Which PC interface reaches an SLC 5/05 DeviceNet network

Industrial networks Published 6 min read By IMDHMI controls team

Short answer

Use the 1784-PCD Series B card on the XP Pro SP3 laptop, or a 1770-KFD on a serial port; a 1784-U2DN covers laptops with neither. The 1761-NET-DNI is a gateway, not a programming interface, and the 1747-SDNPT Ethernet pass-through only exists on scanner firmware revisions that document it, and runs slowly even then. Land the drop cable on the four-wire trunk at any terminal block with the network de-energized.

On this page
  1. The four routes compared
  2. Why the 1761-NET-DNI is not on the list
  3. The Ethernet pass-through route and its firmware gate
  4. Tapping the trunk: five pins, four conductors
  5. Node addresses, RSNetworx and the scan list
  6. The decision for each case
  7. Questions asked

For commissioning one more VFD on an SLC 5/05's DeviceNet, the interface question has a short answer: use the 1784-PCD Series B card on the XP Pro SP3 laptop — that operating system is exactly what the card supports, and the card has already been proven on that machine — or a 1770-KFD on a serial port. The 1761-NET-DNI is a gateway for letting Ethernet devices reach DeviceNet nodes, not a programming interface, so it does not belong in this choice. The Ethernet route through the SLC 5/05 itself, the 1747-SDNPT driver in RSLinx Classic, exists only when the 1747-SDN scanner meets the firmware revisions the scanner manual documents, and even then it is slow. This comparison shows where each route fits, how to land the drop cable on the trunk, and which node addresses to assign.

The four routes compared #

Route Laptop connection Windows support Verdict for this job
1784-PCD Series B PCMCIA slot XP only; unsupported on anything newer Best choice here: the card, its cable and the XP Pro SP3 laptop all exist already
1770-KFD Serial port Works from XP-era laptops with a serial port The purpose-built tool; equal first choice when a serial port is free
1784-U2DN USB port Modern Windows The replacement when a newer laptop has no PCMCIA slot
1747-SDNPT through the SLC 5/05 Ethernet cable XP Last resort: gated by scanner firmware and slow in use
1761-NET-DNI Ethernet cable n/a Wrong tool: it bridges Ethernet clients to DeviceNet nodes, it is not a programming interface

The practical differences between the two PC-card routes come down to driver setup and slot availability rather than reach; the page comparing the 1770-KFD and the 1784-PCD walks through those differences in detail.

Why the 1761-NET-DNI is not on the list #

The 1761-NET-DNI attaches to the DeviceNet as a node and answers Ethernet clients, so a PC can pull explicit message data from remote nodes without any special card. That bridging job is not the commissioning job: building and downloading the scan list to the 1747-SDN needs a direct driver session on the network, which is what the 1770-KFD and 1784-PCD exist to provide. The two devices answer different questions, and the page comparing the 1761-NET-DNI and the 1770-KFD for DeviceNet configuration shows where each one is the right answer. Buying or borrowing a NET-DNI to avoid finding a programming interface adds a device to configure and still leaves the scan-list download unsolved.

The Ethernet pass-through route and its firmware gate #

The 1747-SDNPT driver in RSLinx Classic sends a request through the SLC 5/05's Ethernet port, across the backplane to the 1747-SDN scanner, and the scanner relays it onto the DeviceNet. It is not a feature of every scanner: the scanner installation instructions, publication 1747-IN058, list the hardware, software and firmware requirements, and the scanner user manual, publication 1747-UM655, covers using pass-through together with the ControlFlash firmware upgrade, documenting support from firmware revision 6.002.

Treat this as a way to read a parameter or verify a node from the office, not as the commissioning path: the round trip through the backplane makes browsing slow, and it earns nothing when a 1784-PCD or 1770-KFD is on hand. One more gate: the route needs a RSLinx Classic build that includes the 1747-SDNPT driver, and if the driver is absent from the installed build's driver list, that installation cannot make the connection at all.

Tapping the trunk: five pins, four conductors #

DeviceNet is a four-wire trunk: red carries the 24 V DC positive, black is V−, blue is CAN_H and white is CAN_L. Standard DeviceNet plugs are 5-pin, with the fifth pin as the drain or shield connection, and a 10-conductor cordset is simply two 5-pin connectors back to back on one body for daisy-chaining. So the loose 5-pin connector is not a lesser part; extending from the 1784-PCD cable to the nearest panel terminal block and paralleling the conductors color for color — red to red, black to black, blue to blue, white to white — is the normal way to make the tap when the trunk already lands on terminals. You can tap anywhere on the trunk where terminals exist.

Land the tap with the trunk de-energized: connecting conductors at a live terminal can jar the CAN pair enough to put the network into a bus-off fault, which stops every node at once. The scheduled down day is the window for the tap, the scan-list download and the ladder edit together.

