Controllers and I/O Published 7 min read

Short answer

Pick the route by the module's bus interface, not its family name. XI3 analog modules belong on the ctrlX CORE EtherCAT master once the exact order code is released and its device description is installed; S20 modules belong behind the S20-EC-BK EtherCAT coupler, which carries up to 63 S20 devices — never the S20-ETH-BK, whose datasheet documents Modbus. Third-party Modbus TCP I/O reaches the CORE through the Modbus TCP app or a PLC-app CODESYS softstack.

On this page
  1. Which analog I/O route should you connect to a ctrlX CORE?
  2. Why is the XI3 analog module missing from "Add device..."?
  3. How do S20 analog modules connect to the EtherCAT master?
  4. Does the S20-ETH-BK coupler work on EtherCAT?
  5. How do you add third-party Modbus TCP analog I/O?
  6. How do you verify the route before ordering hardware?
  7. Which route do you order for each case?
  8. Questions asked

Pick the analog I/O route by the interface printed in the module's datasheet, never by the family name. On a ctrlX CORE that leaves three routes: ctrlX XI3 analog modules straight onto the EtherCAT master, an S20 station behind the S20-EC-BK EtherCAT bus coupler, and third-party Modbus TCP I/O carried by the Modbus TCP app or by a CODESYS softstack in the PLC app. The costly error is putting the S20-ETH-BK coupler on the EtherCAT path, because its datasheet documents Modbus. What follows is the decision for each route and the checks to finish before anything is ordered.

Which analog I/O route should you connect to a ctrlX CORE? #

Match the route to the interface printed in the module datasheet: XI3 modules go on the EtherCAT master, S20 modules go behind the S20-EC-BK coupler that carries up to 63 S20 devices, and any Modbus TCP device goes through the app or a PLC softstack.

The interface decides everything because the two buses do different work. An EtherCAT master reads each slave's device description and exchanges cyclic process data with it; a Modbus controller polls registers over a TCP connection. A module that speaks one protocol never appears in the other's configuration tree, so no amount of retyping in "Add device..." moves a Modbus coupler onto the EtherCAT master.

Analog I/O route Interface Where it is configured What must be true first
ctrlX XI3 analog modules EtherCAT slave on the CORE's master ctrlX I/O Engineering, "Add device..." under the EtherCAT master The exact order code is released for commissioning and its device description is installed
S20 station on the S20-EC-BK EtherCAT coupler linking up to 63 S20 devices ctrlX I/O Engineering, coupler added as the EtherCAT slave, S20 modules built onto it The coupler on the order is the S20-EC-BK, not the S20-ETH-BK
Third-party I/O via the Modbus TCP app Modbus TCP over Ethernet The app's own configuration, independent of the PLC app The app is currently released and supports your Modbus roles
Third-party I/O via the PLC app Modbus TCP over Ethernet, stack in the PLC project ctrlX PLC Engineering with CODESYS Fieldbus Communication The softstack or library covers the protocol and you hold the device's register map

Why is the XI3 analog module missing from "Add device..."? #

A missing entry means the module is not released for commissioning or its device description is not installed: the XI3 I/O family carried a not-yet-available status, with release planned for Q3 2022, when this question first came up, and a dated status is not today's status.

Two causes, one check each. First, release status: confirm the exact XI3 order code in the manufacturer's current lineup before planning around it, because a family can be announced while individual analog modules are still listed as not commissionable. Second, the installed catalog: the engineering environment only offers devices whose descriptions are present in that installation, so a module can be missing after an update gap. Update the engineering tools, then look for the exact order code again.

Do not substitute a similar-looking entry to get going. The master and the slave must run the matching device configuration, and a stand-in description produces process data of the wrong size or layout. Once the right module appears, the way its device description data lands in the project has its own quirks — read how ctrlX I/O Engineering maps device data into bits instead of byte-mapping nodes before wiring logic to offsets.

How do S20 analog modules connect to the EtherCAT master? #

Through the S20-EC-BK bus coupler: its datasheet defines it as the link between an EtherCAT network and the S20 system, carrying up to 63 S20 devices, so the coupler — not each I/O module — is the EtherCAT node.

Add the S20-EC-BK in ctrlX I/O Engineering as the EtherCAT slave under the CORE's master, the same workflow as routing an IO-Link master to a ctrlX CORE over EtherCAT, then build the S20 analog modules onto the coupler and assign their process data. The coupler datasheet lists a weight of 177 g with connector and bus base module and operation from -25 °C; read the upper ambient limit from the current datasheet issue before mounting it in a warm cabinet.

Illustrative sizing against the documented limit: a skid needs 30 analog channels, and the S20 analog input module chosen for this example has 4 channels. That is 30 ÷ 4 = 7.5, so 8 modules — seven full and one half-used. Eight modules occupy 8 of the 63 device positions, leaving 63 − 8 = 55 positions free, and the whole station still presents exactly one EtherCAT node to the master.

Does the S20-ETH-BK coupler work on EtherCAT? #

No. The S20-ETH-BK datasheet documents Modbus as its interface, so the ctrlX CORE EtherCAT master cannot scan or configure it, and ordering it for the EtherCAT path is the one design error this selection has to prevent.

The two couplers sit in the same S20 family, which is exactly why the trap exists: the family name tells you the I/O system, the datasheet interface line tells you the bus. If the S20-ETH-BK is already in a design, that design belongs to the Modbus route, and the next check is the transport: a datasheet that says "Modbus" has not yet said whether that is Modbus RTU on serial or Modbus TCP on Ethernet, and the two need different paths on the CORE.

