Explainer
Which DeviceNet explicit read reaches VLT5000 parameter data
Short answer
Values a VLT5000 keeps outside its four cyclic memory-transfer words come off the drive with a DeviceNet explicit read: a Get_Attribute_Single request naming class, instance and attribute, issued with the Omron Explicit Message Send command. The object numbers come from the VLT5000's own DeviceNet manual (MG.50.HX.YY); VLT2800 class tables are candidates to prove with one test read, not values to copy.
On this page
The read that reaches VLT5000 parameter data is a DeviceNet explicit message: a Get_Attribute_Single request naming one object by class, instance and attribute, issued from the CJ1H-CPU43 through the DeviceNet unit's explicit-message command. The cyclic memory-transfer block your drives run on is fixed at configuration, so it will never carry the extra values iFIX needs. The split is therefore: cyclic for the values the drive needs every scan, explicit for everything else, including SyncPos option data. Two things decide whether the explicit read works: the object numbers must come from documentation for the VLT5000's DeviceNet option, whose manual is MG.50.HX.YY, and the request must follow the Omron command's byte format. A VLT2800 object table is a candidate list to prove with one test read, not a copy source. The sections below turn that split into bytes, checks and decisions.
Why the cyclic mapping cannot grow #
Memory data transfer mode exchanges a fixed block between the PLC data area and the drive — on this installation four words per drive, and 2 bytes per word makes 8 bytes every scan. Polled I/O delivers exactly the connection agreed at setup: every byte is assigned when the scanner is configured, and no cyclic mechanism names a parameter number — the same config-time fixity you meet when mapping a 1747-SDN scanner for DeviceNet drive control.
Your cyclic words already do the running control for this drive family; the same job taken from a PLC-5 is in VLT5000 DeviceNet control words from a PLC-5.
Decision: leave the cyclic block as configured and route every other value through explicit messaging.
What a DeviceNet explicit read is made of #
DeviceNet's application layer is CIP, the object model ODVA defines and EtherNet/IP also speaks. Compliance commits a device to the explicit message service: a request/response pair naming exactly one attribute of one object. A read is the Get_Attribute_Single service, code 0x0E, addressed by class, instance and attribute; a successful reply carries the echoed service code 0x8E followed by the value.
Worked example, one 16-bit value. The request is the service byte 0x0E plus the class ID, the instance and the attribute at one byte each: 1 + 1 + 1 + 1 = 4 bytes. The reply is 0x8E plus the two value bytes: 1 + 2 = 3 bytes. CIP fixes those shapes. It does not fix the object numbers — class, instance and attribute for your parameter come from the drive, and the Omron command wraps these bytes in its own control and status words, with the counts given in its manual's command tables.
The Identity object gives you a first read that needs no Danfoss documentation at all: class 0x01, instance 1, attribute 7 returns the product name. If that read answers, node address, wiring and explicit-service handling are all proven, and only the drive's own object numbers remain unknown. Identity behaves the same across CIP networks — what the CIP Identity object reveals about an EtherNet/IP device holds on DeviceNet unchanged.
Where the VLT5000 object numbers come from #
Danfoss's literature list for the VLT 5000 series names the document you need: the VLT 5000 DeviceNet manual MG.50.HX.YY. A parameter number by itself is not an object address; the class, instance, attribute, data type and size for each readable value belong in that manual.
Two leads when your copy prints no mapping table. Danfoss's current DeviceNet option documentation shows the format exists: the MCA 194 converter instructions carry a chapter 5 of parameter mapping lists and note that the FC 302 identifies itself on the network as a VLT 5000, so newer hardware still presents the VLT5000 device profile. Locate the mapping list that matches the option fitted to your drives rather than carrying values across documents on assumption.
The second lead is the VLT2800 DeviceNet document with its object-class table. It generates hypotheses and nothing more: every class, instance and attribute in it is a candidate to prove with one controlled read of a value you can check at the drive. Decision: an object with no documented or tested address stays out of the PLC tag set and out of iFIX.
