Where TIA Portal imports a CANopen EDS file for a device

Industrial networks Published 10 min read

Short answer

Options > Manage general station description files (GSD) in TIA Portal has no CANopen function, so an .eds file never appears there. The import lives on a node added under a CANopen communication module set to CANopen manager mode: select the node, click Import EDS file, then match the node-ID within the CiA 301 range of 1–127 and run the whole segment at one bit rate the device's EDS lists.

On this page
  1. Why does the GSD dialog in TIA Portal refuse my EDS file?
  2. What is the difference between a GSD, a GSDML and a CANopen EDS?
  3. How do I tell a CANopen EDS from an EtherNet/IP EDS?
  4. Where does the CANopen EDS import sit in TIA Portal?
  5. Why is there no node list on my CANopen communication module?
  6. Which node-ID and bit rate must match after the import?
  7. What does an EDS import configure, and what stays manual?
  8. Why does my CANopen node stay silent after a correct import?
  9. Questions asked

TIA Portal never imports a CANopen EDS through Options > Manage general station description files (GSD), because that dialog has no CANopen function: it installs PROFIBUS DP and PROFINET IO descriptions only. The import lives one level down, on a node you add under a CANopen communication module set to CANopen manager mode, where the node's own properties carry the import button. This article shows where that node-level importer sits, how to tell a CANopen EDS from an EtherNet/IP file with the same extension, which node-ID and bit-rate rules decide whether the node answers, and what an import actually configures — with a worked PDO mapping and the checks that prove the bus talks.

Why does the GSD dialog in TIA Portal refuse my EDS file? #

The Manage general station description files (GSD) dialog installs PROFIBUS DP and PROFINET IO device descriptions into the project catalog, so its file browser filters for GSD and GSDML files and will never list a CANopen .eds file, whatever filter you change it to.

That is a scope boundary, not a fault in your installation. The GSD dialog works at project level: it registers a description file and fills the hardware catalog, which suits PROFIBUS DP and PROFINET IO devices because they attach to networks described project-wide. A CANopen node attaches to one specific master module in one specific slot, so its description is assigned to a node object under that module, and the manager itself consumes the file. The dialog's own failure modes belong to the PROFIBUS side — DP/PA link in TIA Portal: GSD tool MLFB mismatch and the 2BA01 fix shows what that path looks like. No filter change makes an .eds appear there; the importer for it lives on the node.

What is the difference between a GSD, a GSDML and a CANopen EDS? #

A GSD file describes a PROFIBUS DP slave, a GSDML file describes a PROFINET IO device, and a CANopen EDS describes a device's object dictionary and PDO behavior to a CANopen manager, so each format has a different consumer and a different place in TIA Portal.

Extension Network What it describes Where TIA Portal consumes it
.gsd PROFIBUS DP slave modules, diagnostics, parameter bytes the Manage GSD dialog
.gsdml PROFINET IO access points, submodules, IO data sizes the Manage GSD dialog
.eds CANopen (CiA 306) object dictionary, default PDO mapping, supported bit rates node properties under a CANopen manager
.eds EtherNet/IP, DeviceNet CIP assembly instances, connection parameters not consumed by the CANopen importer
.dcf CANopen an EDS with concrete values applied for one node generated output, not an import

The extension alone does not identify the network. EDS is a filename convention shared between CANopen and the ODVA networks, so a file that opens cleanly in one ecosystem is foreign to the other; why an EDS file will not add EtherNet/IP to a terminal server covers that trap from the EtherNet/IP side. CiA 306 defines the CANopen EDS as INI-format text, and a device certified under CiA carries a conformant EDS. The DCF goes the other way: after a bus is configured, a DCF records the concrete per-node values, so it is something a tool writes out, not the file you begin with.

How do I tell a CANopen EDS from an EtherNet/IP EDS? #

Open the file in a text editor: a CANopen EDS is plain INI-format text per CiA 306, with a [DeviceInfo] section, bit-rate keys from BaudRate_10 to BaudRate_1000, and object entries written as four-digit hex indices, while an EtherNet/IP or DeviceNet EDS instead lists CIP connections.

The hex indices point into the object dictionary CiA 301 defines — [1800] is the first transmit PDO's communication parameters, [6041] a CiA 402 drive's status word — and the same four-digit scheme carries through every standard object. An EDS can describe a generic CiA 301 device or a profiled one, from digital and analog I/O through drives, so one file format covers the whole device family. The [DeviceInfo] section matters twice: it confirms the file describes a CANopen device, and it flags which bit rates the device supports, which you need before the segment runs. If the text instead lists CIP assembly instances, connection entries or electronic keying, the file is an ODVA EDS for an EtherNet/IP or DeviceNet device, and no TIA Portal CANopen importer takes it — the device belongs on its own network or behind a gateway.

