PLC data concentrator vs SCADA server for RTU polling
Short answer
Poll 50+ RTUs from a PLC data concentrator when links are slow and you must own request sizes, timeouts and scan order; a redundant SCADA server pair earns the job only if its driver exposes those same controls and the terminal server hands each port to one owner at a time, proven by a witnessed failover test. Size either architecture with T_cycle = the sum of request, response, turnaround, wait and retry times per RTU against your required data age.
On this page
For a telemetry front end that polls more than 50 RTUs over radio or telephone links, take the PLC data concentrator as the default and let the redundant SCADA server pair win the job only after two checks pass: its driver exposes request sizes, scan order, timeouts and retries as settings you control per station, and the terminal server hands each port to exactly one server at a time, proven by a failover test you witness. The hardware is not the decision; the number is. Compare the polling cycle you can build and hold against the data age the operation has specified. A concentrator lets you calculate that number before commissioning. A generic HMI-style driver builds its own request blocks and reshapes them as the tag database changes, so the cycle becomes something you measure after the fact instead of something you designed.
The number that decides it #
Polling on one channel is sequential: one request on the wire, its response, then the next station. Every station you add waits behind every other, the same queue that explains why Modbus RTU drive polling on one serial port is slow. Estimate the cycle before choosing hardware:
T_cycle = sum over RTUs of (T_request + T_response + T_turnaround + T_wait + T_retry)
- T_request and T_response are wire time: characters × bits per character ÷ baud. A Modbus RTU read of 10 holding registers is 8 characters out and 25 back, and at 9600 bps with 8E1 framing (11 bits per character) one character takes 1.146 ms.
- T_turnaround covers the RTU's processing and the radio's key-up; on radio it dominates the wire time.
- T_wait covers the quiet interval the Modbus over Serial Line specification requires between frames: at least 3.5 character times, about 4 ms at 9600 bps.
- T_retry is the tax of unreachable stations, timeout × attempts, charged every scan they stay in the list.
Data age follows directly: a value at the HMI is up to one cycle old. Polling is a scan, not an I/O refresh, the distinction behind why Modbus polling is not the same as remote I/O, so treat these values as supervisory. The one safety rule that comes with it: protection lives in the RTU. A shutdown on high pressure executes in the station, never across a poll cycle.
Worked example: 50 RTUs on one radio channel #
The inputs are illustrative; substitute your measured turnaround and configured timeouts. The decision rule is fixed: the cycle computed with the number of dead stations you tolerate must meet the required data age. A cycle that passes only when every RTU answers is not a compliant design.
Assume:
- 50 RTUs on one shared radio channel, 9600 bps, 8E1: 11 ÷ 9600 × 1000 = 1.146 ms per character.
- Each poll reads 10 holding registers: 8-character request, 25-character response.
- Turnaround, RTU plus radio: 150 ms.
- Wait between transactions: 10 ms.
- Required data age: 10 s.
One healthy transaction:
- T_request = 8 × 1.146 ms = 9.2 ms
- T_response = 25 × 1.146 ms = 28.6 ms
- T_transaction = 9.2 + 28.6 + 150 + 10 = 197.8 ms, about 0.198 s
The full cycle is 50 × 0.198 s = 9.9 s. That passes a 10 s requirement by 0.1 s: no margin, and one command, one added block or one retry breaks it.
Add the retry budget. With a 1 s timeout and 2 retries, an unreachable RTU costs 3 × 1.0 s = 3.0 s per scan. Two dead stations give 48 × 0.198 s + 2 × 3.0 s = 9.5 s + 6.0 s = 15.5 s. Fails.
A faster link does not fix it. At 19200 bps the character time halves to 0.573 ms, wire time falls from 37.8 ms to 18.9 ms, and the transaction becomes 18.9 + 150 + 10 = 179 ms, so 50 stations need 50 × 0.179 s = 8.9 s. Turnaround owns this budget, not baud.
What meets the requirement: two independent radio channels of 25 RTUs each, timeout cut to 500 ms with 1 retry. Worst channel, both dead stations on it: 23 × 0.198 s + 2 × (2 × 0.5 s) = 4.6 s + 2.0 s = 6.6 s, a 3.4 s margin under 10 s. Split the medium, not the connectors: 50 terminal-server ports are 50 serial endpoints, not 50 radio channels.
What each option controls #
The architectures separate on which poll parameters are yours to set and which the software decides:
| Control | PLC data concentrator | SCADA pair, generic HMI driver | Telemetry-capable SCADA server |
|---|---|---|---|
| Request size and grouping | Fixed blocks you define | Driver-built blocks that follow the tag database | Configurable per station |
| Scan order, station priority | Your logic | Scan classes, limited granularity | Scheduler per station or class |
| Timeout and retry | Per RTU, in logic | Often one global setting | Per station |
| Cycle predictability | Calculated before commissioning | Measured after the tag build | Calculated if the scheduler is documented |
| Serial path redundancy | Controller redundancy plus a defined comms handover | Port ownership you engineer and test | Documented failover, still tested |
| Stored reports, event buffers | You program the exchange | Only if the driver implements it | Usually native |
| Station diagnostics to the HMI | Status registers you map | Driver quality flags, if propagated | Built-in station status |
A generic driver's optimized blocks are an advantage on a plant network, where bandwidth is cheap; over one radio channel they move your cycle out from under you each time the tag set changes.
