Start and stop ControlLogix polling in iFIX through RSLinx

SCADA and data logging Published 7 min read

Short answer

Stop one ControlLogix PLC's polling by disabling its ABR device: acquisition for that controller stops while other devices on the channel keep updating. Mission Control stops the entire driver and every controller behind RSLinx Gateway, so reserve it for a full pause. Wire Start and Stop buttons to the device's enable state, then test both directions.

On this page
  1. What should the Start and Stop buttons actually stop?
  2. How does iFIX reach the ControlLogix PLCs through RSLinx Gateway?
  3. Which of the four stop levels fits the request?
  4. How do you map each point to its channel, device, and block?
  5. How do you build Start and Stop buttons at device scope?
  6. Does switching to a dummy OPC topic work in iFIX?
  7. How do you verify the pause and the restart?
  8. Questions asked

Stop polling for one ControlLogix PLC by disabling its device entry in the ABR driver; that is the narrowest scope that matches the request. Do not wire the buttons to Mission Control — that stops the communication driver itself, so every controller iFIX reaches through RSLinx Gateway goes quiet together. The ABR driver gives you four stop levels, and picking the level that matches what the operator asked for is the whole engineering decision; the wiring and the test are short.

What should the Start and Stop buttons actually stop? #

The ABR device for that controller, nothing wider: one device entry stands for one controller in the driver configuration, so disabling it pauses acquisition for exactly that PLC while the other devices on the same channel keep updating.

The request is to start and stop polling of specific ControlLogix PLCs, and the failure mode to design against is stopping more than that. Pausing acquisition pauses your view, not the machine — the controller program and its outputs keep running, so lockout on the equipment is unchanged. When only some signals need to go quiet, drop one level narrower and disable those blocks; the controller's other data keeps updating. Reserve the driver-level stop for a genuine everything-pauses window, and label that button for what it actually does.

How does iFIX reach the ControlLogix PLCs through RSLinx Gateway? #

The iFIX SCADA node runs the ABR I/O driver, an OPC client to RSLinx Gateway: each data block scans at its configured rate, and the driver reads that block's OPC item from the topic serving the controller.

RSLinx Gateway reads a controller to serve the OPC items its clients subscribe to, so the polling you want to stop is demand driven from the iFIX side — when the ABR driver stops asking for a controller's items, the demand behind that polling goes with it. Above the blocks you have two levers: Mission Control, which starts and stops iFIX background tasks including the communication driver, and the ABR driver's own enable and disable for channels, devices, and blocks. The first is a hammer; the second matches a per-PLC request. If the deeper problem is how much the SCADA server polls in the first place, PLC data concentrator vs SCADA server for RTU polling covers where collection should live.

Which of the four stop levels fits the request? #

Use the device level to pause one controller, the block level to pause selected data only, and the driver level only when every controller behind RSLinx Gateway must pause; the channel level fits only when the channel boundary equals the request.

Level you stop What stops What keeps running Use it when
Driver, through Mission Control The ABR driver and all iFIX traffic through it Other iFIX drivers, if any; nothing on ABR A commissioning or maintenance window covering every ABR controller
Channel Every device on that channel Devices on the other channels The pause boundary is one whole network path
Device Acquisition for one controller Every other device on the same channel The request names one PLC
Block One block's acquisition Everything else, including that controller's other blocks Only selected signals must pause

Worked example, an illustrative configuration rather than a specification: one ABR driver, two channels, seven devices, 120 blocks, with the target PLC as one device carrying 18 of those blocks on channel 1.

  • Device scope: 18 of 120 blocks stop, 120 - 18 = 102 blocks and 7 - 1 = 6 devices keep updating.
  • Block scope on 5 of the 18: 5 blocks stop, 120 - 5 = 115 keep scanning, and the controller stays fully reachable.
  • Driver scope through Mission Control: 120 - 120 = 0 blocks update, and every controller freezes at once.

Device scope stops 18/120 = 15 percent of the database instead of 100 percent, which is why it is the default answer to "stop polling this PLC".

How do you map each point to its channel, device, and block? #

Open the ABR driver configuration, find the device entry for the target controller, and list every block that reads from it; that map is the whole decision, because it shows what else shares each level you could stop.

  1. Open the ABR driver configuration on the SCADA node and write down the channel list and the device list.
  2. Identify the device whose OPC topic serves the target ControlLogix controller, and note which channel owns it.
  3. Open Database Manager, list the blocks that reference that device, and count them.
  4. Note which displays, trends, and alarms consume those blocks, because their data freezes with the device.
  5. Stop work if the mapping is unclear: a button bound to a guessed device silently stops the wrong controller.

In the driver configuration dialog, each device carries an Enable check box — that state is what your buttons write.

