Troubleshooting

Why a Twido to Citect Modbus RTU link shows no data

SCADA and data logging Published 8 min read

Short answer

A Twido to Citect Modbus RTU link shows no data for one of five reasons: the polling roles, the serial framing, the station address, the port owner, or an unproven register map. Make Citect the Modbus master and the Twido serial port the Modbus RTU slave, match every framing field, and prove one documented register before any tag is imported.

On this page
  1. Put Citect in the master role and the Twido port in the slave role
  2. Match the framing, the station address and the port owner
  3. Check the wiring before the software
  4. Set the Twido port as the Modbus RTU slave
  5. Configure the Citect channel, device and first tag
  6. Map the first register from the addressing document
  7. Read the symptom against the layer
  8. Example: what one two-register read costs at 19200 baud
  9. Decide from the symptom you see
  10. Questions asked

No data from a Twido to Citect over Modbus RTU traces to one of five causes, and they repay checking in this order: the polling roles, the serial framing, the station address, the port owner, and the register mapping. The configuration that works is Citect as the Modbus master (client), the Twido serial port as the Modbus RTU slave (server), every framing field matched on the two ends, and one documented register proven before any tag is imported. The sections below take those five checks in turn, add the wiring checks that produce the same silence, and finish with the arithmetic that tells you whether the link, once talking, is fast enough for the poll rate you planned.

Put Citect in the master role and the Twido port in the slave role #

Modbus RTU allows one master on a segment. Two masters talk over each other; two slaves sit silent while every poll times out. For SCADA the workable split is fixed: Citect owns the poll rate, the retries and the writes, and the Twido port answers. If Citect reports timeouts from the very first request, suspect the roles before the wiring — a Twido port left in programming mode, or configured as a Modbus master for a previous project, will never answer. Schneider's Twido Modbus documentation demonstrates the two roles with two Twidos, one master and one slave; in a Citect project the SCADA side takes the master's half of that example and the Twido keeps the slave's.

Match the framing, the station address and the port owner #

Every field in this list must agree at both ends before the first request goes out. Schneider's FAQ FA229090 for putting a Twido on Modbus RTU specifies port 1 at 19200 baud, 8 data bits, even parity, 1 stop bit and slave address 1; start from those numbers or change both ends together.

  • Baud rate — identical on the Citect port and the Twido port; 19200 is Schneider's documented value for this link.
  • Data bits — 8 on both ends. RTU frames need 8 data bits; a port left at 7 data bits is set up for Modbus ASCII and never decodes RTU.
  • Parity — even on both ends, unless you deliberately move both ends off it at the same time.
  • Stop bits — 1 on both ends.
  • Station address — the address on the Citect device equals the Twido slave address and is not zero; address 0 is the broadcast address on a serial segment and collects no individual reply, which is its own fault with its own page: Why Modbus RTU sends to slave address 0 instead of your device.
  • Port owner — one application at a time. Close TwidoSuite, terminal tools and any other serial driver before Citect opens the port; a port shared with a second application gives you transmit LEDs and no data.

A framing mismatch silences the link even while every LED on the converter flashes, so compare the fields side by side instead of trusting yesterday's settings.

Check the wiring before the software #

The Modbus serial-line specification runs RTU over RS-485, so the pair, its reference and its termination are physical checks, not driver settings. Terminate at the two ends of the segment and nowhere else, keep the shield continuous as the device documentation requires, and connect the signal reference where that documentation calls for one. One swapped data pair produces exactly the silence a framing error produces, which is why the deciding test in the symptom table below is swapping the pair once before rewriting any configuration. A converter left in its RS-232 mode, or powered down at one end, belongs to the same layer. Diagnose the physical side separately from the register map, and change one thing at a time so the trail stays readable.

Set the Twido port as the Modbus RTU slave #

  1. Open the controller's configuration in TwidoSuite and go to the Describe page, where each serial port's role and framing are set.
  2. Set the port that faces Citect to type Modbus, RTU mode.
  3. Enter the framing from the list above and the slave address for your segment, matching the number you will enter on the Citect device.
  4. Transfer the configuration to the controller and confirm it accepted it; from that transfer on, the port belongs to the Modbus link, not to the programming session.
  5. If a 499TWD01100 Ethernet gateway sits between the Twido and Citect instead of a direct serial run, Schneider's setup FAQ for that gateway starts from the same step: the Twido port configured for Modbus slave with a node address assigned.

Configure the Citect channel, device and first tag #

  1. Point a Citect channel at the serial port wired to the Twido and copy every framing field from the PLC side, including the fields you did not expect to matter.
  2. Define the I/O device with the Modbus RTU driver and enter the Twido station address as its device address; the details live in Setting the Modbus slave ID for a Citect I/O device.
  3. Add one read-only tag on the register you took from the addressing document. Do not import the tag database yet: one tag separates a transport fault from a database fault, while an imported set hides the first bad address among retries and quality alarms.
  4. Compile, start communications and judge the tag's quality before its value. Good quality with a value that tracks a change you made at the PLC is the proof the link works.
  5. Prove a write on a spare data word, with the machine in a state where a wrong value cannot move anything, before enabling operator writes.

If the serial side ends in a gateway rather than a direct cable, the Citect half of that arrangement is covered in Connecting Citect SCADA to a Modbus RTU gateway over MODNET.

Map the first register from the addressing document #

Schneider's Twido Modbus addressing document is the authority for which Modbus object each Twido data item answers, so take the register number from it and never from the %MW symbol. Notation is where working links go wrong: a register reference in the 4-prefixed style carries a leading digit that names the object type, and drivers disagree over whether they want that full reference or the raw offset behind it. A tag aimed one place off reads good quality with a wrong or frozen value, which looks like a driver fault and is not. Pick a first item you can change deliberately — a data word you force or write in the logic — and record its object type, width and document reference before the Citect tag exists.

