Troubleshooting
Why a redundant ControlNet pair shows PRI and DISQ
Short answer
Read the redundancy module (SRM) event logs before changing anything: a secondary that cycles from SYN to DISQ has a recorded initiating fault, and node changes will not remove it. The documented ControlNet design keeps at least four nodes per network with two external nodes numbered below the redundant pair; that design improves switchover behavior, not disqualification.
On this page
- Why does my secondary keep dropping from SYN to DISQ?
- How many ControlNet nodes does a redundancy system need?
- Do the extra nodes need to be scheduled, and where do their node numbers go?
- How do I count and number the nodes on my network?
- Can a node count or node number cause the DISQ indication?
- What do I read first in the SRM event logs?
- Which fixes are safe to make while the process keeps running?
- How do I prove the pair is healthy again?
- Questions asked
A redundant ControlLogix pair that alternates between PRI/SYN and PRI/DISQ has a secondary-qualification fault, and its cause is recorded in the redundancy module event logs, the SRM logs. Read those before changing anything on the network. Node count and numbering are a separate design question: the Redundancy Systems User Manual 1756-UM015P-EN-P sets a minimum node count for each ControlNet network in a redundancy system, and Rockwell's switchover guidance places two nodes outside the pair at lower node numbers. Meeting that design improves switchover behavior; it does not clear DISQ. This article gives both checks, a worked node count, and the log sequence that names the fault.
Why does my secondary keep dropping from SYN to DISQ? #
A secondary that alternates between SYN and DISQ has a recurring initiating fault that the redundancy module records each time; DISQ means it is not qualified to take over, so read the SRM event logs for the first event before each transition rather than the final status.
PRI, SYN, and DISQ are three different statements. PRI says this chassis is the primary and is controlling the process right now. SYN says the partner is synchronized and qualified to take over. DISQ says the partner is not qualified, and it carries no reason of its own, because the reason is an event in the redundancy module's log.
| Indication | What it confirms | What it does not confirm |
|---|---|---|
| PRI | This chassis controls the process now | That the partner can take over |
| SYN | The partner is synchronized and qualified | That it stays qualified under load |
| DISQ | The partner is not qualified to take over | Why, which is in the event log |
A primary keeps running while its partner cycles in and out of qualification, so an HMI that keeps updating and remote I/O that keeps moving are not evidence of a healthy pair. Controller redundancy and redundant network media are also different functions, as different as the two schemes compared in why MRP ring redundancy and PROFINET S2 redundancy differ, and a healthy network path does not by itself keep the secondary qualified. The log, not the display, is the first tool here, and the first logged event is the evidence that decides the repair.
How many ControlNet nodes does a redundancy system need? #
At least four ControlNet nodes are required per ControlNet network in a redundancy system, per the Redundancy Systems User Manual 1756-UM015P-EN-P; the two redundant controllers occupy two of them, so two more nodes must exist beyond the pair.
Count ControlNet interfaces that hold node addresses, not chassis or equipment labels. The items in this installation, primary controller chassis, secondary controller chassis, remote I/O chassis, and the SCADA PC, become network nodes only when each holds its own interface: a ControlNet bridge module (a CNB) in each chassis and an interface card in the PC. The ControlLogix Redundancy System manual, 1756-UM523, walks that chassis-and-bridge layout for the redundancy system.
Two checks follow. First, trace the PC path: if it reaches ControlNet through another device instead of its own interface card, the PC is not a node and the network sits one interface short of the minimum. Second, treat the minimum as a design requirement for how the network behaves around a switchover, not as a repair for the DISQ indication; the next sections keep those two jobs apart.
Do the extra nodes need to be scheduled, and where do their node numbers go? #
The two additional nodes do not have to be scheduled nodes, and Rockwell's switchover guidance recommends setting them to node numbers lower than the redundant pair's; on a network with the pair at nodes 10 and 11, put the other two nodes at 08 and 09 or lower.
Scheduled or unscheduled is a separate axis from node number. Scheduling decides which nodes carry cyclic, scheduled connections across the network; a node can sit at a low address and carry no scheduled connection at all. The lower-number recommendation comes from Rockwell's ControlNet switchover note, support answer 64175, framed as a condition for a bumpless switchover. On the network in this question, the natural external nodes are the I/O chassis bridge and the PC interface card, so set those two below the pair's addresses and leave the redundant pair above them. If the PC turns out to have no ControlNet interface, the second external node is still required: the count and numbering rules stand whether or not a scheduled connection uses those nodes.
How do I count and number the nodes on my network? #
Count each ControlNet interface with its own node address, then check the two rules: the documented minimum node count, and the two nodes outside the redundant pair numbered below it. The worked example uses illustrative addresses.
Worked example, illustrative addresses for the installation in this question:
| Participant | ControlNet interface | Node address |
|---|---|---|
| Primary controller chassis | Bridge module (CNB) | 10 |
| Secondary controller chassis | Bridge module (CNB) | 11 |
| Remote I/O chassis | Bridge module (CNB) | 08 |
| SCADA PC | Interface card | 09 |
Count: 2 + 1 + 1 = 4 nodes, and 4 meets the documented minimum. Numbering: the external addresses are 08 and 09, and both are below both pair addresses, 10 and 11, so the recommendation is met.
Same hardware, wrong numbering: controllers at 01 and 02, I/O bridge at 03, PC card at 04. The count still passes; the external addresses 03 and 04 sit above the pair's 01 and 02, so the lower-number rule fails. Expect a bump at switchover on such a network; do not expect renumbering by itself to clear a DISQ that the logs are already recording.