How do you build Start and Stop buttons at device scope? #

Build two actions that write the target device's enable state: Stop clears the Enable state the ABR configuration holds for that device, Start sets it again, and the screen button fires the action through the mechanism your iFIX release documents for driver control.

  1. Create the Stop action so it sets the target device's enable state to disabled, at device scope only.
  2. Create the Start action so it restores the same device's enable state.
  3. Wire the two screen buttons to those actions and put both behind the access level your operating procedure requires.
  4. Add a state indication on the screen — paused or running — driven by the device's enable state, never inferred from the last value shown.
  5. Label the buttons for the real scope, "stop Line 3 PLC data" rather than "stop polling", so nobody expects the other controllers to freeze.
  6. Run the first test in a commissioning window, at device scope, before the buttons go into normal operation.

The exact call a screen makes to change that state is version specific: take it from the iFIX documentation for your release instead of hardcoding a tag or method name you have not verified. What you control is the enable state, and where it lives is the device entry in the driver configuration.

Does switching to a dummy OPC topic work in iFIX? #

Not as the first choice: topic switching is a technique from another HMI package, and iFIX already has native enable and disable at channel, device, and block level, so the loopback topic adds risk without adding control.

The trick points the client at a topic that resolves to the driver itself, which keeps returning the last values — the screens look alive while the data is frozen. That is exactly the failure you are trying to make visible, built in on purpose. In iFIX the pause is a first-class setting: disable the device, show the paused state, and the frozen values carry an honest label.

How do you verify the pause and the restart? #

Press Stop, confirm the target controller's values stop moving while a point from another device on the same channel keeps updating, then press Start and confirm the frozen values move again — test both directions every time.

  1. Before the test, note the current values of one target point and one unrelated point from a different device.
  2. Press Stop. Confirm the state indication shows paused, the target point holds its last value, and the unrelated point keeps changing.
  3. Press Start. Confirm the state shows running and the target point resumes updating.
  4. Test the access level: a user without rights must not be able to flip the state.
  5. If the target keeps updating after Stop, the mapping is wrong — recheck the device entry before widening the scope, because a broader stop masks the mistake while it disrupts unrelated data.

The decision in one line: device scope for one controller, block scope for selected signals, the Mission Control stop only for a full pause, and channel scope only when the channel is the boundary you meant.

Questions asked

Does RSLinx Gateway stop polling the PLC once iFIX stops reading it?

RSLinx Gateway reads a controller to serve the OPC items its clients subscribe to. When the ABR device is disabled and iFIX drops those items, the demand behind that polling goes with it, unless another OPC client on the gateway still subscribes to the same controller. Check for other clients before assuming the network traffic is gone.

What do operators see on screen while the device is disabled?

The last acquired values stay on screen, and a value being visible is not proof it is live. Tie a state indication to the device's enable state so operators see paused versus running, and if the pause can last long, add a heartbeat tag the PLC toggles so staleness is unmistakable.

Is stopping the driver in Mission Control ever the right choice?

Yes, when the request is genuinely to pause everything the ABR driver reaches, such as a commissioning window or network-wide maintenance. Name the button for that scope, and after the restart verify every dependent controller, not only the one you watched during the test.

What if pressing Start does not restore updates?

Check the device's enable state in the driver configuration first, then the mapping: the buttons may be writing a different device or block set than the one that stopped. Re-run the pause test with the driver's diagnostics open. If the supported way to drive that state from a screen is still unclear, get the documented mechanism from the vendor before widening the scope of the stop.

Keep reading

  • Troubleshooting

    Fixing CODESYS OPC DA memory growth stopping SCADA reads

    The reads stop because WinCoDeSysOPC.exe, a 32-bit OPC DA server process, climbs to its 2 GB memory ceiling over weeks and then stops serving tags; killing it only resets the clock. The resolution that held was installing the current, licensed CODESYS OPC DA server — 3.5.22.40 in place of the CODESYSV35SP10Patch2 install — and proving it through the old failure window.

    SCADA and data logging

  • How-to

    Getting CompactLogix PLC data into Excel over EtherNet/IP

    Excel has no EtherNet/IP client, so a CompactLogix reaches a workbook only through a driver layer: an RSLinx edition that documents OPC or DDE support, or a driver library used within its license — RSLinx Classic Lite does neither. Put the PC and controller on one subnet, prove a single controller-scoped tag read, map that one cell, and add writes only against a dedicated test tag the logic validates.

    SCADA and data logging

  • Selection guide

    Selecting SCADA software for mixed PLCs and SQL logging

    Shortlist the candidates, then pass or fail each one on nine commissioned paths: a live read from every PLC family in the mix, one parsed serial ASCII transaction, a browser client session on the target touch-panel PC, and one logged record in SQL Server or MySQL verified across a database outage. Accept a package only when every path passes all its checks; a failed path keeps a candidate alive only with a named gateway or OPC route.

    SCADA and data logging