How do you add third-party Modbus TCP analog I/O? #

Over Ethernet, with the protocol stack in one of two places: the Modbus TCP app, whose stated purpose is connecting the CORE to third-party devices over Modbus TCP independent of the PLC app, or CODESYS Fieldbus Communication running inside the PLC app.

The app route is the cleaner architecture when it is released for your market: configuration lives in the app and the data reaches your application from there. At introduction the app was described as not yet available for the general market — a dated statement, so confirm current availability and the supported Modbus roles before building on it. The PLC route needs no separate app: the CODESYS softstack or another capable library opens the connection from the PLC project, and the channels arrive as project variables you scale yourself.

Either way, the device side decides the workload: which side is the client, the register map, and the scaling of each channel. The mechanics of polling analog channels through a coupler are covered in running analog I/O over a Modbus TCP bus coupler, and the client side in setting up a CODESYS Modbus TCP client. Moving that data into the PLC project also changes the license number to check — see how the ctrlX PLC license calculates I/O data and core use.

How do you verify the route before ordering hardware? #

Read four things off paper, in this order: the exact module and coupler order codes, the interface line of each datasheet, the device-description presence in your installed engineering version, and the register map of any Modbus device.

  1. Write the exact order codes from the datasheets onto the order, coupler included, and check each against the manufacturer's current lineup.
  2. Read the interface line of every coupler and module: EtherCAT or Modbus, and for Modbus, RTU or TCP.
  3. Confirm the device description for each EtherCAT device is present in the installed version of the engineering tools; update the tools if an entry is absent.
  4. For Modbus devices, record which side is the client, the register addresses and data types of every analog channel, and the scaling into engineering units.
  5. Add the expected process data to your license check before the order leaves your desk.

None of these routes is a safety function: emergency stop and guard signals stay on the safety chain your risk assessment defined, not on an analog input module.

Which route do you order for each case? #

Order the S20-EC-BK station as the default EtherCAT path unless the exact XI3 order code is confirmed released and present in your device catalog; route every Modbus device through the PLC softstack, and move that to the Modbus TCP app only if it is currently released for your use case.

  • XI3 confirmed released and in the catalog: XI3 analog modules directly on the CORE's EtherCAT master — the shortest path, one engineering tool, no coupler.
  • XI3 not confirmed: S20 analog modules on the S20-EC-BK, sized against the 63-device limit — the documented EtherCAT route for S20 modules.
  • S20-ETH-BK already specified: keep it out of the EtherCAT tree, confirm its transport from the datasheet, and run it on the matching Modbus path.
  • Third-party Modbus TCP unit: CODESYS Fieldbus Communication in the PLC app now; the Modbus TCP app if its current release supports your roles and device count.

Questions asked

How many S20 modules fit behind one S20-EC-BK coupler?

Up to 63 S20 devices, per the coupler datasheet. The budget belongs to the coupler, so a station that outgrows it gets a second S20-EC-BK as its own EtherCAT slave on the same master rather than an extension of the first station. Each coupler then keeps its own 63-device limit and its own process image.

Is the S20-ETH-BK just the Ethernet version of the S20-EC-BK?

No — it is the Modbus member of the same family, and the similar names are exactly the trap. Check the order code character by character on the purchase order and again on the delivered coupler's label: an ETH where an EC belongs moves your station to the Modbus route, and no EtherCAT configuration will find it.

Does the Modbus TCP app replace the PLC app on the CORE?

No. The app was introduced to connect the CORE to third-party Modbus TCP devices independently of the PLC app, so the two can coexist. At introduction it was described as not yet available for the general market, so its current release status, its supported Modbus roles and its device limits are the three things to confirm in current documentation before choosing it over the PLC softstack.

Can I build and test the configuration on a virtual ctrlX CORE?

Yes for the project, no for commissioning. A virtual CORE lets you build the EtherCAT configuration and the PLC logic, and a documented offline import brings EtherCAT I/O real-time data into ctrlX PLC Engineering without a connected CORE, so logic can be written against realistic data. The physical coupler and modules are still needed to commission the station.

Do I need a bigger ctrlX PLC license for the added analog I/O?

Check it, because the ctrlX PLC license is calculated against the I/O data your application uses, along with core use. An S20 station's process image and a Modbus softstack's data both count toward that number once they land in the PLC project, so size the station first, then compare the total against your license before the modules arrive.

Keep reading

  • Selection guide

    Add 4-20 mA analog inputs when the CompactLogix rack is full

    Swap the installed four-channel analog input card for an eight-channel one when channel isolation matches; that adds four inputs against a need of three, with no rack, power-supply or enclosure change. If isolation rules the swap out, reposition the existing power supply to free an end slot. When the cabinet itself is full, add a POINT I/O analog module or IO-Link converters over EtherNet/IP.

    Controllers and I/O

  • How-to

    How to run analog I/O over a Modbus TCP bus coupler

    Yes: remote analog I/O behind a Modbus TCP bus coupler can close a control loop from the PLC. Prove the electrical path with the network out of the loop, bring up the connection with a real timeout, map and scale the channels against known test points, then close the loop on measured timing — one documented integration refreshes coupler data every 10 ms, but the valve and hydraulics set the real response, and a failed exchange is a fault state, never fresh data.

    Controllers and I/O

  • Selection guide

    Selecting multi-channel Modbus analog input remote I/O

    Sixteen 4-20 mA loops become Modbus data through remote I/O with current-rated analog inputs, never through a serial converter. Match input type and loop power first, then channel count — one 16-channel single-ended module or two 8-channel differential modules — and buy only against the manufacturer's register map.