S7-300 to S7-1500 PUT/GET links during panel migration
Short answer
Yes. An S7-300 in STEP 7 and an S7-1500 in TIA Portal exchange data during a one-panel-at-a-time migration: configure an S7 connection, start PUT/GET in the S7-300 program, permit it in the S7-1500's protection settings, and give the exchange one mapped interface DB. The shared Profibus cable alone proves nothing about CPU-to-CPU data.
On this page
- What the engineering tools decide
- Read the existing Profibus link first
- Start PUT/GET on the S7-300 side
- Permit the partner on the S7-1500
- Pick the physical path for the transition
- Worked example: sizing the interface DB for a four-module S7-300 rack
- Commission one direction at a time
- One writer per byte
- Questions asked
Yes, the two can talk. An S7-300 that you still program in STEP 7 and an S7-1500 programmed in TIA Portal exchange data over a configured S7 connection while panels migrate one at a time. Two conditions decide whether it works: the PUT/GET operation starts on the S7-300 side, and the S7-1500's access protection permits PUT/GET from a remote partner. The Profibus cable the panels already share does not prove any of this; it usually carries cyclic I/O between a master and slaves, not CPU-to-CPU data.
What the engineering tools decide #
STEP 7 and TIA Portal are programming environments; neither one sets what the plant network carries. Keep three layers apart when you assess a mixed-generation floor:
- Physical path: Profibus, PROFINET, MPI, or an adapter that bridges one to the other.
- Transfer method: S7 PUT/GET, open TCP communication, or the existing cyclic I/O exchange.
- Data contract: which controller owns each value, which bytes and bits carry it, and who reads versus who writes.
A panel being a STEP 7 project and the next panel being a TIA project says nothing about their ability to exchange data; a configured connection between the CPUs does. Moving the program itself out of STEP 7 is a separate job, covered in migrating S7-300 projects from STEP 7 v5.5 to TIA Portal; here the old CPU stays in STEP 7 and a bridge carries the data until its own swap comes.
Read the existing Profibus link first #
Before you promise a bridge, record what the current link actually is. Open each panel's hardware configuration and program and note three things: the network type each CPU sits on, the node role (master, slave, or neither), and the blocks that carry data between panels.
The answer picks your branch. Panels configured as Profibus slaves under a common master tend to transition cleanly, because the cyclic I/O arrangement keeps working until that panel's own swap. Panels that reach each other only over MPI need new interface hardware before any CPU-to-CPU transfer is possible. And a panel whose Profibus link turns out to carry only slave I/O proves nothing yet about a data bridge — do not treat "the panels use Profibus" as evidence of CPU-to-CPU communication.
Start PUT/GET on the S7-300 side #
PUT and GET exchange data between two CPUs over an S7 connection: PUT writes data to the partner CPU, GET reads data from it. The CPU that executes the instruction is the initiator; it reaches into the partner's memory, not the other way round.
That direction matters on a mixed-generation floor. The reported field experience with this exact pair is consistent: GET and PUT called in the S7-300 program, over a PROFINET connection to the S7-1500, work — while attempting the same transfer initiated from the S7-1500 side failed on the same hardware. Plan the S7-300 as the initiator and commission each direction you need on its own, as described below. A stall on a different CPU pair, covered in why S7-400 to S7-1500 PUT/GET over PROFIBUS stalls, is a separate failure mode; do not import its diagnosis here.
Permit the partner on the S7-1500 #
The S7-1500's access protection can refuse PUT/GET from any remote partner, and by default that refusal stands until you change it. In the CPU's Protection & Security properties, permit access with PUT/GET communication. On newer S7-1500 firmware that right is granted through the project's security settings, in the users and roles configuration, so the connecting role must carry the communication privilege.
This switch is per CPU and per project. A setting that worked on the last migrated panel proves nothing about the next one; check it on every S7-1500 before the S7-300's first transfer attempt.
Pick the physical path for the transition #
For the bridge itself, three paths cover the cases you will meet:
- The S7-300 already has an Ethernet communication processor such as a CP343-1. Configure the S7 connection in TIA Portal against it; doing this on the TIA side is the reported easier route, and it keeps the legacy project untouched.
- The S7-300 is a Profibus slave. Keep the cyclic I/O arrangement until that panel's own swap; no bridge is needed yet for values that already move as I/O.
- The S7-300 has only MPI. Add an MPI-to-Ethernet adapter as a temporary bridge, or fit a communication processor, because MPI alone gives you no Ethernet path to the S7-1500.