What moves the count is the PC path. If the SCADA application reaches the controllers over another network, the PC contributes no node, the network runs one short, and the fix is a second external ControlNet interface, the PC's own card or another participant, numbered below the pair. Tracing which interface at which address actually reaches the network is the same job as troubleshooting a PLC-5 ControlNet connection path from a driver.
Can a node count or node number cause the DISQ indication? #
No — node count and numbering below the pair affect how smoothly a switchover runs and can add bump, but they do not disqualify a secondary; a DISQ that cycles between switchovers has a separate recorded cause that only the logs will name.
That split explains why the usual quick moves do not clear this symptom:
- Adding a node to reach the design minimum: correct for the design, but the design does not tie the count to qualification, so expect the cycling to continue until the logged cause is repaired.
- Renumbering so the externals sit below the pair: correct for the bumpless-switchover recommendation, and it changes bump behavior, not qualification.
- Rescheduling the network: scheduling assigns cyclic connections, a job with failure modes of its own, worked through in troubleshooting ControlNet scanning of legacy 1771 specialty I/O; it neither repairs an incompatible module nor restores a lost synchronization path.
- Repeating the synchronize attempt: each attempt can return SYN briefly, and the recorded condition that dropped the secondary last time is still present for the next time.
What do I read first in the SRM event logs? #
Open both redundancy modules' event logs and find the earliest event that precedes the first SYN-to-DISQ transition, because later alarms are usually consequences; record the exact event text and its timestamp instead of paraphrasing it.
Both partners keep logs, and they do not record the same things: one usually holds the initiating event while the other logs only that it lost its partner. Work the sequence below, following the monitoring and troubleshooting material in the Redundancy Modules Installation Instructions, 1756-IN087:
- Pull the logs from both the primary and the secondary, not only from the chassis the programming terminal reaches.
- Preserve the state first: save both projects and record chassis contents, slot positions, firmware revisions, node addresses, and the current indication.
- Bracket one full SYN to DISQ to SYN cycle and copy the exact event text with timestamps.
- Work backward from DISQ to the earliest relevant event: a module fault, a partner-communication failure, a synchronization-link event, or a configuration change.
- Compare the two chassis slot by slot, module types, placement, and firmware, against an approved combination; one module updated on one side is a common mismatch.
- Inspect the path the earliest event names: a synchronization-link event points at that link and its modules; a ControlNet event points at interface status, taps, connectors, termination, and trunk.
- Apply one correction, re-synchronize with the documented procedure, and keep the change record so the result stays attributable to that correction.
A communication dropout recorded after DISQ is the partner reacting to the loss, not the cause of it, which is why the search runs backward from the transition, not forward from the newest alarm.
Which fixes are safe to make while the process keeps running? #
Keep the primary in control and make one targeted correction at a time: node numbering, rescheduling and log reading can all be done live, but do not perform an exploratory switchover while the secondary shows DISQ, because the pair then has no qualified takeover path.
Logs, counting, and the numbering correction carry no risk to the running process; the switchover is the risky step, so schedule that test with whoever owns the process rather than improvising it at the machine. If the design check failed, correct it anyway: bring the network to the documented minimum and set the external nodes below the pair, expecting smoother switchovers while the log work continues. If the earliest event names a module or a link, repair that one thing, and move both partners to one approved firmware combination together rather than updating a single module on one side.
How do I prove the pair is healthy again? #
A return to SYN is an intermediate result, not the acceptance test; run the pair through the load and network conditions that previously produced DISQ and compare the event logs before and after the correction until no new qualification event appears.
Run a full shift at production load with normal HMI polling, then confirm three things: the intended primary stays primary, the secondary holds SYN without cycling, and neither log records a new qualification event. Then apply the decision for each case:
- Four nodes present and both external addresses below the pair: the design is met. Take the earliest SRM event before the first transition, repair the cause it records, re-synchronize, and hold a clean shift as the acceptance test.
- Count short, or an external address above the pair: correct the design to the four-node, lower-number arrangement and expect smoother switchovers, not an instant cure; keep reading the logs for the qualification fault.
- DISQ returns after a correction: the earliest new event names the next condition in the chain. Repair that one thing, re-synchronize, and repeat until a full shift passes with SYN steady and no qualification events.
Questions asked
Does redundant ControlNet media, a dual trunk, satisfy the node requirement?
No. Redundant media provides an alternate cable path where the installed hardware supports it; the node requirement is about devices that hold addresses and communicate on the network. A network can have dual media and still lack the external nodes, so check the two independently: media for path failures, node count and numbering for switchover behavior.
Do both controllers and redundancy modules have to run matching firmware?
The pair must run a combination the redundancy documentation approves for that controller, redundancy module, and network interface family. Compare the two chassis slot by slot and revision by revision while the logs are open, and move both partners to one approved combination rather than updating a single module on one side. A mismatched pair is a common qualification fault, and the earliest logged event usually names it.
How do I catch the events when DISQ appears only every few days?
Leave the pair running and keep a timestamp record at the operator station: note each time the display leaves SYN and returns. After two or three cycles, pull the event logs from both redundancy modules and match the operator timestamps against the logged ones. The earliest event common to both partners before the first transition is the initiating fault to correct.
Why did DISQ start right after a module swap or a chassis power cycle?
Qualification faults usually follow a change to one partner: a replaced module, a power interruption, a configuration download, or a firmware move. The redundancy module logs the change before the disqualification, which is why the earliest event matters more than the indication on the display. Compare the changed side against the untouched partner and restore an approved combination before re-synchronizing.