SINAMICS V20 USS communication with an S7-300 instead of PROFIBUS
Short answer
No, the SINAMICS V20 has no PROFIBUS interface, so standard telegram 1 (PZD2/2) cannot be selected for it on an S7-300 DP network. The drive's remote-control path is USS over RS-485: a serial master port on the PLC side, a terminated twisted-pair bus, and the drive's command and speed-reference sources set to that serial link. For the S7-300 the feasibility lives in the serial communications module in the rack; a new panel takes an S7-1200 or S7-1500.
On this page
- Why standard telegram 1 cannot be selected for the V20
- What the V20 offers instead
- What changes for the S7-300
- USS transactions instead of cyclic telegrams
- Terminating the RS-485 bus for one serial port and two V20 drives
- If the DP network cannot change
- Communication loss and the safety boundary
- The decision for each case
- Questions asked
No. The SINAMICS V20 has no PROFIBUS interface, so the drive never appears as a station on the S7-300's DP network and standard telegram 1 (PZD2/2) cannot be selected for it. The drive's documented remote-control path is USS over RS-485, and that changes the commissioning order: a serial master port on the PLC side, a terminated twisted-pair bus out to the drive, and the drive's command and speed-reference sources pointed at that serial link — all before any word mapping is written. This article gives the decision for each case: what to do when the S7-300 rack must stay, what to build into a new panel, and what fits when the DP network is immovable.
Why standard telegram 1 cannot be selected for the V20 #
A PROFIBUS telegram is chosen per slave station: the device declares itself on the bus, and the telegrams it can exchange are listed from its own interface. Standard telegram 1 is the smallest of those arrangements, two process-data words out to the drive and two back — the PZD2/2 in the original question. The V20 never reaches that step, because it has no PROFIBUS interface to declare; its fieldbus connectivity is USS on RS-485, and a USS device does not present itself as a DP station. This is not a setting you failed to find. There is nothing to select for this drive, in any hardware configuration you can build around it.
A drive that does carry a PROFIBUS interface takes the normal DP route, the one described for an S7-300 and an MM420 in Configuring S7-300 PROFIBUS control for an MM420 drive.
What the V20 offers instead #
USS — the drive protocol Siemens documents as the protocol of the universal serial interface — runs over RS-485 with one master polling one or more addressed drives. The V20 joins it at its RS-485 terminals, and its operating instructions fix the physical layer: screened twisted pair for the run, with the bus terminated by fitting bus terminating resistors.
The drive-side settings come before any PLC programming: a distinct USS address per drive, a baud rate the master port also runs, and — the selection that decides whether any of it works — the command source and the speed-reference source set to the serial link. Leave those two at their local source and the drive will answer every poll politely while running from its own terminals; the HMI speed-entry consequence of a serial-referenced V20 is explained in why a CB1241-driven V20 takes no HMI speed entry.
What changes for the S7-300 #
The DP port on the S7-300 CPU speaks PROFIBUS and will never carry USS: the two differ from the electrical layer up, so the port you configured for the network is not the port for the drive. USS needs an RS-485 serial master on the controller side, and that port decides the route:
| Your situation | The route | What decides it |
|---|---|---|
| S7-300 rack must stay | A serial communications processor in the rack acting as USS master | Whether that module's documentation lists USS among its protocols |
| S7-200 family in the panel | The CPU's serial port with its documented USS support | The port then serves USS alone; no second protocol on it |
| New machine | S7-1200 or S7-1500 with the USS instructions in TIA Portal | Published application examples: support entry 63696870 for an S7-1200, entry 90468030 for an S7-1500 with ET 200SP |
For the installed S7-300 the decision is binary. Read the order number of the point-to-point serial module in the rack and open its documentation: if USS is among the protocols it lists, the rack can master the V20; if it is not, this PLC cannot talk to the drive, and no amount of parameter work on either side changes that. Hand a port to the USS master logic and it serves USS alone — no HMI and no second protocol on that port while the master runs. For a new panel the choice is made for you: the S7-1200 and S7-1500 carry documented USS instructions, and the manufacturer's application examples cover exactly this pairing, which makes that route the recommendation wherever the controller is not already installed.
USS transactions instead of cyclic telegrams #
On a configured DP network the words arrive in the process image every bus cycle and the program never sees a transaction. USS is the opposite: the program forms each request, addresses the drive, sends it on the port, waits, checks the reply, and only then acts on it.
Three rules keep that honest. Keep command preparation separate from transaction sending — rewriting the transmit buffer while a request is in flight corrupts the request or hides the one that actually went out. Treat a stored reply as stale until proven fresh: the drive address and a per-drive receive flag tell you which poll the answer belongs to. Map the words from the V20's own USS documentation: the frame carries a command word, a status word and the speed values as process data, and their bit assignments and speed scaling are defined in the drive's operating instructions, not in a PROFIBUS telegram printout left over from another job.
