Drives and motion Published 8 min read

Short answer

Pick a servo drive that closes its own position loop and accepts its commands from the MicroLogix 1500's outputs: a point-table drive driven by binary select bits for preset positions, and pulse train plus direction from the controller's high-speed outputs for fine axes. SERCOS and Logix-only EtherNet/IP servo platforms do not fit, because the MicroLogix 1500 has no servo motion instructions to be their master.

On this page
  1. What the MicroLogix 1500 puts on a drive
  2. The command interfaces that fit
  3. The interfaces that do not fit
  4. Example: how fast does one pulse-train axis turn?
  5. Count the I/O before you order
  6. Wiring, feedback and the one safety rule
  7. The decision, case by case
  8. Questions asked

A manual machine tool retrofit that keeps its MicroLogix 1500 for relay logic should buy AC servo drives that the controller can command with nothing but discrete outputs, a pulse train and, where needed, an analog reference. The MicroLogix 1500 has no servo motion instruction set, so the drive must close its own position loop, store its own target positions, and accept a start, a point number or a pulse train. Drives with a point table and binary select inputs handle preset positions; the onboard pulse outputs handle the one axis that needs fine control; servo platforms that need a Logix motion controller as master do not fit. Below: the interface rules, the arithmetic for the pulse-train axis, and the decision for each case on your machine.

What the MicroLogix 1500 puts on a drive #

Your controller's role in this retrofit is selection and trigger, not trajectory. The MicroLogix 1500 has no servo motion instruction set: no motion groups, no gearing, no camming, no interpolated moves, and no servo module was ever offered for the platform. It was bought for relay logic and counting, and that is exactly the job it keeps.

The interfaces it does have, straight from the MicroLogix 1500 user manual: two onboard high-speed outputs, configurable either as 20 kHz pulse-train output or as PWM, and two onboard high-speed counters rated at 20 kHz. In the Compact I/O bank, the 1769-HSC high-speed counter module accepts counter and encoder inputs up to 1 MHz and carries onboard 5–30 V DC sourcing outputs designed for high-speed control duties.

So the deciding line in any servo amplifier datasheet is its command interface. If the amplifier can hold preset targets in its own memory and take a start from an output, or take a pulse train plus direction and close its own position loop, the retrofit works. If it needs a motion-capable Logix controller as its master, it does not.

The command interfaces that fit #

Point table selected by binary outputs #

This is the primary fit. Amplifiers built for this retrofit store up to 128 preset points in the drive itself, and you rewrite those values through the amplifier's own setup tools when the job changes. The PLC never sends a position at run time; it sends a point number.

Each select output doubles the reachable count: with n select bits, the drive addresses 2^n point numbers, so seven bits reach 2^7 = 128. That costs seven spare discrete outputs for selection, one output for start, one for enable, and two inputs back — in-position and alarm.

Hold each new selection for at least one full controller scan before the start output pulses, so the select bits are already stable when the amplifier reads them, and leave the selection unchanged until the in-position input closes. The move itself runs on the drive's own acceleration and deceleration settings; the scan rate shapes nothing but the start.

Pulse train and direction #

For the axis that needs arbitrary positions — setup moves, sizing cuts — generate a pulse train on one onboard high-speed output and a direction level on a second discrete output. The amplifier counts the pulses against its own closed loop and lands the axis on target; the controller's job ends when the pulse stream stops. The hard limit is the controller's rated pulse-output frequency, and the example below turns that rating into a rev/min ceiling for your axis. Match the amplifier's pulse input type — line driver, open collector, sink or source — to the output driving it, and interpose a circuit wherever the two disagree; that costs less than a dead output stage.

Analog reference for a speed axis #

An axis that only needs speed — a variable spindle, a dial-fed slide — fits an amplifier that takes an analog velocity reference. An analog output module in the Compact I/O bank supplies the reference, and the amplifier scales and ramps it internally. Reserve this interface for speed control: preset positioning over an analog reference is the weakest fit on this controller, because every motion decision lands back on a processor with no motion instructions.

