Drives and motion Published 6 min read

Short answer

The second telegram does not belong to a second device. STARTER models the SINAMICS DCM as two communication objects, the CUD and the drive, and gives each its own telegram; a telegram is a fixed layout of process data words, not hardware. Keep the drive telegram because it runs the motor, map the CUD telegram only for signals the program uses, and remove it only where the documentation for the installed configuration allows.

On this page
  1. One enclosure, two objects
  2. What a telegram is
  3. Why the CUD keeps its own interface
  4. Worked example: two areas, twelve bytes each way
  5. Make both sides agree
  6. The decision, case by case
  7. Questions asked

Insert a SINAMICS DCM with an advanced CUD as a PROFIBUS slave, open the communication configuration in STARTER, and two telegrams appear: one between the PLC and the CUD, one between the PLC and the drive. That is not a duplicated slave and not a mistake. STARTER models the DCM as two logical objects, the control unit device (CUD) and the drive, and each object owns its own telegram. A telegram is a fixed layout of process data words, so the second one costs a second area of the process image, not a second device. The drive telegram runs the motor. The CUD telegram carries controller-level signals, and you remove it only where the documentation for your configuration allows.

One enclosure, two objects #

The surprise is fair, because the DCM arrives as one unit, but every SINAMICS drive is engineered as a set of objects, not as a box. In the SINAMICS G and S families the control unit and the power module are physically separate parts, and one control unit can serve several drives, so the model gives the control unit its own interface and each drive its own. The DCM puts the control electronics and the power section in one enclosure and keeps the same object model: the CUD is the object that hosts the PROFIBUS connection, and the drive is the object that represents the motor-control function. Two objects, two telegrams, one slave. Building the PROFIBUS or PROFINET link itself, network, addressing and integration into the CPU, is covered in Connect an S7-300 to a DCM drive over PROFIBUS or PROFINET; the rest of this article is about the telegram model and what to do with the second telegram.

What a telegram is #

A telegram is a defined arrangement of cyclic process data words. The rules come from PROFIdrive, the drive profile of PROFIBUS and PROFINET, standardized as IEC 61800-7: a telegram number fixes how many words are exchanged in each direction and which signal occupies each word, and both ends must select the same arrangement. On the S7-300, as PROFIBUS master, the arrangement appears as output words written toward the drive and input words read back. The classic drive telegram carries a control word and a setpoint toward the drive, and returns a status word and an actual value. PROFIdrive also fixes the scaling of normed setpoints: 16384 stands for 100 percent of the drive's reference quantity, so each percent of reference is 16384 divided by 100, about 164 counts.

Which signals sit in the CUD telegram and which in the drive telegram is not decided by the object names. It is decided by the telegram selected for each object, and the selected telegram's description, shown in STARTER for the configured objects, is the only place to read it.

Why the CUD keeps its own interface #

The CUD is not a second drive. It hosts the PROFIBUS connection and the controller-level functions, and its telegram is the channel the profile defines for that object: whatever signals the selected telegram assigns to it travel there, independent of the drive telegram. The separation originates in the modular SINAMICS architecture, where it is a necessity; the DCM applies the same model to hardware that happens to share a housing. That makes the CUD telegram worth reading rather than deleting: a true leftover would carry nothing, and whether it carries something your application wants is answered by its signal list, not by the enclosure.

Worked example: two areas, twelve bytes each way #

Hypothetical numbers, chosen to show the arithmetic. Suppose the configured drive telegram is four words in each direction and the CUD telegram is two words in each direction. Bytes per direction: 4 words × 2 bytes per word = 8 bytes for the drive telegram, 2 words × 2 bytes per word = 4 bytes for the CUD telegram, and 8 + 4 = 12 bytes total. If the S7-300 hardware configuration places this slave at byte 256, the slave occupies outputs 256 to 267 and inputs 256 to 267. Word addresses step by two because each word spans two bytes: the drive control word is output word 256, the setpoint is output word 258, the status word is input word 256 and the actual value is input word 258, while the CUD words sit at 264 and 266. The order, drive telegram first and CUD second, is read out of the configured module list, never assumed.

Scaling check with the same example: with a reference speed of 1500 rpm, a command of 750 rpm is 750 ÷ 1500 × 16384 = 8192, so output word 258 receives 8192.

Before testing any changed mapping, disable the drive or uncouple its load: a control word that reaches the wrong address can command an unplanned rotation.

Make both sides agree #

The model is harmless as long as both ends describe it identically. Work through four checks.

