Why a Pt100 cannot connect to a 4-20 mA analog input module
Short answer
A Pt100 is a passive platinum resistor: it produces no signal until an input drives a measuring current through it. A 4-20 mA input channel waits for a transmitter to source current, so a bare Pt100 reads nothing, under-range or fault. Use an input module with an RTD range, or add a Pt100 transmitter whose 4-20 mA or 0-10 V output matches a range the channel accepts.
On this page
- What a Pt100 is, and the standard that defines it
- Why a current input channel sees nothing
- The direct fix: an input module with an RTD range
- The transmitter fix: keep the channels you have
- The two paths side by side
- Worked example: one transmitter loop
- Wiring details that move the reading
- The decision
- Questions asked
A Pt100 will never read on a 4-20 mA analog input module, and no scaling trick will change that. The Pt100 is a passive platinum resistor; that current-input channel is built around a transmitter that sources current. Wire the bare sensor to such a channel and the channel has nothing to measure, so the input word sits at zero or in the under-range state for as long as it is wired that way. There are two working connections: an input module with an RTD range, which drives the measuring current itself, or a Pt100 transmitter, which converts the resistance into a current or 0-10 V signal the channel already accepts. This article gives the mismatch behind that fact, both fixes with their numbers, and the decision for each case.
What a Pt100 is, and the standard that defines it #
IEC 60751 is the standard that defines industrial platinum resistance thermometers, and the Pt100 is its baseline element: 100 Ω of platinum at 0 °C, rising to about 138.5 Ω at 100 °C, with tolerance classes that bound how far a real element may sit from that curve. The property that decides this whole question is that the sensor has no output of its own. To read it, an input must push a small measuring current through the element and measure the voltage that current produces — in other words, it must measure resistance. An RTD is not a thermocouple either: it generates no electromotive force of its own, so an input built for thermocouple millivolts will not read it. Whatever reads a Pt100 correctly must, by construction, source that current.
Why a current input channel sees nothing #
A current input channel measures the current flowing in a closed loop. It is engineered around a two-wire transmitter that draws its supply from the loop and regulates the loop current between its live zero and its full-scale value; a dead loop reads 0 mA. A bare Pt100 is a two-terminal resistor with no ability to source anything, so alone across the channel terminals it produces exactly that dead-loop condition.
A module of this class shows the limit clearly. Schneider documents the TSX AEZ 802 for the TSX Micro platform as eight current inputs with 12-bit conversion, current ranges only, and no resistance or RTD range in its channel configuration. So commit this: no parameter, jumper or scaling table turns a current-only channel into an RTD channel, and a thermocouple input will not do it either. The fix is hardware, and you have two choices.
The direct fix: an input module with an RTD range #
On a TSX Micro rack the direct fix is the TSX AEZ 414: an analog input module with four channels and automatic linearization for Pt100 and Ni1000 probes, documented with its connection system on 15-pin SUB-D connectors. Configure the channel for Pt100 and for the lead scheme you wired — 2, 3 or 4 conductor — and the module drives the element, linearizes the curve and hands your program temperature directly. The channel word arrives in tenths of a degree Celsius: a room at 20.0 °C reads as 200, in an input word such as %IW3.0 for slot 3, channel 0 (substitute your own slot and channel from the configuration screen).
Two bench checks prove the channel before you trust it. A decade box at 100 Ω should park the word near 0, because that resistance is 0 °C; 138.5 Ω should park it near 1000, because that is 100.0 °C.
These are legacy references. Schneider's product pages already list the Premium-platform equivalent TSX AEY 414 as discontinued in December 2020, so confirm the lifecycle of any RTD module you specify against the current catalogue and discontinuation bulletins. For new work the same channel-type logic applies, and the walkthrough on configuring and scaling analog inputs on a Modicon M340 shows the modern equivalent. Decision: if the rack has a free slot and an RTD module exists for it, take this path — nothing extra to power, nothing to calibrate, no scaling to write, and lead compensation is the module's job.
The transmitter fix: keep the channels you have #
A Pt100 transmitter's input side drives the probe and measures its resistance; its output side sources a clean current signal into the channel, mapped across the span you order. A transmitter spanned 0-100 °C sends its live zero at 0 °C and full scale at 100 °C. Order the span to cover the process with margin, mount the transmitter at the probe head when the cable runs long, and prefer a current output over 0-10 V for anything but short runs: a current loop shrugs off lead resistance, and its live zero exposes a broken lead immediately. If the only spare channel is voltage-type, order the 0-10 V output version, matched to a range the channel configuration actually offers.
From there the channel is an ordinary current input, and the two-point pattern in scaling a current-loop analog input to engineering units in CPM2 ladder applies unchanged. If the CPU has no analog input at all, the same transmitter approach works through the routes in adding a current-loop sensor to a PLC without analog inputs.
