Which hardware reads two 4-20 mA inputs on a logic module

Controllers and I/O Published 5 min read

Short answer

For two 4-20 mA signals, choose by the base module's order number. The 0BA6 24RC (6ED1052-1HB00-0BA6) has no analog inputs, so fit one AM2 expansion module (6ED1055-1MA00-0BA2) and set both channels to the 0/4-20 mA range. The 0BA8 (6ED1052-2MD00-0BA8) has 0-10 V inputs, so read each loop through a 500 Ω conversion resistor; and because the 0BA6 has no Ethernet, a 0BA8 cannot serve as its networked analog extension.

On this page
  1. The decision by order number
  2. The 0BA6 path: one AM2 on the rail
  3. The 0BA8 path: current through a resistor
  4. Sizing the conversion resistor for the current loop on the 0BA8 voltage input
  5. Scaling and proving both channels
  6. Questions asked

Two 4-20 mA loops on a LOGO! logic module come down to the base module's order number. The 0BA6 24RC, 6ED1052-1HB00-0BA6, has no analog inputs at all, so the answer there is one AM2 expansion module, 6ED1055-1MA00-0BA2, with both channels set to the live-zero current range. The 0BA8 base, 6ED1052-2MD00-0BA8, carries its own analog inputs, but they are 0-10 V voltage inputs, so each current loop reaches them through a conversion resistor at the input terminals. The worked example below sizes that resistor.

The decision by order number #

Read the order number off the base module before anything is ordered or wired; it settles the whole selection:

Hardware Order number Analog capability Decision for two current loops
Base module 0BA6 24RC 6ED1052-1HB00-0BA6 None Fit one AM2 expansion on the rail
Analog expansion AM2 6ED1055-1MA00-0BA2 Two inputs, 0-10 V or 0/4-20 mA, 10 bit One transmitter per input, current range configured
Base module 0BA8, without display 6ED1052-2MD00-0BA8 On-board analog inputs, voltage only One conversion resistor per channel at the input
0BA8 as a front end for a 0BA6 6ED1052-2MD00-0BA8 plus 6ED1052-1HB00-0BA6 Needs a network link between the bases Ruled out: the 0BA6 has no Ethernet

Two neighbouring cases are not this one. On a full PLC with no analog inputs at all, the workarounds are collected in how to add a current-loop sensor to a PLC without analog inputs. On controllers that do carry a network port, remote analog input modules are a third route, covered in selecting multi-channel Modbus analog input remote I/O.

The 0BA6 path: one AM2 on the rail #

The 24RC base has no analog inputs, so a current loop has nowhere to land: not on the terminals, not in the program. Its analog expansion is the AM2, which brings two inputs and evaluates both signal families — voltage and live-zero current — at 10 bit resolution. Wire one transmitter per input and configure both channels for the current range; no conversion parts sit in the signal path, and each channel scales and alarms independently in the program.

The module occupies two module widths — 36 mm at 18 mm per module width — so confirm that much free rail beside the base before the panel closes.

A second logic module is not an alternative on this base. The 0BA8 cannot serve as a networked analog front end for the 0BA6, because the 0BA6 has no Ethernet port to link to.

The 0BA8 path: current through a resistor #

The 0BA8 base, ordered without a display, carries its analog inputs on the module itself — but they are voltage inputs, and a current loop cannot land on one directly. The conversion is a resistor placed at the input, across which the loop current develops the voltage the input reads. One resistor per channel, not one shared: two loops through a single resistor would sum their currents and corrupt both readings. With one resistor per channel, both loops are read with no expansion hardware. The resistor value is neither a catalog default nor a guess: it falls out of the input span and the full-scale current, which the next section works through.

Sizing the conversion resistor for the current loop on the 0BA8 voltage input #

The inputs, each with its source:

  • Loop signal: 4 to 20 mA, the live-zero output of each transmitter — the two signals this selection must read.
  • Input span: 0 to 10 V, the documented voltage range of the 0BA8 base's analog inputs.
  • Constraint: the full-scale current through the resistor must stay at or below the top of that span, or the top of the loop clips off.

The rule, in words: a resistor converts current to voltage by Ohm's law, V = I × R. Take the largest resistance that keeps full-scale current inside the span, so the loop uses as much of the input's resolution as the hardware allows.

The arithmetic:

  • R = 10 V ÷ 0.020 A = 500 Ω
  • Endpoints: 0.004 A × 500 Ω = 2.0 V at live zero, and 0.020 A × 500 Ω = 10.0 V at full scale
  • Full-scale dissipation: (0.020 A)² × R = 0.20 W

The result: at that value the loop maps across 8 V of the input span — 80 % of the input's resolution — with the band under live zero carrying no process meaning, free for the alarm design.