The fault that follows most often is a drive that answers every poll but will not start, because the command source was never moved to the serial link. That failure is worked end to end in S7-1200 USS MM420 run-command failure walkthrough.
Terminating the RS-485 bus for one serial port and two V20 drives #
The inputs: one serial port acting as the USS master and two V20 drives, wired as a three-node line — the layout a two-drive panel gives you. The physical rules come from the V20 operating instructions: screened twisted pair for the RS-485 run, and termination fitted as a 120 Ω bus terminating resistor.
The rule in words: an RS-485 bus is a line, only its two physical ends are terminated, and every node between the ends is left unterminated.
The arithmetic: three nodes on one line put the master port at one end and the far drive at the other, so the ends take one 120 Ω resistor each — 2 ends gives 2 resistors. The interior node count is 3 − 2 = 1, so the drive in the middle carries no resistor.
The result: 120 Ω fitted at the master end of the twisted pair and 120 Ω at the far drive, with the middle drive unterminated between them.
The decision: this bus carries exactly two 120 Ω terminators — never one, never three. Zero termination is the classic cause of sporadic framing errors on a link that otherwise looks sound, and a third resistor means a middle node was terminated by mistake. When a third drive extends the line, the bus end moves: the far-end resistor belongs on the new far drive, and the drive that held it becomes an interior node with none.
If the DP network cannot change #
Two routes, in order of preference. If the drive choice is open, fit a drive with a documented PROFIBUS interface and use standard telegram 1 as designed; the V20 is the wrong drive for that slot. If the V20 must stay, a protocol gateway bridges it: the gateway masters the drive over USS on the RS-485 side and presents itself to the S7-300 as an ordinary DP slave, with the word mapping defined by the gateway's documentation rather than by telegram 1 or by the drive's USS frame. A gateway the S7-300 detects but reads no I/O data from is its own commissioning fault, covered in fixing an S7-300 PROFIBUS gateway that reads no I/O data.
Communication loss and the safety boundary #
Configure both ends of the failure path together: the drive's documented response when valid USS messages stop arriving, and the PLC's response when a transaction fails or times out. A speed reference stored in PLC memory is not a live command, and a reply older than one poll is treated as no reply.
One safety note: a stop commanded over USS is an ordinary process stop, so every safeguarding function the machine's risk assessment calls for must act through dedicated safety hardware, independent of the serial link.
The decision for each case #
- You asked whether the V20 takes telegram 1 (PZD2/2) on DP with an S7-300: no. The drive has no PROFIBUS interface, so the question ends there.
- The DP network is fixed and the drive choice is open: fit a drive with a documented PROFIBUS interface, and telegram 1 then behaves as the network expects.
- The S7-300 and the V20 are both fixed: the serial module order number in the rack decides. If its documentation lists USS, wire the RS-485 line in screened twisted pair under the two-terminator rule, set each drive's address, baud rate, command source and reference source to the serial link, and build the transaction handling. If it does not list USS, this rack cannot master the drive — change the module or the controller.
- New machine: S7-1200 or S7-1500 with the documented USS instructions and the manufacturer's V20 application example. Published documentation backs every step of that route, which is why it is the recommendation wherever the controller is not already installed.
Questions asked
Can the serial port that runs USS also talk to an HMI?
The S7-200 SMART manual is explicit about it: once a port is set to USS for drives, no other use is allowed on that port, an HMI connection included. The port belongs to the USS master logic alone. So an operator panel goes on the CPU's other interface or its network port, and any port handed to USS is treated as unavailable to everything else for the life of the program.
What sets the update time between the PLC and the drive on USS?
The program's transaction schedule. USS is request and response: a drive is updated only when the master sends it a request and takes in the reply, so nothing moves in the background the way a configured PROFIBUS telegram does. Fewer words per request and fewer drives on the bus shorten the cycle; a noisy line that forces retries stretches it.
Can a second PLC share the same RS-485 bus with its own USS master?
No. USS is a single-master bus: one port owns the polling, and every drive on the line answers only that master. A second controller that needs the drive's data takes it from the first controller over the network between the PLCs, not from the drive's bus.
How many V20 drives can one USS master port control?
Several. USS is a master-slave bus, so one port controls multiple drives, each polled at its own distinct address. The S7-1200 and S7-1500 documentation states that their USS instructions can communicate with several drives on the bus. The practical count for a given port comes from that port's own documentation and from how fast each drive must be updated for the process.