If the transition also means converting the panel network from Profibus to PROFINET, the hardware-side decisions live in converting PROFIBUS to PROFINET on an S7-300 retrofit; treat that conversion and this data bridge as two separate tasks with separate tests.
Worked example: sizing the interface DB for a four-module S7-300 rack #
Take one legacy panel as an example configuration: rack 0 with two 16-channel digital input modules in slots 4 and 5, each occupying two input bytes (IB0 to IB1 and IB2 to IB3), and two 16-channel digital output modules in slots 6 and 7, each occupying two output bytes (QB0 to QB1 and QB2 to QB3). Read the real addresses from your hardware configuration before you use them.
The rule: the interface DB on the S7-1500 is one byte array, one array index per legacy I/O byte, with the index equal to the byte offset. The array length equals the input bytes plus the output bytes you map.
The arithmetic:
- Input bytes: 2 + 2 = 4
- Output bytes: 2 + 2 = 4
- Transfer window: 4 + 4 = 8 bytes
So the interface DB carries an array of eight bytes. Index 0 through 3 hold IB0 through IB3, and index 4 through 7 hold QB0 through QB3. The initiating side addresses the same eight bytes in the S7-300 as one contiguous area covering the four input bytes and, in a second transfer, the four output bytes — keep reads and writes as separate operations so a fault in one cannot corrupt the other.
The decision: size the array to the byte count of the rack you are mapping — eight here. When a later panel swap adds a module, grow the array by that module's byte count before the cutover, and never let two signals share an index.
Commission one direction at a time #
For every exchange, write down four things before you power the logic with it: which CPU executes the instruction, which CPU is the partner, which memory area moves, and whether the operation is a read or a write. That record prevents the classic commissioning error — enabling one direction and expecting the other to work automatically.
Test with a byte that no machine logic uses. Perform the transfer, watch the test byte arrive on the partner, then change it and watch it propagate. If it fails, read the status of the initiating instruction and the partner's diagnostics rather than changing network settings at random: a wrong partner address, a missing permission, a mis-set DB number, and a direction mismatch all look like a silent value from the process side.
One writer per byte #
Map the exchange into a documented interface instead of letting both programs poke scattered addresses. The pattern that has worked in the field: one global DB on the S7-1500 as a byte array, the array index matching the legacy byte address, and the bit number inside the byte matching the legacy bit. Name each signal, its legacy source, its index and bit, its direction, and its owning controller — check byte order and data type on anything wider than one byte.
Then give every value exactly one writer. While the S7-300 program still runs, do not write into its output image from the new CPU: a running program and a PUT write fighting over the same output bytes will move real machine outputs. Take over an output only when the legacy logic that drives it is deactivated or switched over — the same cross-tool write discipline behind fixing the STEP 7 V5.5 warning after TIA Portal wrote an S7-300. One safety note to keep on the wall during every cutover: never enable a write direction into a live panel until you have proven, on the bench or in a stopped state, which program owns those bytes.
Run the migration this way and each panel swap is small: configure the connection, permit the partner, map the bytes, prove both directions, then move the logic one signal at a time.
Questions asked
What has to be switched on for an S7-1500 to accept PUT/GET?
In the S7-1500 CPU's Protection & Security properties, allow access with PUT/GET communication from remote partners. On newer S7-1500 firmware this right is granted through the project's security settings with users and roles, so give the connecting role the communication privilege. A configured S7 connection does not override this switch: with the permission off, the S7-300's PUT or GET is rejected.
Can the S7-1500 start the PUT/GET instead of the S7-300?
Both CPUs offer the instructions, but commission the direction you actually need and do not assume the other direction works because one does. Migrators report the S7-300-initiated setup working while an S7-1500-initiated attempt failed on comparable hardware, so plan the S7-300 as the initiator and prove each direction on your own CPUs before you trust either.
How do I test the link before it carries real signals?
Pick one byte that no logic uses on either CPU. Write a test pattern from the initiating side, read it on the partner, then pulse a single bit and confirm the change arrives within one scan cycle of your expectation. Run the read and the write direction separately. Only map real process signals after the test byte behaves in both directions.
Our panels talk over MPI, not Profibus. Does that change the plan?
The transfer method stays the same but the physical path does not. An S7-300 that only has MPI needs an MPI-to-Ethernet adapter or a communication processor to reach the S7-1500 over Ethernet. Use the adapter as a temporary bridge during the transition, and give each panel native Ethernet the day its CPU swap comes, so the adapters do not become permanent infrastructure.