The two paths side by side #
| Situation | Wire this | Why it works |
|---|---|---|
| Free slot in the rack | RTD input module, the AEZ 414 class on TSX Micro | The module drives and linearizes the probe, so the word arrives already in temperature |
| Rack full, or probe far from the cabinet | Pt100 transmitter, 4-20 mA output, into the existing channel | The transmitter does the excitation, and the current loop ignores lead length |
| Only spare channel is voltage-type | Pt100 transmitter with a 0-10 V output matched to that range | The resistance-to-voltage conversion happens inside the transmitter |
| Several probes, no analog slots | Multi-channel RTD remote I/O polled over Modbus RTU | One converter serves the whole probe set and leaves the rack untouched |
That last row is a standard catalogue category, not a workaround: multi-channel RTD input units expose their readings as Modbus RTU registers, and choosing one follows the same criteria as selecting multi-channel Modbus analog input remote I/O.
Worked example: one transmitter loop #
Take the transmitter path with the span from the previous section, and put the probe at a process temperature of 60.0 °C. At that point the Pt100 element reads about 123.2 Ω, and the transmitter converts it to a loop current of 4 mA + (60/100) × 16 mA = 13.6 mA. The channel measures 13.6 mA, and the PLC scales linearly between the span endpoints: temperature = ((13.6 − 4) / 16) × 100 °C = 60.0 °C. The same probe on the direct path needs none of that arithmetic, because the RTD module hands the program the value 600, in tenths of a degree, ready to use.
Wiring details that move the reading #
Lead resistance is the trap in the direct path. Over its first 100 degrees the element climbs 38.5 Ω — 0.385 Ω per degree — so every ohm of copper in a 2-wire connection masquerades as about 2.6 °C of warm error (1 ÷ 0.385 ≈ 2.6), a fixed offset that grows with cable length. A 3-wire connection lets the input subtract one lead's drop and cancels that offset; a 4-wire connection removes the lead effect entirely. Both the RTD module and the transmitter support these schemes, and the wiring diagram for your module shows the terminal assignments. When a lead breaks, a current loop falls to 0 mA and an RTD channel leaves its valid range; set the channel's break detection and route that status into the alarm list as shown in detecting a failed analog input channel and reporting it to SCADA.
The decision #
For each case, the call:
- Bare Pt100 on a current-input or thermocouple channel: do not wire it and do not try to scale it — that reading will never be real.
- One or two probes and a free slot: fit the RTD input module, configure Pt100 with the lead scheme you wired, and use the tenths-of-a-degree word directly.
- Rack full, or probes far away: add a Pt100 transmitter with a current output spanned just past the process range, and scale between the endpoints.
- Voltage-only spare channel: the same transmitter with a 0-10 V output, matched to that channel range and kept to short runs.
- Several probes and no slots: multi-channel RTD remote I/O over Modbus RTU.
One safety note: a standard analog input channel is not a safety device, so if this temperature trips a heater or protects a person, design and validate the complete function — probe, channel, logic, final element — to the SIL or PL the risk assessment calls for.
Questions asked
Can I put a Pt100 on a voltage input using a resistor?
Only by converting a current signal to a voltage first; the resistor cannot excite a bare Pt100. Fit the Pt100 transmitter, then put a 250 Ω precision resistor across the channel terminals: 4 mA through 250 Ω gives 1 V and 20 mA gives 5 V, so a voltage channel sees a 1-5 V signal. Use a 0.1 % tolerance resistor and scale between those two points.
Is a Pt100 the same as a thermocouple?
No. A Pt100 is an RTD: one metal's resistance changes with temperature, so the input must drive a measuring current through it and read the voltage that current creates. A thermocouple generates its own microvolt-level signal from the junction of two dissimilar metals and needs no excitation at all. Neither device works on the other's input type, so check what is printed on the probe before you pick a channel or a module.
What transmitter span should I order?
Cover the process range with margin at both ends, then keep the span as narrow as that allows. A 0-100 °C span puts 16 mA across 100 degrees, or 0.16 mA per degree; on a 12-bit channel that is about 0.02 °C per count before noise, so resolution is rarely the limiting factor. Choose the span from the temperatures the process actually runs, and note the endpoints in the scaling block.
Can I read several Pt100s without analog channels?
Yes, through an RTD-input remote unit that speaks Modbus RTU. Converters of this class take up to four Pt100 probes, some accept Pt100, 0-500 Ω or 0-2000 Ω inputs, and they run from a 10-30 Vdc supply. The PLC polls their holding registers like any other Modbus RTU slave and scales per that unit's register map. Verify the unit's stated accuracy and update time before using it for control rather than logging.
How accurate will a Pt100 loop be?
Budget the sensor first: IEC 60751 Class B permits ±0.3 °C at 0 °C, widening linearly to ±0.8 °C at 100 °C, and Class A tightens that to ±0.15 °C at 0 °C. Then add the transmitter's or module's stated accuracy and the scaling error; the parts add up, they do not take the best of the three. If a degree matters to the process, order Class A probes and read each datasheet.