Sending the request from the CJ1 #
The CS/CJ Series DeviceNet Units operation manual (W380) specifies the Explicit Message Send command: it sends a DeviceNet-defined explicit message to a slave and delivers the reply into a response area you allocate. The CJ1W-DRM21 unit's manual (W267) states the reach plainly — explicit messaging can read and write data in any data area. W380's command tables show where the destination node, the service and object bytes and the response length go; the drive-side numbers come from the mapping work above. That command is the builder: CX-One configures the network, node addresses and scanner registration, while the message itself is assembled in the command operands in your program.
Test one object at a time. Keep every request parameter constant while a test runs, so a failure points at one thing. Check the command's completion and the reply status before decoding payload, and decode only with the object's documented data type and length.
Reading the symptoms when a read fails #
| What you see | Where the fault sits | The check that settles it |
|---|---|---|
| No reply or command timeout | Network path or node address | Node address against the scanner registration, before any request byte changes |
| Reply status flags an error | Service or object address | Class, instance and attribute against the drive's mapping list |
| Success, value wrong | Decoding, not the read | Data type, word order and scaling against the documented object |
| Success, length wrong | Wrong object or wrong expectation | Reply length against the object's documented size |
A success with a wrong value is a decoding fault before it is anything else, and word order inside the reply is the classic version — the same trap that fixing ABB IRC5 PROFINET word values with a byte swap resolves. Work the other direction too: never edit request bytes to compensate for a wrong iFIX tag or scaling definition. The PLC value is validated first, then the SCADA mapping.
Proving the value before iFIX sees it #
Chain each object through four checks: the command completes without error; the reply length matches the object's documented size, 3 bytes in the worked example; the decoded value matches what the drive itself displays at the same operating point; only then does the value get an iFIX tag, with its scaling defined in one place.
Explicit reads are transactions, so the program's poll loop sets the update rate and network load moves it. Schedule reads for the values iFIX uses and promise no scan-rate match. Scaling into engineering units is CJ1 arithmetic, and multi-word results there carry their own trap: a multiply or divide result can spill past its target area, which CJ1 four-word result spillover fix covers.
Decisions, case by case:
- Values the drive needs every scan: stay in the cyclic block the drives already run.
- Parameter data: Get_Attribute_Single, with class, instance and attribute from the VLT5000's own DeviceNet documentation, one proven object per iteration.
- VLT2800 table entries: test candidates, never configured values.
- SyncPos data: no documented object, no read — the mapping list for the fitted option has to exist first.
- NE1A safety node: its own endpoint with its own object set; its path is proven from its own documentation, never inherited from the drive.
Questions asked
Is there a CX-One equivalent to a DeviceNet explicit message builder?
The documented builder is the command itself. The CS/CJ Series DeviceNet Units manual (W380) specifies the Explicit Message Send command, and its operands carry everything a utility screen would enter: destination node, service and object bytes, and the response area. CX-One handles network configuration, node addresses and scanner registration. No CX-One screen for composing explicit messages appears in that manual, so plan the request as program code and keep the byte layout in one tested routine.
Can the same explicit read pull data from the NE1A safety node?
Not by inheritance. The NE1A is its own DeviceNet endpoint with its own object set, so the drive's class, instance and attribute numbers mean nothing to it. Its documentation decides which objects and services it exposes; prove one known value with a single test read before any safety-system tag reaches iFIX. Until an object is documented and tested, treat that data as unavailable rather than assume the drive's behavior carries over.
How often can an explicit read update a value?
As often as the program issues it. An explicit read is a request/response transaction, not cyclic data, so the update rate is your poll rate and every read costs a full network transaction. Response time moves with network load, so stagger reads across the scan instead of piling them into one window, and keep the cyclic four words for the values the drive needs every scan.
Will the VLT2800 object class table work on a VLT5000?
Treat every class, instance, attribute and data type in it as a candidate, never as a match. The table was made for a different drive family, and a wrong class usually returns an error status rather than another model's value. Prove one entry by reading a parameter whose value you can verify on the drive's own display, then extend the working set one object at a time. A parameter number alone is not an object address.
What does an error status in the reply mean?
The device answered, so the network, wiring and node address are working; the service or the object address is wrong. An unsupported service, a class or instance that does not exist, or an attribute the object does not expose all come back as an error reply. Recheck the class, instance and attribute against the drive's DeviceNet mapping documentation before changing anything in the network configuration.