The decision: fit a 500 Ω part rated 0.5 W per channel, because the 0.20 W burned at full scale is four fifths of a 0.25 W part's rating but only two fifths of a 0.5 W part. Hold the tolerance at 0.1 % so a plus-tolerance resistor cannot push full scale over the span top: the full-scale current through a 505 Ω part already asks for 10.1 V. The computed value is a ceiling — anything above it clips the top of the loop, so never exceed it to chase resolution.

Scaling and proving both channels #

The program sees the converted signal as the LOGO! analog value: the voltage span maps to an internal value of 0 to 1000, and the analog block rescales it with a gain of 0.00 to 10.00 and an offset of -10000 to +10000. On the resistor path the loop occupies raw 200 to 1000; gain 1.25 with offset -250 spreads it back over the full internal span:

  • 1.25 × 200 - 250 = 0
  • 1.25 × 1000 - 250 = 1000

Both settings sit inside the documented windows, so no extra scaling blocks are needed. On the AM2 the module converts the current range in hardware, and only the engineering scaling is left to set.

Commission both channels at the ends of the loop: drive 4 mA and confirm the scaled value reads the loop's low process value, then drive the full-scale current and confirm the high one. Test one channel at a time, so a swapped pair surfaces before startup instead of during it, and record both endpoint readings, raw and scaled, on the commissioning sheet. If the configuration will not download to the 0BA6, the USB link is the first suspect; the failure modes and their fixes are collected in resolving 0BA6 USB connection failures.

Questions asked

Does the AM2 expansion module need its own power supply?

The module needs a DC feed: its specified supply window is 12 V to 24 V DC. A panel that already has a 24 V DC control rail can power it from there; a panel fed only with AC needs a small DC supply for the expansion. Plan any 2-wire transmitter's loop supply separately, because the module measures current and does not source it.

What resolution does the AM2 give a 4-20 mA loop?

The module converts at 10 bit, which is 1024 counts across the converted span. Over the 16 mA between live zero and full scale that is about 0.016 mA per count, so a reading changes by roughly one thousandth of the loop per count. That is ample for level, pressure and temperature monitoring; it is not a metering-grade conversion.

Is a 250 Ω resistor acceptable instead?

Electrically it works, since 20 mA through 250 Ω is 5.0 V, comfortably inside the input span. But the loop then covers only 1.0 V to 5.0 V, half the span the derived value uses, and the resolution loss buys nothing. Keep the value from the sizing example unless the transmitter's own documentation caps its burden resistance; a lower cap wins.

How does each path detect a broken current loop?

On the resistor path a broken wire stops the current, the input falls to 0 V, below the 2.0 V live-zero point, and the program alarms on under-range. The AM2's live-zero current range gives the same check in software: anything under 4 mA is a fault, not a process value. Program both alarms, then prove them by lifting one wire while the loop is out of service.

Keep reading

  • Selection guide

    Add 4-20 mA analog inputs when the CompactLogix rack is full

    Swap the installed four-channel analog input card for an eight-channel one when channel isolation matches; that adds four inputs against a need of three, with no rack, power-supply or enclosure change. If isolation rules the swap out, reposition the existing power supply to free an end slot. When the cabinet itself is full, add a POINT I/O analog module or IO-Link converters over EtherNet/IP.

    Controllers and I/O

  • Selection guide

    Which analog inputs an S7-1200 water monitoring system needs

    An S7-1200 CPU carries only two onboard analog inputs, both voltage-type, so a water monitoring system with four to six analog sensors needs SM 1231 signal modules sized one channel per transmitter: current-range channels for loop-powered instruments, voltage channels for the rest, 12-bit on voltage and 11-bit on current. The data leaves over the built-in PROFINET port through the web server's CSV pages, WinCC, or SIMATIC NET OPC - no Modbus or PROFIBUS unless a sensor itself speaks one.

    Controllers and I/O

  • How-to

    How to add a 4-20 mA sensor to a PLC without analog inputs

    Connect the transmitter through a CP1W analog input expansion unit on the CP1E's expansion connector and scale it with Pressure_bar = (I_mA - 4) × (10 bar / 16 mA). If no expansion unit fits, convert the 4-20 mA loop to a 0-1 kHz pulse train with a 24 VDC signal conditioner and count it on a high-speed counter input over a fixed gate.

    Controllers and I/O