Why ctrlX MOTION needs EtherCAT for third-party axes

Drives and motion Published 7 min read

Short answer

ctrlX MOTION addresses axes only as EtherCAT slaves through CoE (CiA 402) or SoE, so a PROFINET/PROFIBUS servo module like the Siemens F-TM cannot be declared as a native axis. Command it instead with CODESYS Fieldbus Communication plus CODESYS SoftMotion, which excludes the ctrlX MOTION feature set.

On this page
  1. Can ctrlX MOTION control a servo drive that sits on PROFINET?
  2. Which drive protocols can I declare as ctrlX MOTION axes?
  3. How many drives can ctrlX MOTION synchronize at once?
  4. Why doesn't declaring the axis in the PLC create the drive connection?
  5. Can the PROFINET drive still be moved from the ctrlX controller?
  6. What do I check before committing a third-party EtherCAT drive?
  7. Which architecture do I choose for this machine?
  8. Questions asked

ctrlX MOTION connects drive axes only as EtherCAT slaves, and a third-party drive qualifies through CoE (the CiA 402 drive profile) or SoE. A Siemens F-TM servo module in an ET 200SP node communicates over PROFINET or PROFIBUS, so it cannot be declared as a native axis — no setting, axis declaration or kinematics assignment bridges that boundary. The documented alternative is PLC-based CODESYS Fieldbus Communication combined with CODESYS SoftMotion, which commands the axis but excludes the ctrlX MOTION feature set. Below are the protocol rule, the capacity number behind it, and the decision for each architecture.

Can ctrlX MOTION control a servo drive that sits on PROFINET? #

No — ctrlX MOTION addresses drive axes only as EtherCAT slaves, so a servo module on an ET 200SP node that speaks PROFINET or PROFIBUS, like the Siemens F-TM, cannot be declared as a native axis in the motion app. The boundary sits on the motion side, not the drive side. In the current documentation, the ctrlX MOTION drive interface is the EtherCAT slave: the motion app addresses axes through the real-time EtherCAT network and nothing else. The F-TM in this installation is a PROFINET or PROFIBUS node with no CoE or SoE interface, so both EtherCAT integration paths stop before they start — there is no slave to scan and no objects to configure.

Forcing it fails in two recognizable ways. Setting CoE or SoE options in the axis configuration does nothing, because the module does not expose them. Declaring the motor in the machine kinematics produces a geometric description of an axis the controller cannot command; the declaration is accepted, the drive never moves.

Which drive protocols can I declare as ctrlX MOTION axes? #

CoE, which carries the CiA 402 drive profile, and SoE, both over EtherCAT, are the supported interfaces for third-party drives; a profile name on the datasheet still leaves the drive's implementation to be tested before you commit. CoE carries the CiA 402 objects, including the mode-of-operation entry 0x6060 that tells the drive how to interpret each command — the same object covered in how CODESYS SoftMotion switches the CiA 402 mode of operation 0x6060. SoE is the second accepted servo profile on the same bus. Bosch Rexroth documents both paths for third-party drives and publishes how-to examples for connecting third-party CoE and SoE servos to a ctrlX CORE running the motion app.

The profile label is a necessary condition, not a guarantee. Rare drives interpret the standard in ways the motion app does not expect, and the vendor's guidance is that such drives need testing. Budget that test before the mechanical design is frozen, not after.

How many drives can ctrlX MOTION synchronize at once? #

250 drives synchronized in real time is the documented capability of ctrlX MOTION, and every one of them must be an EtherCAT slave; a PROFINET axis contributes zero to that count because the motion app cannot address it. The figure comes from the vendor's product description of the motion software and assumes the synchronization runs on the EtherCAT network under that app.

Illustrative sizing example: a machine carries 12 EtherCAT servo axes and 3 F-TM axes on its ET 200SP node.

  • Axes on the machine: 12 + 3 = 15
  • Axes ctrlX MOTION can address: 12 (the EtherCAT axes)
  • Capacity used: 12 of 250 drives, 12 ÷ 250 = 0.048, so 4.8 percent
  • Slots remaining: 250 − 12 = 238
  • PROFINET axes addressable: 3 × 0 = 0

The count never decides an integration like this one. Twelve axes sit under five percent of the documented ceiling, so capacity is nowhere near binding — membership in the EtherCAT slave set is the whole constraint, and each PROFINET axis contributes zero no matter how large the machine grows.

Why doesn't declaring the axis in the PLC create the drive connection? #

Because the declaration builds an axis object in the controller, while the commands, status and feedback still need a bus the motion app can drive; assigning the motor to machine kinematics describes geometry and never opens that channel. Keep four layers separate when you audit the design:

  • Motor and encoder: the electromechanics and the feedback. The absolute encoder reports position to the drive.
  • Drive: closes the motor loops and executes motion commands.
  • Fieldbus: carries commands and status between controller and drive.
  • Motion application: turns PLCopen blocks and kinematics into bus traffic, but only onto a bus it supports.

PLCopen motion blocks operate on the axis object the controller holds. If that object has no live command and status channel behind it, the blocks run against a shell. The F-TM's absolute encoder answers "where is the motor"; it does not answer "how do commands reach the drive", which is the question that decides this integration.

Can the PROFINET drive still be moved from the ctrlX controller? #

Yes, through PLC-based CODESYS Fieldbus Communication combined with CODESYS SoftMotion; that route commands the axis over its own bus but excludes the ctrlX MOTION feature set, so kinematics, robotics and CNC functions are off the table. On this route the drive keeps its PROFINET connection and is commanded by cyclic data through CODESYS Fieldbus Communication, the same class of mechanism used to control a PROFINET servo drive with cyclic telegram data. CODESYS SoftMotion supplies the PLCopen block layer above it, so the block-level goal from the original requirement survives here. The same SoftMotion core runs on other hosts as well, as in CODESYS SoftMotion over EtherCAT on a Raspberry Pi runtime; the block set does not depend on the controller it sits on.