Where does the CANopen EDS import sit in TIA Portal? #

The import lives on the node object under a CANopen communication module: insert the module, set its operating mode to CANopen manager, add a node, select that node and run its Import EDS file button — the documented SIMATIC PN/CAN LINK procedure selects the default entry called CANopen node universal.

Do it in this order:

  1. If the hardware catalog has no entry for the article number printed on the module, install the module's hardware support package first; a package built for a different TIA release refuses to install, so match versions before troubleshooting anything else.
  2. Drag the CANopen communication module into the rack.
  3. In the module's properties, set the operating mode to CANopen manager.
  4. Add a node under the manager; the default entry is the generic node the documentation calls CANopen node universal.
  5. With the node selected, click Import EDS file and choose the device's .eds file.
  6. Set the node-ID to the device's own address and pick a bit rate the EDS lists.

Some third-party master modules split the job differently: the vendor's own configuration tool owns the bus and the EDS import, and TIA Portal only sees the module's process image. Check which side owns the description before hunting through dialogs.

Why is there no node list on my CANopen communication module? #

A freshly inserted module shows no node list and no import control because nodes exist only when the module acts as the CANopen manager; in the slave operating mode the module is itself a node that someone else's manager describes with an EDS, so there is nothing to import.

This mode mismatch is the single most common reason an engineer concludes the importer is missing. The node branch, the node-ID assignment and the import control all appear in the module's properties only once the operating mode says manager, because the manager is the object that consumes device descriptions. Diagnose in order: catalog entry present, operating mode set to manager, node added. Each step produces the next — no catalog entry means install the support package, no manager mode means no node list, no node means no place for the EDS to land, and every one of those dead ends looks, from the outside, like a missing feature.

Which node-ID and bit rate must match after the import? #

Two settings decide whether the node answers: the node-ID, which must be unique on the segment and match the address set on the device by switch or LSS within the CiA 301 range 1–127, and the bus bit rate, which every node on the segment must share at one value.

A node-ID mismatch produces silence, not an error: the manager sends its service requests to an address nobody answers, and the node simply stays absent, so set the project value to what the device physically carries before you blame the cable. CiA 301 defines the standard rates 10, 20, 50, 125, 250, 500, 800 and 1000 kbit/s, there is no auto-negotiation anywhere in the protocol, and the [DeviceInfo] section of each EDS flags which of them the device supports. The manager and every node run one shared value from that list; a device forced onto a rate its EDS does not list stays off the bus. A bus-off indication on the manager with both end-of-line 120 Ω terminations fitted points at a rate mismatch before anything else.

What does an EDS import configure, and what stays manual? #

The import parses the EDS object dictionary and offers the device's objects and default PDO mapping, but the file is a description, not a configuration: the PDO map you keep, the transmission types, the startup SDO writes and the node-ID remain decisions you make in the node's properties.

PDO communication parameters sit in fixed object-dictionary blocks — 0x1400 upward for receive PDOs and 0x1800 upward for transmit PDOs — with mapping parameters one block over at 0x1600 and 0x1A00. Confirm each PDO's transmission type: a cyclic-synchronous PDO needs the manager to produce SYNC objects, an event-driven PDO fires on change or on its event timer. Add the startup SDO writes the device needs before it enters operational — a mode-of-operation selector, a scaling factor, an event time. Startup SDO writes change how a drive behaves, so before the manager starts nodes into operational, put the machine in a state where live outputs cannot move a load. Compile, and the module assigns process-image addresses to the mapped PDO bytes; those offsets are what your program reads and writes.

Worked example, using example CiA 402 drive objects: map receive PDO 1 with the control word 0x6040 (2 bytes) and the target velocity 0x60FF (4 bytes). The arithmetic is 2 + 4 = 6 bytes, inside the 8 data bytes a CANopen PDO may carry, so the map fits one PDO. Add the target position 0x607A (4 bytes) to the same PDO and the sum is 6 + 4 = 10 bytes, over the PDO limit, so the compile rejects the node — put it in receive PDO 2 instead. The same decision shape applies when a gateway fronts the drives, as in running CiA 402 CANopen drives from an S7-1500 through a gateway, where the mapping lives on the gateway side.