  • In the S7-300 hardware configuration, confirm the DCM appears once, at its PROFIBUS station address, with both telegram areas as modules under that one slave.
  • In STARTER, confirm each telegram entry has an owner inside this DCM, the CUD object or the drive object, and that neither belongs to another drive object or device.
  • Compare length and order: the total bytes and the module sequence the hardware configuration shows must equal what the drive side shows. A mismatch either stops cyclic exchange or shifts every word after the disagreement, and a plausible value at a PLC address is no proof that the intended signal sits there.
  • Check the communication diagnostics on both sides, then monitor one defined status signal and confirm the PLC indication agrees with the drive's own indication.

A working bus proves that data moves, not that the program reads the right word. If STARTER must reach the drive online through the S7-300, that path is its own setup, covered in connecting STARTER to a PROFIBUS drive through an S7-300.

The decision, case by case #

Commit per case:

Case Decision
Drive telegram; the program sends commands or reads status through it Keep it. It is the motor-control interface. Map it word by word and prove one status bit against the drive's display.
CUD telegram carries signals the program reads or writes Keep it and map those signals. It has a real role.
CUD telegram; nothing in the program touches its addresses Leave it configured and map nothing to it. Removing it changes the module layout and can shift the drive telegram's addresses, for a saving of a few bytes. Remove it only where the documentation for the installed configuration offers a layout without a CUD telegram, then re-verify every address.
The two sides disagree on length or order Stop and fix the configuration first. No mapping decision means anything until they match.

For a line-up of several DCMs where the S7-300 only commands speed and reads status, the committed configuration is one drive telegram per DCM at a documented telegram whose signals match your program, the CUD telegram left as configured, and nothing in the program mapped to it. Two telegrams per DCM is the model working as designed: one slave, two process data areas.

Questions asked

Does the CUD telegram give the DCM a second PROFIBUS station address?

No. The DCM keeps one station address, and both telegrams are process data areas under that single slave; their offsets come from the module order in the hardware configuration. A second station entry would create a second slave the drive cannot answer for, so treat a duplicate station as a configuration error and delete the duplicate entry, not the telegram.

Is the PLC-to-CUD telegram a copy of the drive telegram?

No. Each object's telegram has its own signal set, fixed by the telegram selected for that object. The drive telegram normally carries the motor signals, control word, setpoint, status word and actual value, while the CUD telegram carries the signals its own description assigns. List both word by word in STARTER before deciding the second one is redundant; equal lengths do not mean equal contents.

Is it worth deleting the CUD telegram to free process image space?

Almost never. In the worked example the CUD area is four bytes per direction, small against the process image of an S7-300, and deleting the telegram changes the module layout, which can move the drive telegram's addresses and silently break the program mapping. Keep the area and map nothing to it unless the documentation for the installed configuration explicitly offers a layout without it.

Where are the telegram layouts documented?

In two manuals and one screen. The SINAMICS DCM List Manual's telegram overview assigns a signal to every word of every supported telegram, and the SINAMICS DCM Control Module manual describes the CUD and its communication interfaces. In the project, STARTER shows the word-by-word assignment for the telegram actually selected on each object, and that is the version which must match the S7-300 hardware configuration.

Keep reading

  • Troubleshooting

    Why an ATV71 on PROFIBUS needs a power cycle to initialize

    An Altivar 71 that appears in S7-300 diagnostics but only readies after a power cycle is failing its command-state sequence, not its PROFIBUS connection. Step the command word only when the status word confirms each state, and check that both the command channel and reference channel point at the network.

    Drives and motion

  • How-to

    Bridging a PLC-5/15 DH+ network to a Kinetix 300 servo drive

    Yes, a DH+-to-EtherNet/IP gateway exchanges command and feedback words between a PLC-5/15 and a Kinetix 300, but it only moves data: the drive must execute the motion profile locally. Replace the stepper controller, pulse expander, and encoder-counter functions with an eight-word map that carries a 32-bit position as two 16-bit words behind a data-valid handshake. If the machine needs trajectory points streamed per scan, migrate the controller instead of bridging it.

    Drives and motion

  • How-to

    Connect an S7-300 to a DCM drive over PROFIBUS or PROFINET

    Yes: an S7-300 controls a DCM over PROFIBUS or PROFINET by installing the drive's GSD or GSDML description, selecting the same supported telegram on both sides — standard telegram 1 (PZD-2/2) is the safe first choice — exchanging the 4-byte records with SFC14 and SFC15, and trusting the link only once cyclic exchange runs fault-free. A clean link still will not move the motor while the drive's command source is local or an enable is missing.

    Drives and motion