramp: 3 m radius, 0.5 rpm top speed, 0.1 m/s2 edge limit #
Inputs, with sources:
- Platform radius r = 3.0 m — example input; measure your own deck.
- Top stage speed 0.5 rpm — example cue speed.
- Tangential acceleration limit at the platform edge a-t-max = 0.1 m/s2 — example value. Its basis: ISO 2631-1 rates whole-body vibration below 0.315 m/s2 weighted RMS as not uncomfortable for standing persons, and 0.1 m/s2 holds you under a third of that, leaving margin for jerk and uneven loading. The binding number comes from your risk assessment, and the arithmetic below converts whichever value it sets.
- 2 hp induction motor on the GS31-22P0 and a high-PPR rotary encoder — the application as built.
Rules in words: on a linear ramp from rest, angular acceleration is final angular velocity divided by ramp time, and tangential acceleration at the edge is radius times angular acceleration — so the minimum ramp time is radius times angular velocity divided by the limit. Centripetal acceleration at constant speed is radius times angular velocity squared, and it adds to what a standing person feels.
Arithmetic:
- omega-max = 0.5 rev/min x 2-pi / 60 = 0.0524 rad/s
- alpha-max = 0.1 m/s2 / 3.0 m = 0.0333 rad/s2
- t-min = 0.0524 / 0.0333 = 1.57 s
- Set both ramp parameters to 2.0 s: a-t = 3.0 x (0.0524 / 2.0) = 0.079 m/s2, a 21 percent margin under the limit.
- Centripetal at full speed: a-c = 3.0 x 0.0524-squared = 0.0082 m/s2 — under a tenth of the limit, so ramping governs, not rotation.
- Deceleration point: theta = 0.0524-squared / (2 x 0.0333) = 0.0411 rad = 2.4 degrees.
Decision: scale the reference so full-scale command equals 0.5 rpm at the deck, set acceleration and deceleration ramps to 2.0 s, and start deceleration 2.4 degrees before the cue mark, trimmed by the overshoot you measure. The relationship is linear, so a stricter limit scales the ramp directly: a 0.05 m/s2 limit needs (3.0 x 0.0524) / 0.05 = 3.14 s minimum, so set 3.5 s. Verify with the encoder that measured angular acceleration stays at or below 0.0333 rad/s2 in both directions, loaded and empty.
What the encoder is for #
Three supervisory jobs, none of them regulation:
- Verify the ramp: differentiate encoder speed during acceleration and deceleration, both directions, loaded and empty; alarm above the assessed limit — 0.0333 rad/s2 in the example.
- Verify the stop: measure actual overshoot past the 2.4-degree deceleration point and trim the cue accordingly.
- Detect what a frequency command cannot see: commanded frequency with no platform motion (stall, sheared coupling), and platform motion with no command.
Mounting decides what the loop measures. An encoder on the motor shaft sees slip and nothing downstream; an encoder on the platform or a final shaft sees the truth, including transmission faults and backlash. Calibrate counts per platform revolution by measured rotation in both directions, because backlash makes the ratio differ by direction.
The boundary none of these interfaces crosses #
One note, and it carries the load: RS-485, analog and pulse train are standard control channels, and none of them protects a person. A stage carrying actors needs a risk assessment — ISO 12100 gives the method: identify the hazards, estimate and evaluate the risk, then reduce it by inherently safe design first, safeguarding second, information for use last. The safeguards it calls for are designed and validated to the PL (ISO 13849) or SIL (IEC 62061) the assessment specifies; those are separate ratings, and validation covers the complete machine function, not the controller alone.
Make the protective stop real in hardware: use the drive's documented safe-stop input where the manual provides one, or break the path to the motor in the way the chosen stop category requires. Until that validation is complete, run every ramp and stop test with the platform empty.
Questions asked
Is the GS31-22P0 pulse train input a position command like a servo's?
No. The cut sheet lists pulse train among its input signals, and on this drive family a pulse input is a frequency command — the GS30 series documents its pulse input as a digital input rated to 33 kHz. A servo in pulse mode closes a motion loop on the pulses; this VFD does not. The GS31's terminal assignment and pulse-to-frequency scaling still have to come from its manual, and you have not found them there.
How often should the PLC rewrite the frequency command over RS-485?
Only when the target changes. The drive ramps toward the last target it received, so a late or missed write leaves motion bounded by the configured ramp instead of uncontrolled. Updates faster than your cue source changes speed add nothing. Spend the poll cycle on the status and fault words instead — analog wiring carries nothing back at all.
Why not close a PID loop on encoder speed to enforce the acceleration limit?
Because a PID's correction is bounded only by its output limits, not by an acceleration limit: a position or speed error becomes a frequency step the platform must follow. The limit belongs in the trajectory, meaning the drive ramp. Use the encoder to supervise — alarm when differentiated speed exceeds the assessed limit, and when commanded frequency produces no motion.
Is 12-bit analog resolution fine enough for stage speed?
Yes. Twelve bits give 4096 counts across the span: 2.44 mV per step on a 10 V reference, or 0.024 percent of full scale. Against a 0.5 rpm top speed that is 0.00012 rpm per step, roughly four orders of magnitude finer than cue positioning needs. Resolution is never the binding constraint on this stage; ramp and stopping behavior are.
What should the PLC do when the encoder signal disappears?
Treat it as a stop condition. Command the drive down through its deceleration ramp, inhibit further cues, and latch the fault for inspection. The ramp still bounds the stop. Running a people-carrying stage open loop, with speed commanded but never measured, is exactly the condition the risk assessment has to rule out.