Controllers and I/O Published 8 min read

Short answer

Sixteen 4-20 mA loops become Modbus data through remote I/O with current-rated analog inputs, never through a serial converter. Match input type and loop power first, then channel count — one 16-channel single-ended module or two 8-channel differential modules — and buy only against the manufacturer's register map.

On this page
  1. The chain a serial converter cannot close
  2. The selection check, in order
  3. Single-ended or differential, decided by the grounds
  4. Loop power and the voltage budget
  5. The register map to demand before buying
  6. One device or two, RTU or TCP
  7. Commissioning before you trust the logs
  8. Questions asked

Sixteen 4-20 mA loops reach a PC as Modbus data through one class of hardware: remote I/O whose analog inputs are rated for current. A serial converter is not that hardware — it re-shapes a physical interface and measures nothing. The selection that decides success comes before any brand choice: inputs that accept 4-20 mA with the right loop-power arrangement, sixteen channels in one or two Modbus devices, and a published register map. Buy single-ended inputs only when every loop shares one grounded common; buy differential — typically eight channels per base, so two bases — when the loops come from different panels and grounds.

The chain a serial converter cannot close #

A loop becomes Modbus data in four stages: the transmitter drives current through the input's burden resistance, the module's converter digitizes the voltage that develops, firmware writes the result to a register, and the Modbus interface serves reads of that register. An RS-485-to-RS-232, USB or Ethernet converter belongs strictly after that chain exists, between a module and a host that needs a different physical layer.

That is why missing, frozen or plausible-looking-nonsense values on the PC side are not a polling bug when no analog input sits between the loops and the network. The PC application is the Modbus client requesting registers; the remote I/O is the instrument. Scale in the application only after a register demonstrably holds a digitized current.

The selection check, in order #

Run the checks in this order; each one removes candidates before price or preference can mislead:

  1. Input type. Channels explicitly rated for loop current. A 16-channel voltage input still cannot accept the loops.
  2. Channel count. Sixteen current channels across one or two devices — a single 16-channel unit, or two 8-channel units on one trunk.
  3. Input architecture. Differential unless every loop shares one grounded common reference.
  4. Loop power. Active inputs, or a documented external loop supply, for two-wire transmitters.
  5. Register map. Published before purchase: per-channel addresses, data types, diagnostics, update behavior.
  6. Protocol. Modbus RTU on RS-485 or Modbus TCP, matching the host that will poll.

The market covers every row: documented RS-485 remote I/O families with Modbus RTU and analog voltage-or-current inputs (Advantech), four-channel analog input modules that isolate input, output, power and network from one another (Acromag), and distributed remote I/O and RTU lines (Moore Industries), alongside 8-channel loop-current DIN-rail modules running from a 12 to 24 VDC supply with 9 to 28 VDC as the absolute maximum.

Check Require for sixteen current loops Walk away when
Input type Channels rated for loop current The range is voltage-only, or current needs an undocumented adapter
Channel count 16 current channels on one or two devices Reaching sixteen takes three or more devices
Input architecture Differential unless all loops share one grounded common Single-ended inputs facing separately grounded loops
Loop power Active inputs or a documented loop supply for 2-wire transmitters Passive inputs, 2-wire field devices, and no supply plan
Isolation Network isolated from power and inputs; channel grouping stated The datasheet gives no isolation statement
Resolution and format 12-bit minimum; data type and byte order documented The raw count format is unpublished
Register map Per-channel address, function code, diagnostic register, update rate No map is available before purchase
Protocol RTU on RS-485 or TCP, per the polling host The Modbus role and supported function codes are unstated

Single-ended or differential, decided by the grounds #

If all sixteen loops are powered from one supply and their negatives tie to one grounded common — the usual case inside a single panel — take the 16-channel single-ended module: the channels share that reference and you land one common connection. If the loops arrive from different panels, or the transmitters are separately powered with their own grounds, take differential inputs: each channel measures between its own two terminals, so reference differences appear as common-mode the input rejects rather than as measurement error. Plan on roughly half the channels per base in differential form — eight where the single-ended version gives sixteen — so sixteen loops means two bases at two addresses. When exactly one loop misbehaves on an otherwise clean shared-common trunk, fixing that loop with a signal isolator costs far less than re-architecting the input side.

Loop power and the voltage budget #

A two-wire transmitter gets its power from the loop: an active input supplies it, a passive input needs an external supply wired in series. Whichever arrangement you choose, verify the voltage budget at 20.0 mA, where the drops peak.

Illustrative worked example, with the values you would read off the datasheets: a 24.0 VDC loop supply, a transmitter specified to run on at least 12.0 V, a 250 Ω input burden, and 4.0 Ω of round-trip wiring.

  • Input burden: 0.0200 A × 250 Ω = 5.00 V
  • Wiring: 0.0200 A × 4.0 Ω = 0.08 V
  • Total required: 12.00 V + 5.00 V + 0.08 V = 17.08 V
  • Margin: 24.0 V − 17.08 V = 6.92 V

One receiver passes with about 6.9 V in hand. Stack a second 250 Ω receiver in series — a second logger watching the same loop — and the requirement reaches 22.08 V, leaving 1.92 V; that is too thin against supply tolerance and transmitter aging, so do not stack it. Split the loop with an isolator or repeater instead. Sensitivity: every extra 100 Ω of series burden costs 2.0 V at full-scale current, and a transmitter with an 8.0 V minimum instead of 12.0 V buys back 4.0 V. Check the module's own supply the same way — the documented 8-channel module above wants 12 to 24 VDC, so a 24 VDC cabinet feed is the natural choice.