Treat this as a different motion architecture, not a workaround that attaches the F-TM to ctrlX MOTION. Machine kinematics, the robotics functions and the CNC functions live in ctrlX MOTION, and none of them follow the axis onto the CODESYS route. Any coordinate transformation the machine needs on that axis becomes your IEC 61131-3 code.

What do I check before committing a third-party EtherCAT drive? #

The drive's EtherCAT device description, the CoE or SoE implementation it actually exposes, and a bench test that exchanges commands and feedback — those three decide whether a third-party axis goes in. Get the device description file from the drive vendor and let the engineering tool build the axis from the drive's own objects rather than a generic template. Read which CiA 402 or SoE objects the drive implements and how it behaves on enable, because that is where nonstandard interpretations show up. Then test before the design is locked: power the drive, enable it, jog it in both directions, run one programmed move and watch the feedback track the command. A concrete walk-through of that integration path on this site covers interfacing an EFC5610 drive with a ctrlX CORE over EtherCAT.

Which architecture do I choose for this machine? #

If the machine needs ctrlX MOTION functions, put every motion axis on EtherCAT with CoE or SoE; if the F-TM must stay, command it through CODESYS Fieldbus Communication and SoftMotion and design around the excluded features. The three cases:

Case 1 — the machine needs ctrlX MOTION functions. Gantry kinematics, coordinated multi-axis motion, robotics or CNC: select an EtherCAT drive with CoE or SoE for every motion axis, including the one currently on the F-TM. Replace or relocate that axis; do not split it across architectures.

Case 2 — the F-TM stays. Accept CODESYS Fieldbus Communication plus CODESYS SoftMotion for that axis, keep it out of any ctrlX MOTION kinematics, and write the transformation logic yourself. PLCopen blocks survive at the command level; the ctrlX MOTION feature set does not.

Case 3 — mixed machine. EtherCAT axes go to ctrlX MOTION, the F-TM axis runs on the CODESYS route, and the two exchange data as ordinary PLC variables, not as one motion coordinate system.

Record the bus, the drive protocol and the software components of each axis where maintenance can find them, so a future fault is read against the right architecture. If the F-TM is the fail-safe variant, its safety function stays engineered and validated in the safety controller it belongs to — neither motion architecture revalidates it.

Questions asked

Can I still program the axis with PLCopen function blocks on the CODESYS route?

Yes, at the block level. CODESYS SoftMotion implements the PLCopen motion blocks and issues them over the fieldbus connection you configure, so the block-level part of your goal survives. What does not survive is everything above it: machine kinematics, robotics and CNC functions are ctrlX MOTION features and stay excluded on this route.

Can I wire the motor's absolute encoder straight to the ctrlX controller instead?

No. The encoder reports position to its drive on the ET 200SP node; an axis also needs a command and status channel, and ctrlX MOTION addresses that channel only on EtherCAT with CoE or SoE. Moving the feedback wire creates no command path, so the deciding constraint remains the drive's bus.

Is the 250-drive figure a hard limit per controller?

Bosch Rexroth publishes it as a capability of the ctrlX MOTION software: up to 250 drives synchronized in real time. It is not broken down per CPU model, so treat it as the software's ceiling and keep large systems comfortably below it, confirming against the current product documentation when a count grows toward a couple of hundred axes.

Does a CiA 402 label on the drive guarantee it works?

No. The profile defines the objects, including mode of operation 0x6060, but implementations vary and rare drives interpret the standard in ways the motion app does not expect. The vendor's own guidance is that such drives need testing: enable, jog both directions, run one programmed move and watch the feedback before the design is committed.

Do the controller vendor's own drives use a different path?

No. ctrlX DRIVE units are documented as operating under an EtherCAT master, exchanging real-time and acyclic data over that network, so they sit on the same slave-side path as any third-party CoE drive. The difference is confidence: their implementation is known to the motion app, while a third-party drive's implementation is what your bench test establishes.

Keep reading

  • Troubleshooting

    Troubleshooting S7-1200 PROFINET servo motion control issues

    Fix an S7-1200 PROFINET servo project in order: compile the motion calls in FB1 first, set drive and TIA Portal to the same telegram — Telegram 3 on this pairing — then prove one axis holds enable and velocity through repeated scans. A first-generation CPU 1214C executes independent single-axis motion only; the flying shear's deterministic master-slave cut belongs in the drives or in a motion-class controller, and no telegram adds it.

    Drives and motion

  • How-to

    Bridging a PLC-5/15 DH+ network to a Kinetix 300 servo drive

    Yes, a DH+-to-EtherNet/IP gateway exchanges command and feedback words between a PLC-5/15 and a Kinetix 300, but it only moves data: the drive must execute the motion profile locally. Replace the stepper controller, pulse expander, and encoder-counter functions with an eight-word map that carries a 32-bit position as two 16-bit words behind a data-valid handshake. If the machine needs trajectory points streamed per scan, migrate the controller instead of bridging it.

    Drives and motion

  • Explainer

    CODESYS SoftMotion over EtherCAT on a Raspberry Pi runtime

    Yes: CODESYS Control for Raspberry Pi SL lists the CODESYS EtherCAT master and SoftMotion, so motion over EtherCAT is functionally supported. Its scheduler depends on Linux, so the runtime is not hard real-time as shipped; an RT preempt-patched kernel minimizes jitter. Budget the setpoint age your axis tolerates, measure worst-case jitter under full load, and accept the axis only when the measurement fits the budget.

    Drives and motion