Node addresses, RSNetworx and the scan list #

DeviceNet node addresses run from 0 through 63, 64 addresses in total, and 62 is the usual default for a programming adapter and its driver. RSNetworx for DeviceNet is where you assign node addresses, set the network rate — the choices are 125, 250 or 500 kbit/s — build the scan list and download it to the 1747-SDN. Version 10 on the laptop is workable for this; a newer version is better when it installs. One documented trap from the release notes: RSNetworx for DeviceNet is tested only on operating systems installed from original Microsoft media, in 32-bit or 64-bit versions, so an image rebuilt from other media is a known source of setup trouble. The scan-list mechanics are walked through step by step in the article on how to map a 1747-SDN scanner for DeviceNet drive control.

Worked example: take a network where the 1747-SDN sits at node 0 and three existing drives hold nodes 1, 2 and 3. The addresses run 0 through 63, so 64 exist. Set the new VFD to node 4 on its DeviceNet communication card before it powers up, and let the 1784-PCD take its default, node 62. That places 6 of the 64 addresses — nodes 0, 1, 2, 3, 4 and 62 — leaves 58 free, and, more importantly, leaves no duplicates, which is the condition the scanner needs to attach every node on its first scan.

The decision for each case #

  • XP Pro SP3 laptop with a PCMCIA slot and the 1784-PCD Series B in hand: install the PCD driver and use it. The Ethernet question is settled; there is no need for a gateway or pass-through.
  • The 1784-PCD but a newer laptop: the card is not supported above XP. Move to a 1770-KFD on a serial port or a 1784-U2DN on USB; do not fight the driver.
  • No adapter on site and only Ethernet in reach: check the 1747-SDN firmware against publications 1747-IN058 and 1747-UM655. If it meets them, the 1747-SDNPT route will read the network, slowly; if it does not, bring a 1770-KFD or 1784-U2DN before the down day.
  • Considering a 1761-NET-DNI to avoid an interface purchase: it answers the wrong question. For scan-list commissioning, use a direct interface.

After the scan list downloads and the drive takes its node, the ladder edits go into RSLogix 500, version 9.00 on this job. The drive-side steps, from setting the node address on the communication card to the scan-list entry and the data-table addresses the scanner exposes, are walked through in the article on adding a DeviceNet drive node to an SLC 500.

Questions asked

Can I get onto the DeviceNet through the SLC 5/05 Ethernet port?

Only through the 1747-SDNPT driver in RSLinx Classic, which routes requests through the Ethernet port, the SLC 5/05 backplane and the 1747-SDN scanner. The scanner installation instructions publication 1747-IN058 and the user manual publication 1747-UM655 list the hardware, software and firmware revisions the feature needs, so check the scanner's firmware before counting on it. Even when it works it is slow: acceptable for reading one parameter, poor for browsing and commissioning a whole drive.

Is RSNetworx for DeviceNet required, or is it just for commissioning?

It is required for the DeviceNet side of the job: the scan list for the 1747-SDN scanner is built and downloaded in RSNetworx for DeviceNet, and node addresses and the network baud rate are set there. Version 10 is workable for this; a newer version is worth installing when the laptop allows it. The ladder edits afterwards are RSLogix 500 work, and version 9.00 handles them.

Can I connect my drop cable while the network is running?

Landing conductors on a live terminal can jar the CAN_H and CAN_L pair enough to put the network into a bus-off fault, which stops every node at once. Schedule the tap for the down window, de-energize the 24 V DC trunk, then connect red to red, black to black, blue to blue and white to white on the matching terminals.

How long can the trunk be at each DeviceNet baud rate?

The DeviceNet specification ties trunk length to baud rate: 500 m at 125 kbit/s, 250 m at 250 kbit/s and 100 m at 500 kbit/s. Faster rates buy shorter trunks, so a long existing trunk usually means the network is already running at 125 kbit/s and your new drive and programming adapter must be set to match whatever the scan list uses.

Keep reading

  • How-to

    Choosing the DeviceNet configuration connection path

    RSNetWorx for DeviceNet cannot reach a 1769-SDN through the MicroLogix 1500 serial port: that port talks to the controller, not to the trunk. Configure the scanner from a direct DeviceNet interface such as a 1770-KFD or 1784-PCD, or route through a Logix controller port such as Ethernet on an L32E. RSNetWorx is still required for scan-list work; Auto-Configure covers only simple I/O blocks.

    Industrial networks

  • How-to

    Reach a safety PLC over EtherCAT EoE from a Windows PC

    Enable IP forwarding on both XF10 and eoe0 on the ctrlX CORE, activate the gateway's Virtual Ethernet port in the EtherCAT configuration, and add a persistent Windows route to 172.31.0.0/16 with the CORE's PC-side address as next hop. The safety tool then reaches the gateway over the EtherCAT cable with no separate service connection.

    Industrial networks

  • Troubleshooting

    Anybus DeviceNet master gateway setup for two IRC5 robots

    Device not initialized on this gateway is a configuration fault; in the reported setup it cleared in the S7-315's PROFIBUS station configuration, not on the trunk. Three masters share one DeviceNet line legally when each owns different slaves: the gateway scans both IRC5 controllers as internal slaves while each robot stays master of its own I/O node, with unique node addresses and byte counts matched on the robot, the gateway and the PLC.

    Industrial networks

Which DeviceNet explicit read reaches VLT5000 parameter data