Why a pulse-mode servo drive takes STEP and DIRECTION from the PLC
Short answer
A pulse-mode servo drive accepts hardwired STEP and DIRECTION pulses exactly as a stepper input would: the drive closes its own position loop, but every positioning, homing and coordination decision is made by the PLC program, and the HMI only writes setpoint tags. If the application needs drive-integrated motion such as CNC or printing paths, select a drive family that executes motion internally.

On this page
A pulse-mode servo drive has no motion instructions behind it: the PLC commands it with hardwired STEP and DIRECTION pulses, the interface a stepper motor takes. The drive closes its own position loop on its encoder, but every positioning, homing and coordination decision — target, speed, ramps, when to home, how axes sequence — is made by the PLC program. The HMI never reaches the drive; it writes setpoint tags into the PLC. That is the documented architecture for pairing a pulse-interface drive such as a SINAMICS V60 with an S7-1200: Siemens' reference application (support entry ID 38391227) positions a V60 from the pulse interface of a CPU 1214C in the TIA Portal. If the application needs drive-integrated motion — CNC interpolation, printing or plotting paths — select a drive family that executes motion internally instead.
The drive is a power amplifier with a stepper interface #
A pulse-mode drive's entire motion vocabulary is a pulse train. Every STEP pulse advances the motor by one increment fixed by the drive's electronic gear, and the level on the DIRECTION input sets the sign. That is the complete command interface: no motion programs, no profile generator, no homing routine, no instruction set, and no data channel back to the controller. The drive is best understood as a power amplifier — it tracks whatever pulse stream arrives, and that is all it does.
Inside the housing it is still a servo. The drive reads its motor encoder and closes the position loop itself, so the shaft holds the commanded angle under load instead of losing steps the way an open-loop stepper can. The interface is the stepper's; the loop behind it is not. A comparison of a step-and-direction servo drive with an open-loop stepper covers exactly that distinction, and it has a consequence worth planning around: holding the commanded angle is the drive's job, but knowing where the axis actually is becomes nobody's job unless you add hardware for it.
What the PLC program owns #
With the drive reduced to a pulse follower, motion engineering moves into the CPU. In the TIA Portal you configure an Axis technology object on a pulse train output, and from then on the CPU drives a pulse output and a direction output for that axis. The technology object brings the motion instructions with it — enable the axis, home it, jog it, absolute move, relative move, velocity move — each with busy, done and error outputs that your sequencer consumes. The Command table technology object holds preconfigured motion steps for machines that run stored sequences.
Everything a built-in motion controller would do therefore becomes your code. Speed and acceleration limits, and the scaling from pulses to machine units, are configured in the Axis object. Homing is a sequence your program runs against a reference switch wired to a PLC input: search, stop, set position zero. Interlocks between axes, fault handling, handshakes with the rest of the machine — program logic, every one of them.
One axis takes one pulse channel, meaning a pulse output plus a direction output. How many channels your exact CPU provides is a specification of that CPU; the documented Siemens application for the V60 is written for a CPU 1214C, so match your axis count to your own CPU's channel list before you freeze the panel layout. Two pulse channels do not synchronize each other either: coordination is your logic starting a move, waiting for done, then starting the next.
A pulse interface carries no handshake back, so enable and ready have to be designed in. MC_Power enables the axis inside the CPU; the drive's ready contact, wired to a PLC input, is the only way your logic actually knows the drive is up. Assume that handshake instead of wiring it and you reproduce the pattern described in Troubleshooting missing Drive Ready on a V60 axis retrofit.
The HMI writes tags, the PLC pulses the drive #
A basic panel such as the KTP400 connects to the CPU over PROFINET and never to the drive. Operator entries land as tags in the PLC: a target position, a speed, jog buttons, a mode selector. The motion logic reads those tags, calls the Axis instructions, and the CPU emits the pulses. Status runs the opposite way: ready, homed, moving, in position and fault are values your program copies from the technology object into panel tags. There is no screen-to-drive path, and there are no drive diagnostics on the panel beyond what you mirror.
Even where a drive does take a communication card, the panel still acts only through the controller — the pattern behind why a CB1241-driven V20 takes no HMI speed entry, where a speed entered at the screen becomes motion only when the link between the PLC and the drive is right. In the pulse architecture that link is the wiring itself, which makes the whole chain visible: tag, logic, pulse, motion.
Worked example: from millimetres to pulses #
The figures here are an example for arithmetic, not a default; the gear setting comes from your drive's parameters and your encoder count. Take an electronic gear of 10,000 pulses per motor revolution on a ball screw with a 5 mm lead:
- Resolution: 5 mm per revolution ÷ 10,000 pulses per revolution = 0.0005 mm per pulse.