The PLC data concentrator #
You build every request, so block sizes, order, frequency, timeouts and retries are explicit, and the arithmetic above is the commissioning result rather than a hope. The pattern is established controls work: a controller as the protocol front end, the same role as using a PLC as a Modbus RTU to Profibus gateway, pointed at RTUs instead of another fieldbus. Two obligations come with it. First, map a status word and a last-good timestamp per RTU so the HMI can tell a live value from a frozen one; a plausible number with a dead radio behind it is the classic telemetry failure. Second, make redundancy a communications handover: a hot-backup pair in which both controllers transmit on the same channel is two masters interleaving requests and stealing responses. Keep per-station counters for successes, timeouts and CRC errors so field faults are diagnosable from the HMI.
The SCADA server pair and the terminal server #
Two servers give you host redundancy, not polling redundancy, until you engineer single ownership of each port. A terminal server moves serial bytes; it adds no RTU protocol behavior the driver lacks. Its per-port policy decides what you can build: some ports take one session, some take several, and a session can persist after a host crashes. Concurrent sessions are not coordination. Two active masters interleave requests, capture responses meant for the other, and can send an RTU conflicting commands.
Build active/standby: one server polls, the standby holds its port sessions closed, opens them on failure, and the returning host rejoins quiet. If the driver holds ports open continuously and offers no commanded release, this architecture cannot deliver the redundancy on the drawing, and that is the point to take the concentrator instead. Each host is a compact, always-on machine; an industrial mini PC in the MTU cabinet beside the terminal server carries the driver load of a 50-station poll.
Reports, commands and protocol choice #
Inventory the transactions each RTU type needs, not only its live registers: setpoints, totalizer resets, stored reports. Report retrieval from a flow computer or event logger is a multi-request exchange with record identification, progress and recovery after an interrupted transfer; a driver that reads registers flawlessly may still be unable to complete it. If reports are in scope, interrupt a retrieval on purpose and check for lost and duplicated records before accepting the capability.
Commands are transactions in the same cycle. A write costs the same order of time as a read, and the operator feels its latency behind the running scan; getting writes through ahead of the poll is its own discipline, covered in speeding up Modbus RTU writes behind polled reads.
If the RTUs speak DNP3 or IEC 60870-5, 101 over serial and 104 over TCP, prefer a master that speaks the protocol natively. Class-based scans and event-driven reporting cut steady-state traffic on a slow link below anything flat register polling achieves, which can settle the architecture by itself.
Failover you must witness #
Run these before acceptance, with numbers recorded:
- Kill the active server mid-scan: capture the polling gap and the first standby acquisition, and compare both against the tolerated interruption.
- Pull the active host's network cable so its sessions die uncleanly: capture how long the terminal server holds the port and whether the standby can take it.
- Restore the failed host: confirm it returns as standby, never as a second master.
- Fail one RTU: confirm the retry budget and the data age of the healthy stations sharing its channel.
- Power-cycle the terminal server: confirm both hosts recover their ports without manual intervention.
The verdicts: gap within tolerance, port release within the gap, and no observation of two masters, ever.
The decision, case by case #
- Slow shared medium, radio or telephone, 50-plus stations, required data age under 10 s: the PLC data concentrator. The 9.9 s healthy cycle above is exactly the case where owning block sizes, timeouts and the channel split decides whether a 10 s requirement is met.
- SCADA server pair: choose it when the driver documents per-station request size, scan class, timeout and retry settings, and the terminal-server handover passes the failover tests above.
- Stored reports or event retrieval required and the driver's report exchange is unproven: concentrator, or a telemetry-capable server. Do not commit a generic driver to an unverified report sequence.
- RTUs native to DNP3 or IEC 60870-5: the server with that protocol driver, for its event-driven reporting.
- Port handover unsupported by the driver and terminal server together, with redundancy a requirement: concentrator, or change one of those two components until it is supported.
For the example system: one channel at 9.9 s healthy is rejected; two channels with a 500 ms timeout, 6.6 s worst case, is accepted.
Questions asked
How many RTUs can one serial channel carry?
There is no fixed station count, only cycle time. At the example's 0.198 s per healthy transaction, 50 RTUs need 9.9 s per scan on one 9600 bps radio channel and 25 RTUs need 4.95 s. Divide your required data age by the per-station transaction time, then subtract the retry budget of the dead stations you tolerate; that quotient, not a vendor's station limit, is the channel's capacity.
Can both SCADA servers stay connected to the same terminal-server port?
Only if that port's documented policy allows multiple sessions, and even then concurrent sessions are not coordinated polling: two active masters interleave requests and capture each other's responses. Build active/standby instead, with the standby's connections closed until failover, and set the terminal server's idle or session timeout below your tolerated polling gap so sessions abandoned by a crashed host release in time for the standby to take the port.
What should we demand from the SCADA vendor before choosing the server pair?
Written answers to four things: per-station control of request size and grouping, scan class, timeout and retry count; a documented method for the standby to open the serial path and for the returning host to stay quiet; propagation of per-station communication quality to the client; and a demonstrated report retrieval with an interrupted transfer, if you need reports. If any answer is a feature request rather than documentation, the concentrator takes the job.
When is the SCADA server pair the better choice despite slow links?
When the historian, alarm engine and poll engine belong on one redundant pair, and the driver documents the controls the poll needs. It is also the right choice when RTUs report events by DNP3 or IEC 60870-5, because unsolicited reporting removes most steady-state polling from the link. Confirm the driver still publishes request sizes, scan classes and timeouts so you can verify the cycle arithmetic, and that per-station communication quality reaches the operator display.
What does an unreachable RTU do to the rest of the scan?
It taxes every other station. Each dead RTU consumes timeout times attempts on every scan while it stays in the normal poll list: at 1 s timeout and two retries, five dead stations add 15 s to a cycle that was 9.9 s healthy. Move stations with consecutive failures to a slower scan, polling them every fifth cycle, and return them to the normal list on a good response, so one bad radio path cannot age the whole field.