Why does my CANopen node stay silent after a correct import? #

Silence after a clean compile points at addressing or the physical layer before it points at software: the project node-ID and the device's address disagree, the segment runs two bit rates, or a terminating resistor is missing, and the manager reports an absent node rather than raising an import error.

Verify in three steps. Compile first: expect zero hardware-configuration errors, and a PDO over the 8 data bytes or a node-ID collision fails here rather than on the wire. Go online second: the manager should sit in its operational state with no bus-off indication, and a bus-off with both terminations fitted points at the bit rate, not the program. Third, watch the module's input address range in a watch table while toggling a physical input on the device: the mapped bit must follow. Static process data with the node operational means the PDO is mapped but never fires — check the transmission type, set an event timer or confirm SYNC production.

Three failures recur after a working import. Vendor-specific keys outside CiA 306 can be dropped silently, so compare the imported object list against the device manual and add missing entries by hand. An EDS written for an older firmware revision can map objects the shipped device does not implement, which surfaces as service-request aborts at startup — take the file matching the revision on the nameplate. And re-running the import on a node discards manual PDO edits, so finish choosing the file before tuning the map. Close the job by power-cycling the station and repeating the watch-table check: the mapped data must come back on its own through the node's boot-up.

The decision, case by case:

  • A GSD or GSDML file for a PROFIBUS DP or PROFINET IO device goes through the Manage GSD dialog, as it always has.
  • A CANopen EDS goes through a manager-mode CANopen module: add the node, import on the node, then match the node-ID and run the segment at one shared rate.
  • An EtherNet/IP or DeviceNet EDS has no CANopen importer anywhere in TIA Portal; put that device on its own network or behind a gateway.
  • An imported node that stays silent: match the node-ID, confirm one bit rate across the segment and both terminations, then repeat the watch-table check.

Questions asked

Can two devices share one CANopen EDS file?

Yes, if they are the same device type running the same firmware revision, because the EDS describes the type, not the individual unit. Each device still gets its own node object on the manager and its own unique node-ID. An EDS written for a different firmware revision can list objects the shipped device does not implement, and those missing objects surface as service-request aborts during startup writes.

Do I need a DCF file instead of an EDS in TIA Portal?

No. A DCF is a CANopen description with concrete values filled in for one node, such as its node-ID and configured PDO contents, and tools normally generate it after a bus is configured. Inside TIA Portal the node object itself holds those per-node values, so the project takes the EDS at import and stores the rest.

What happens if two CANopen nodes get the same node-ID?

Both devices answer the manager's service requests on the same address, responses collide, and both nodes look faulty or absent, while the compile stays clean because the conflict is on the bus, not in the project. Assign each node-ID once per segment inside the CiA 301 range, then set the matching value on the device's switch or configuration before powering the segment.

How does this change when a CANopen device hangs off a gateway?

A controller without a CANopen port reaches these devices through a gateway that runs the manager itself: the gateway appears in TIA Portal as a PROFIBUS or PROFINET device described by its own GSD or GSDML file, and the EDS import happens in the gateway's configuration tool. The node-level import described above applies only to a CANopen master module configured directly in a TIA Portal project.

Keep reading

  • Selection guide

    How to choose between Modbus, Profibus and CANopen

    Match the protocol to the PLC master that already exists, not to the datasheet that impressed you. Then fit the cable run to the bit rate, because CAN-based trunks shorten as speed rises, and mix protocols one segment at a time through gateways or the PLC itself. A fourteen-device example shows the arithmetic.

    Industrial networks

  • Troubleshooting

    DP/PA link in TIA Portal: GSD tool MLFB mismatch and the 2BA01 fix

    The GSD-tool workflow in TIA Portal V15 does not take the 6ES7153-2BA10-0XB0 IM153-2 directly, so the DP/PA link station never comes up. Siemens documents that MLFB as the spare-part successor of the earlier IM153-2, so configure the station as 6ES7153-2BA01-0XB0 or 6ES7153-2BA02-0XB0. The DP network then runs at 1.5 Mbit/s with the PA segment separate — no 45.45 kbit/s coupler-only setup needed.

    Industrial networks

  • Comparison

    PROFINET versus DeviceNet for machine and panel I/O

    Choose by controller ecosystem first: PROFINET is industrial Ethernet at 100 Mbps with line, star and ring topologies, while DeviceNet is a CAN-based trunk running 125 to 500 kbps. Speed only decides when the panel needs dense or fast I/O. PROFINET for new high-speed machines, DeviceNet where the Rockwell-era devices and wiring already exist.

    Industrial networks