The register map to demand before buying #

The map must state, per channel: the register address and function code (input registers on one function code at some vendors, holding registers at others), the data type — 16-bit integer counts, engineering units, or 32-bit values spanning two registers with the word order stated — the count-to-current relation or the raw values at the span endpoints, a diagnostic that flags open loops and over- or under-range, and the update rate.

Scaling then follows two formulas. With counts: engineering value = EU_low + (raw − R4) / (R20 − R4) × (EU_high − EU_low), where R4 and R20 are the raw readings at the endpoints of the span. With milliamps returned directly: fraction of span = (I − 4 mA) / 16 mA, so 12.0 mA is exactly half scale — 5.0 bar on a 0-10 bar transmitter. Keep raw, status, scaled and logged values as separate tags during commissioning so a clipped input or stale register is visible in the data.

Sixteen channels in one contiguous register block read in a single request. Gaps are workable but must be known before configuration: split each read to stay inside one block, because a read that crosses a register-map gap comes back as Modbus exception 02.

One device or two, RTU or TCP #

One Modbus RTU read of sixteen contiguous registers is an 8-byte request and a 37-byte response: 45 bytes, 450 bits at 10 bits per character, so 450 / 9600 ≈ 47 ms of line time at 9600 bit/s plus turnaround. One rack, one address, one transaction — logging at 1 s spends under 5 % of the line on it. Two 8-channel devices double the transactions and still sit under 10 %; what actually limits you is loading many devices and long register lists onto the one serial port, which is why one serial port makes Modbus RTU polling slow as device count grows. Wire the trunk as a multidrop bus: unique slave addresses from the 1 to 247 range, identical baud, parity and stop bits on every device and the host, termination at both ends, stubs as short as the layout allows.

The protocol decision is about the host, not the field side. RTU over RS-485 for one cabinet and a host with a serial port. Take a TCP coupler when the host is Ethernet-only, the run is long, or several clients read the same channels — running analog I/O over a Modbus TCP bus coupler covers that configuration, and documented TCP gateways operate across −40 to 85 °C on a 10/100 Mbit/s RJ45 port. If the polling and logging host is not yet fixed, an industrial mini PC in the cabinet makes a compact Modbus client and historian next to the trunk.

Commissioning before you trust the logs #

  1. Wire and prove one channel end to end: apply or observe the span endpoints and mid-span, and compare measured current, raw register, scaled value and logged value.
  2. Break that input deliberately and confirm the diagnostic bit and the logged status both change. If any of these loops also feeds a running controller, that break is a process trip — agree the outage before pulling a terminal.
  3. Confirm byte order and signedness against one known input, never by shifting addresses until numbers look plausible.
  4. Duplicate the wiring across the remaining channels, record the address and settings of every device, and let the logger run a full shift with raw and status values recorded alongside the engineering units.

The selection, in one line: current-rated inputs, sixteen channels in one or two devices, differential inputs unless the loops share one grounded common, a passing loop budget at full-scale current, and a register map in hand before the purchase order.

Questions asked

Can I read 4-20 mA on a voltage input module through a resistor?

Only where the manufacturer documents the arrangement. A 250 Ω resistor across a 0-5 V input gives 1.0 V at the live-zero point and 5.0 V at full scale, but it consumes 5 V of loop budget and ties channel commons together. For sixteen field loops, buy native current inputs with real isolation instead.

Is 12-bit resolution enough for monitoring and logging?

Almost always. Twelve bits split the 16 mA span into 4096 steps of about 3.9 µA each; on a 0-10 bar transmitter that is roughly 2.4 mbar per step, finer than a trend display resolves. Move to a 16-bit module when one span must carry both a wide range and small changes, or when the value feeds control.

Should this trunk be Modbus RTU or Modbus TCP?

RTU over RS-485 for one cabinet and a host with a serial port: it is the simplest multidrop, and a full 16-channel rack polls in about 47 ms at 9600 bit/s. Choose TCP when the host is Ethernet-only, the cable run is long, or several clients need the same channels at once.

How do I prove the scaling before trusting the logs?

Apply or measure the span endpoints and mid-span on one channel and check the arithmetic: (12.0 − 4.0)/16.0 = 0.50, so the register must sit at half scale at 12 mA. Prove one channel per module end to end, then spot-check the rest against a meter. Log the raw value next to the scaled value until every channel passes.

Keep reading

  • How-to

    How to run analog I/O over a Modbus TCP bus coupler

    Yes: remote analog I/O behind a Modbus TCP bus coupler can close a control loop from the PLC. Prove the electrical path with the network out of the loop, bring up the connection with a real timeout, map and scale the channels against known test points, then close the loop on measured timing — one documented integration refreshes coupler data every 10 ms, but the valve and hydraulics set the real response, and a failed exchange is a fault state, never fresh data.

    Controllers and I/O

  • Selection guide

    Add 4-20 mA analog inputs when the CompactLogix rack is full

    Swap the installed four-channel analog input card for an eight-channel one when channel isolation matches; that adds four inputs against a need of three, with no rack, power-supply or enclosure change. If isolation rules the swap out, reposition the existing power supply to free an end slot. When the cabinet itself is full, add a POINT I/O analog module or IO-Link converters over EtherNet/IP.

    Controllers and I/O

  • Explainer

    Why Modbus polling is not the same as remote I/O

    Polled Modbus moves each remote point one request-response transaction at a time, so register data refreshes on the poll cycle — commonly hundreds of milliseconds — not in step with the controller's I/O scan. Native remote I/O refreshes the whole remote image in a time close to one scan and faults deterministically on node loss. Use polled Modbus for supervisory points that tolerate its measured cycle, and native remote I/O when interlocks or short pulses need every-scan behavior.

    Controllers and I/O