Read the symptom against the layer #

One symptom per layer; run the deciding test before changing anything else:

Symptom Check first Deciding test
Citect never transmits channel port selection; port already owned by another application close every serial application, restart the poller, watch the converter's transmit LED
Transmit LED blinks, no reply framing, station address, slave mode on the PLC port compare each framing field side by side, then swap the RS-485 data pair once
Replies with a Modbus exception requested object not supported, or wrong access type match the request against the addressing document entry for that item
Good quality, wrong or frozen value address notation, data width, word order write a known pattern at the PLC and read the raw value in Citect
Timeouts that come and go termination, shield continuity, duplicate station address watch the channel error counters while changing one physical variable at a time

Example: what one two-register read costs at 19200 baud #

Take the read of two holding registers, function code 03, on the documented framing of 19200 baud with 8 data bits, even parity and 1 stop bit. An RTU character at that framing is 11 bits — one start, eight data, one parity, one stop — so at 19200 bit/s a character takes 11 ÷ 19200 = 0.573 ms. The request is 8 bytes, station address plus function code plus start address plus quantity plus CRC: 8 × 0.573 = 4.58 ms. The response is 9 bytes, station address plus function code plus byte count plus four data bytes plus CRC: 9 × 0.573 = 5.16 ms. RTU also holds the line silent for 3.5 character times between frames: 3.5 × 0.573 = 2.01 ms on each side of the exchange, 4.01 ms together. One complete transaction is 4.58 + 5.16 + 4.01 = 13.75 ms — call it 14 ms.

The decision follows from that number. Against a 500 ms Citect poll period, the block occupies 14 ms, about 2.8% of the period, so the serial link is nowhere near its limit and several blocks of that size can share the channel. Against a 20 ms poll period it cannot work at all: one transaction is 70% of the period before any retry, and a single corrupted frame consumes the rest. Keep the poll period at least ten times the transaction time — 150 ms or longer on this framing — and move anything faster to a network built for it.

Decide from the symptom you see #

Silence from the first poll is a role, framing, address or wiring fault in that order: confirm Citect is the master and the Twido port a Modbus RTU slave, put the framing list on both ends, give the segment one unique nonzero station address, then swap the data pair once and substitute the converter. Data that arrives but reads wrong is not a link fault — go back to the addressing document and correct that tag's object, width or notation. Timeouts appearing under load point at the physical layer, not the driver. And whatever the symptom, nothing else enters the tag database until one documented register reads with good quality and tracks a value you changed at the PLC; that single proof turns the rest of the commissioning into data entry.

Questions asked

What station address range does the Citect Modbus RTU device accept?

The device address is entered in the Citect I/O device definition and must lie between 1 and 255 inclusive. Enter the number configured as the Twido slave address, and never 0: on a serial segment 0 is the broadcast address, and a broadcast collects no individual reply, so a device entered as 0 polls nothing and times out on every cycle.

Can TwidoSuite stay connected to the port while Citect polls?

No. The port described for Modbus serves the Modbus link, and a programming session cannot share it with Citect's poller. Close TwidoSuite before starting communications. When a program change is due, stop the Citect channel first, use the port for the transfer, restore the Modbus description afterwards and restart the poller, and expect a run of timeout entries in the Citect diagnostics across that window.

What timeout should the Citect device use for the Twido?

Work up from the framing rather than from a default. At 19200 baud with 8 data bits, even parity and 1 stop bit, the two-register read in the example finishes in about 14 ms, so a 250 ms device timeout gives roughly eighteen times the transaction time: loose enough that a busy controller is not dropped offline, short enough that a broken link still cycles through retries at a usable poll rate.

Why does Schneider's Twido serial FAQ FA198580 list settings I never enter?

Its response-timeout and inter-frame-delay entries configure the master side of a Modbus link: how long a master waits for a reply and how long the line stays silent around a frame. A Twido answering Citect is the slave and uses only the port type, framing and station address from that same list; the master-side entries describe the equipment doing the polling.

Should the Twido poll Citect instead?

A Twido port can be a Modbus master, and Schneider's Twido Modbus documentation shows a two-Twido example built that way, but keep the master role with Citect for SCADA. PLC-initiated exchange pushes poll rates, retries and write timing into controller logic while the SCADA side must be arranged to accept unsolicited data, so every later change becomes a program edit and a transfer instead of a project change.

Keep reading

  • Troubleshooting

    Connecting InTouch to a CLICK PLC over Modbus RTU

    Set the Modbus I/O Server to RTU, not ASCII: the CLICK PLC is an RTU-only slave and silently discards ASCII frames. Wire to an RS-232 port, copy the PLC port's baud and framing — 38400 only if the port is set to it — and keep the 584/984PLC topic only after one known register reads back exact.

    SCADA and data logging

  • How-to

    Connecting Citect SCADA to a Modbus RTU gateway over MODNET

    Yes — MODNET is Citect's driver for Modbus over TCP/IP, and a true RTU-to-TCP converter presents standard Modbus TCP on its Ethernet side, so the combination works. Success then rides on two things: the gateway's operating mode, and carrying the RTU slave address and register offsets into Citect correctly, proved by reading one register whose value you can see at the device.

    SCADA and data logging

  • Selection guide

    PLC data concentrator vs SCADA server for RTU polling

    Poll 50+ RTUs from a PLC data concentrator when links are slow and you must own request sizes, timeouts and scan order; a redundant SCADA server pair earns the job only if its driver exposes those same controls and the terminal server hands each port to one owner at a time, proven by a witnessed failover test. Size either architecture with T_cycle = the sum of request, response, turnaround, wait and retry times per RTU against your required data age.

    SCADA and data logging