- A 250 mm travel: 250 ÷ 5 = 50 revolutions, so the program emits 50 × 10,000 = 500,000 pulses.
- A 25 mm/s feed: 25 ÷ 5 = 5 revolutions per second, so the pulse stream runs at 5 × 10,000 = 50,000 pulses per second.
Now the constraint shows itself. If the pulse channel's maximum output rate is R pulses per second, the axis speed ceiling is R ÷ 10,000 × 5 mm per second. Set the gear twice as fine and resolution doubles while the same channel's speed ceiling halves. Every pulse-driven axis design is that trade between the pulse rate the CPU can deliver and the resolution and speed the machine demands; the numbers above show how the three quantities bind together.
Commissioning order #
- Wire the interface from the drive manual's connection diagram for your controller family — the V60 getting-started documentation includes one for the S7-1200. Short, shielded pulse wiring with clean grounding is the difference between crisp edges and noise-driven motion; the same discipline applies as when wiring a V90 servo to an S7-200 SMART pulse train interface.
- Configure the
Axistechnology object: which outputs carry the pulse and direction signals, pulses per motor revolution from the drive's gear parameters, machine scaling, dynamic limits. - Prove the axis before any sequence code exists: the axis control panel moves the axis in manual mode and is the documented tool for optimizing settings and testing the system.
- Wire the home reference switch and run homing at a reduced search speed.
- Wire and prove the enable and ready signals, the travel limits and the emergency stop before the first powered move.
- Mirror the panel tags last, then hand the machine over.
Keep the first production moves at reduced speed until homing position and travel limits have been proven against the real machine.
Pulse control or drive-integrated motion: the decision #
For point-to-point servo work — jog, index moves, homing, sequenced single axes, operator-entered targets on a panel — pulse control is a sound, documented architecture, and compact S7-1200 hardware runs it well. The trade-off is engineering time: profiles, homing, interlocks and fault handling are all your code, and none of them exist in the drive. Plan that work into the machine build instead of discovering it at commissioning.
The moment motion stops being point-to-point, change architecture:
| Application | Architecture that fits |
|---|---|
| Jog, index moves, homing, single-axis sequences, panel-entered targets | STEP and DIRECTION pulses, all motion logic in the PLC |
| Interpolated paths, electronic cam, printing or plotting trajectories | Drives taking cyclic setpoints over a motion bus, motion executed by the drive or a motion-capable controller |
Linear and circular paths need phase-locked position commands to two or more axes at once; independent pulse channels do not provide that, and building interpolation on top of them is a research project, not a controls task. On the same controller family the documented alternative is cyclic setpoint exchange over PROFINET, which is what control a PROFINET servo drive with cyclic telegram data covers, together with the commissioning pattern in Troubleshooting S7-1200 PROFINET servo motion control issues.
The decision, then: keep the pulse architecture for the single-axis, point-to-point machine built around a CPU 1212C and a basic panel, and own the motion code in the PLC. For CNC interpolation, printing or plotting paths, specify a drive family that executes motion internally over a motion bus instead of assembling coordination out of independent pulse channels.
Questions asked
Can a CPU 1212C with a KTP400 Basic panel drive a V60 servo?
Yes. The connection is hardwired: the CPU's pulse output and direction output feed the drive's STEP and DIRECTION inputs, exactly as the V60 getting-started documentation shows for the S7-1200. Siemens' reference application for this pairing is written for a CPU 1214C, so count your planned axes against the pulse channels of the exact CPU you have before the panel layout is final.
Does the panel ever command the drive directly, and can it show drive faults?
It never commands the drive directly. Operator entries land as PLC tags, and the CPU pulses the drive from them. Fault visibility is engineered the same way: your program mirrors axis status from the technology object into panel tags, and if the drive offers a digital ready or fault output, wire it to a PLC input so the state reaches the screen as a real signal instead of an assumption.
What happens to the axis when the CPU goes to STOP or loses power?
Pulse generation stops, so the drive receives no new step clock. What the axis does next — ramp down on the drive's own settings, coast, or trip a position fault — is decided by the drive's configuration, because there is no data channel to carry a controlled stop command. Decide that stopping path deliberately during commissioning, and keep the safety stop wired independently of the pulse interface.
Does the PLC ever know the real axis position under pulse control?
Only the commanded position, as a count of the pulses issued, scaled through the Axis configuration. The drive's encoder holds the shaft on that command, but nothing reports measured position back to the controller. If the machine needs actual position values for registration, cut or print timing, or deviation alarms, add an encoder input to the PLC or move the axis onto a bus where the drive reports position cyclically.