Why MRP ring redundancy and PROFINET S2 redundancy differ

Industrial networks Published 6 min read

Short answer

MRP ring redundancy gives an S7-1500R/H system a second network path; PROFINET S2 redundancy lets an IO device hand over between the two redundant controllers without restarting. A device can have either one without the other, and the 16-participant ring limit plus the firmware versions for S2, MRP-Interconnect and R1 decide what you can actually build.

On this page
  1. What does the MRP ring protect on an S7-1500R/H system?
  2. What does PROFINET S2 redundancy protect that MRP does not?
  3. Can a device have MRP without S2, or S2 without the ring?
  4. What happens to a non-S2 device at controller changeover?
  5. How many devices can the PROFINET ring of an R system hold?
  6. Which firmware versions unlock each redundancy function?
  7. Which redundancy functions does your system actually need?
  8. Questions asked

An MRP ring and PROFINET S2 redundancy protect two different things in an S7-1500R/H system, and a single device can have one without the other. Media Redundancy Protocol (MRP) protects the network path: it keeps traffic moving when a ring link fails. PROFINET S2 system redundancy protects the relationship between an IO device and the redundant controller pair: it lets the device hand over between the two CPUs without dropping offline and restarting. Building the ring buys you path redundancy, not bumpless changeover; specifying S2 devices buys you bumpless changeover, not path redundancy. This article separates the two functions, states the ring participant limit with the arithmetic that applies it, lists the firmware versions each function needs, and ends with the decision for each case.

What does the MRP ring protect on an S7-1500R/H system? #

MRP protects the network path: a Media Redundancy Protocol ring gives the traffic between the redundant system and its IO devices a second physical route, so any single link or participant in the ring can fail without isolating a device.

In the baseline S7-1500R/H architecture, the subordinate PROFINET IO system is an MRP ring, and both R/H CPUs sit in that ring directly through their x1 interfaces in the MRP manager role. The assigned IO devices preferably join the ring directly too, because that is what gives each device a fully redundant path to the controller pair. Direct participation requires an MRP-capable switch onboard each participant; two Ethernet connectors by themselves prove nothing. Devices can also attach indirectly through additional MRP-capable switches, but such a branch is a single path and gives up the path redundancy the ring provides.

What does PROFINET S2 redundancy protect that MRP does not? #

S2 protects the handover: PROFINET system redundancy lets an IO device maintain its communication relationship with both members of the redundant controller pair, so control transfers between the CPUs without the device dropping offline and rebuilding its connection from an unconnected state.

The two R/H CPUs of one system together form a single redundant PROFINET IO controller. An S2 device holds the relationships to both halves at once, so when the controlling CPU changes, the device switches its connection instead of re-establishing it. MRP has no say in that transfer: it reroutes Ethernet frames and nothing more. That is why path redundancy and controller redundancy need separate acceptance criteria, and why a device can pass one test and fail the other.

Can a device have MRP without S2, or S2 without the ring? #

Yes, and that split is the design trap: an MRP participant without S2 still restarts at every controller changeover, while an S2 device outside the ring changes over bumplessly as long as its own branch stays up.

The four combinations and their outcomes:

Device arrangement Path protection Changeover behavior
MRP-capable S2 device directly in the ring Alternative paths through the ring Bumpless transfer between the CPUs
MRP-capable non-S2 device directly in the ring Alternative paths through the ring Restart at changeover; outputs can drop to 0
S2 device outside the ring on its own branch The branch itself is a single path Bumpless while the branch stays up
Non-S2 device outside the ring Single path only Restart at changeover, on a single path

Read the middle rows together: ring membership fixes link failures, S2 fixes changeovers, and neither substitutes for the other.

What happens to a non-S2 device at controller changeover? #

It restarts: the device loses its application relation and rebuilds it with the new controlling CPU, and depending on the device its outputs can drop to 0 and attached drives can stop.

Non-S2 devices are still supported on the redundant system, from TIA Portal V16 and R/H CPU firmware V2.8 onward. While such a standard device is unavailable after the handover, no process data is transferred, and what its outputs hold in the meantime follows its configured substitute value behavior — which is why one device keeps last values while another lets outputs fall or stops its drive.

Before engineering a non-S2 device into a redundant system, confirm from the risk assessment that a momentary output drop or drive stop at changeover is acceptable for that actuator; that acceptance, not the restart itself, decides the case. How long the plant sees the disturbance also depends on ring recovery and CPU watchdog timing, which the guide to configuring S7-1500R/H watchdogs for MRP ring recovery walks through.

How many devices can the PROFINET ring of an R system hold? #

The limit is 16: on S7-1500R CPUs the PROFINET ring may carry no more than 16 PROFINET devices, and that count includes the two R-CPUs sitting in the ring.

The count is deliberately strict because ring size is an availability factor: the more participants, the more often the ring reconfigures, and the more the redundant system's availability suffers.