The interfaces that do not fit #

Servo platforms that command their drives over a motion network are out on this controller, in two forms. SERCOS-ring servo amplifiers take their motion from the controller on the ring, and the ring master is a motion-capable Logix controller. Servo drives commanded only through CIP Motion on EtherNet/IP are the same story: the motion planner lives in the Logix processor, and the MicroLogix 1500 has neither the instruction set nor the network role to run it. That is the same divide described in why a Kinetix 5500 needs a motion-capable Logix controller: a servo platform does not become usable by wiring its network onto a controller that cannot plan motion.

The rule that follows: if an amplifier cannot reach a commanded position from discrete outputs plus a pulse train, it cannot serve this retrofit, whatever its datasheet says about connectivity.

Example: how fast does one pulse-train axis turn? #

Inputs, with their sources:

  • Pulse-output ceiling: 20,000 pulses per second — the onboard pulse-train output rating documented in the MicroLogix 1500 user manual.
  • Command resolution: 10,000 pulses per motor revolution — an example electronic-gear setting chosen for this calculation, not a universal value; read the real figure from the amplifier's electronic gear parameters.

The rule in words: axis speed in rev/min equals the pulse rate in pulses per second, divided by the command resolution in pulses per revolution, multiplied by 60 seconds per minute.

The arithmetic: 20,000 pulses per second ÷ 10,000 pulses per revolution = 2 rev/s. Then 2 rev/s × 60 s/min = 120 rev/min.

Result: at this resolution the axis tops out at one revolution every half second — a 120 rev/min ceiling.

The reusable threshold: pulse-interface ceiling in rev/min = 1,200,000 ÷ pulses per revolution, where 1,200,000 is the 20,000 pulses/s rating × 60 s/min. A feed axis that jogs at or under 120 rev/min fits the pulse interface at this resolution. A fine axis whose fastest move needs more than 1,200,000 divided by your pulses-per-revolution does not: coarsen the resolution if the machine's positioning accuracy allows, or make that axis a point-table axis with more stored points. Fine resolution and high speed together are the combination this platform cannot buy you — that axis is the controller-migration case in the last section.

Count the I/O before you order #

  1. Classify every axis first: preset, fine, or speed-controlled. The class fixes the interface and the point count.
  2. Per point-table axis: seven select outputs if the full point table must be reachable, one start output, one enable output; in-position and alarm back to two inputs.
  3. Per fine axis: one high-speed pulse output and one direction output — and the controller has exactly two high-speed outputs in total, so the fine-axis count is two at most.
  4. Reserve the onboard high-speed counters for scale and encoder feedback; add the 1769-HSC module when a scale feeds faster than they absorb — its inputs run to 1 MHz and its 5–30 V DC sourcing outputs handle fast control duties.
  5. Sum the discrete outputs across steps 2 and 3, check them against the controller's own output points plus expansion, and order any expansion with the drives.

Wiring, feedback and the one safety rule #

Bring each amplifier's in-position and alarm contacts back to discrete inputs, and wire the alarm contact normally closed so a broken wire reads as a drive alarm. If the enable handshake never closes and the drive sits unready, the fault shape repeats across brands — troubleshooting missing Drive Ready on a V60 axis retrofit walks that same fault on another retrofit.

Run pulse, direction, and scale or encoder lines in shielded cable, and land the shields where the amplifier manual's wiring diagram says. Keep those signal cables out of the tray that carries the drive power wiring.

Keep each drive's hardwired enable inside the machine's existing guard chain: your MicroLogix selects and starts motion, and its outputs are not a safety function.

Because every drive on this list closes its own position loop, tuning lives in the amplifier, and each axis tunes on its own numbers — why axis loop tuning differs between axes covers the spread you should expect between a light slide and a heavy one.