Worked example. Take an R system with 2 R-CPUs, 12 ET 200SP drops in the ring and 2 MRP-capable ring switches: 2 + 12 + 2 = 16 participants, exactly at the limit, so nothing else may join. Adding a 13th drop gives 2 + 13 + 2 = 17, one over the limit, and that configuration is not supported on an R CPU. The supported ways out are an indirect branch for the extra device, accepting a single path for it, or a second ring coupled with MRP-Interconnect, where the limit then applies per ring.

Which firmware versions unlock each redundancy function? #

Family names decide nothing: S2, non-S2 device support, MRP-Interconnect and R1 each carry their own interface-module, control-unit, TIA Portal and firmware requirements, and the table below is the selection checklist.

Function Documented requirement
S2 on ET 200SP/MP High Feature interface modules from firmware V4.2
S2 on SINAMICS drives CU310/320PN control units from firmware V5.2
S2 link to another PROFINET IO controller PN/PN coupler as the connecting element
Non-S2 IO devices on an R/H system TIA Portal V16 or later, R/H CPU firmware V2.8 or later
MRP-Interconnect, redundant coupling of several MRP rings R/H CPU firmware V2.9 or later
PROFINET R1 redundancy, line topology, CPUs over an external switch CPU 1517H-3 PN or CPU 1518HF-4 PN, TIA Portal V18, firmware V3.0

Check the installed interface-module variant and its firmware on every device, not just the product family: an ET 200SP drop on older firmware cannot be configured into S2.

Which redundancy functions does your system actually need? #

Specify both when the machine must ride through a cable break and hand over control without a glitch: MRP membership buys path redundancy, S2-capable hardware buys bumpless changeover, and only a device with both delivers both.

The decisions, per case:

  • The ring may lose any single link and a restart at changeover is tolerable: put the device in the MRP ring; S2 is optional.
  • Changeover must be bumpless and the device branch is trusted: choose an S2-capable device; ring membership is optional.
  • A link failure and a CPU changeover must both pass without process interruption: put an S2-capable device directly in the ring, with the firmware the table above requires.
  • The device count exceeds what one ring can hold: couple further MRP rings with MRP-Interconnect instead of stretching a single ring past its limit.
  • The redundant system must also serve an S7-400 DP master: that integration is its own design, and the S7-1500R/H MRP ring to S7-400 DP master integration guide covers the configuration path.

Commission accordingly: prove a CPU changeover and prove a ring-link interruption as two separate tests, because a pass on one proves only that one. A device that is reachable after a link failure and glitch-free through a changeover, with firmware matching the table, is the configuration where MRP and S2 are actually both delivering.

Questions asked

Do two Ethernet ports on a device prove MRP support?

No. Direct ring participation needs an MRP-capable switch onboard the device and the MRP operating mode configured. Two connectors on an ordinary device only mean two cables; check the device's documented supported functions before counting it as a ring participant. A switch that merely forwards traffic does not join the ring by itself.

What does a standard IO device do while it is reconnecting after a changeover?

No process data is transferred until the device is available again, and what its outputs hold during that gap follows the configured substitute value behavior. That is why the restart is device-dependent: one device keeps last valid values, another lets its outputs fall to 0 or stops its drive.

Does the ring participant limit include the CPUs?

Yes. The documented rule counts PROFINET devices including the R-CPUs in the ring, so an R pair leaves 14 places for IO devices and ring switches. The documentation also treats ring size as an availability factor, so staying below the maximum is better engineering than designing right up to it.

How does MRP-Interconnect help when one ring is not enough?

Available on R/H CPUs from firmware V2.9, MRP-Interconnect couples several MRP rings with redundant interconnection, so devices beyond the capacity of a single ring still get redundant paths. The participant limit then applies per ring rather than to the whole system, which is the supported way to scale past one ring.

Keep reading

  • How-to

    Connecting Modbus devices to a ControlNet system

    No box translates ControlNet producer/consumer packets into Modbus transactions. Every working link terminates both protocols in one device and bridges through a mapped data table: a ProSoft 3100/3150-MCM module in the Allen-Bradley chassis, a standalone FieldServer, SST or Anybus ControlNet to Modbus gateway, or a Logix controller acting as data concentrator. Choose the module when one controller owns the data, the gateway when two established systems must exchange it.

    Industrial networks

  • Selection guide

    How to select a CODESYS fieldbus master for industrial Ethernet

    Select the master around the device, not the connector: the 750-340 is a PROFINET IO coupler, and a PROFIBUS station needs a different coupler. Confirm three matches — device protocol, runtime master package, supported network adapter — then size the bus cycle from the process budget; the worked example clears a 10 ms sensor-to-actuator budget at a 2 ms cycle and fails it at 4 ms. Bench-test a laptop NIC only if the runtime documents it.

    Industrial networks

  • Comparison

    PROFINET versus DeviceNet for machine and panel I/O

    Choose by controller ecosystem first: PROFINET is industrial Ethernet at 100 Mbps with line, star and ring topologies, while DeviceNet is a CAN-based trunk running 125 to 500 kbps. Speed only decides when the panel needs dense or fast I/O. PROFINET for new high-speed machines, DeviceNet where the Rockwell-era devices and wiring already exist.

    Industrial networks