The decision, case by case #

Case on the machine Command interface Cabinet hardware per axis Verdict
Preset positions: tool stations, work offsets, die stops Drive point table 7 select outputs, start, enable; in-position and alarm inputs Fits — the default for this retrofit
One fine axis, arbitrary targets Pulse train and direction One high-speed output, one direction output, input type matched Fits under the pulse ceiling from the example
Speed-controlled axis: variable spindle, dial feed Analog velocity reference One analog output module Fits where the amplifier takes an analog reference
Coordinated or interpolated axes Motion network: SERCOS ring or CIP Motion A motion-capable Logix master Does not fit — change the controller first

Manual machine whose positions repeat from a fixed set: buy a point-table amplifier with binary select inputs, wire seven select bits so the whole stored table is reachable, and trigger each move with one start output. That one architecture covers tool stations, work offsets and stop positions.

One axis needs arbitrary fine positions: pulse train and direction from the onboard output, checked against the example's 120 rev/min ceiling at the resolution your accuracy demands — exceed it and the axis either coarsens its resolution or joins the point-table axes.

Two axes that must move together — contouring, threading, synchronized gantries: no amplifier choice fixes this, because what is missing is a motion master, not a drive. Migrate the relay logic to a current controller as described in migrating a MicroLogix 1500 machine to a current PLC, then choose the servo platform that controller can master.

A speed-controlled axis: analog output module into an amplifier with an analog velocity reference; nothing else in the retrofit changes.

Questions asked

Can the MicroLogix 1500 command more than two pulse-train axes?

Not on pulse trains: the controller has two onboard pulse outputs, and that is the pulse-train budget for the whole controller. A third positioning axis can still run on this platform if the drive holds its own point table, because point selection costs only spare discrete outputs, not pulse channels. Beyond about three positioning axes, or any axis needing coordinated motion, move the machine to a controller with a motion instruction set.

How many preset positions can seven select bits reach?

Binary select doubles the reachable count with every bit: seven bits give 2 to the 7th, which is 128 distinct point numbers, and six give 64. That is usually enough for a manual machine's work offsets and tool stations, and the points stay stored in the drive through power cycles, so the PLC only ever sends the selection and a start.

What sets the move time of a point-table axis?

The amplifier's own acceleration, deceleration and jerk parameters set how the axis moves; the controller scan only sets when the move starts. Expect the start to reach the drive within one or two scans of the start output, and treat the profile numbers in the drive as the tuning knobs for move time and settle. Nothing in the PLC shapes the motion between the start and the in-position input.

Is there a motion module that adds servo instructions to a MicroLogix 1500?

No. The MicroLogix 1500 platform has no motion instruction set and no servo module to add, which is why the drive must carry the positioning on every retrofit of this kind. If a job needs camming, gearing or interpolated axes, the fix is a controller change, not a module: migrate the logic to a current controller with motion support and keep the drives' command interfaces in mind when you do.

Keep reading

  • How-to

    Bridging a PLC-5/15 DH+ network to a Kinetix 300 servo drive

    Yes, a DH+-to-EtherNet/IP gateway exchanges command and feedback words between a PLC-5/15 and a Kinetix 300, but it only moves data: the drive must execute the motion profile locally. Replace the stepper controller, pulse expander, and encoder-counter functions with an eight-word map that carries a 32-bit position as two 16-bit words behind a data-valid handshake. If the machine needs trajectory points streamed per scan, migrate the controller instead of bridging it.

    Drives and motion

  • Troubleshooting

    Troubleshooting missing Drive Ready on a V60 axis retrofit

    S-rUn on the drive proves the enable reached it; it proves nothing about the return path. Hold the MC_Power enable TRUE for the whole test, then trace the drive-ready contact, its 24 V sense wiring, the PLC input channel and the tag mapping in that order. Local jog proves the motor and power stage, not the PLC interface.

    Drives and motion

  • Explainer

    Why ctrlX MOTION needs EtherCAT for third-party axes

    ctrlX MOTION addresses axes only as EtherCAT slaves through CoE (CiA 402) or SoE, so a PROFINET/PROFIBUS servo module like the Siemens F-TM cannot be declared as a native axis. Command it instead with CODESYS Fieldbus Communication plus CODESYS SoftMotion, which excludes the ctrlX MOTION feature set.

    Drives and motion