How-to
Reading DH+ global status words into ControlLogix
Short answer
The 1756-DHRIO does not expose DH+ Global Status Words to ControlLogix and no generic CIP message can fetch them. Replace them with explicit MSG reads of the integer registers the PLC-5 or SLC program already writes, one request in flight per node, and budget one channel connection per controller-to-node pair against the 32 a DH+ channel supports.

On this page
- Does the 1756-DHRIO support DH+ global status words in ControlLogix?
- Why do the active-node diagnostics work when the status words never arrive?
- Which PLC-5 or SLC registers do you read instead?
- How do you configure the MSG reads?
- Should each controller read the legacy nodes or should one collector serve an array?
- What update rate can you expect and when is data stale?
- How do you verify the replacement before the cutover?
- Questions asked
The 1756-DHRIO does not deliver DH+ Global Status Words to ControlLogix, and no generic CIP message will fetch them: the module's DH+ channel carries explicit messages and active-node diagnostics, and its documentation defines no Global Status Word object or service to address. The replacement is a set of MSG reads from the source registers the legacy program already writes, one request in flight at a time, with a valid flag per node. This article gives the procedure, the connection budget of 32 per DH+ channel, and a worked line example with the direct-read versus collector decision.
Does the 1756-DHRIO support DH+ global status words in ControlLogix? #
No: the 1756-DHRIO's DH+ channel carries explicit messages and reports active nodes, and no revision of its documentation defines a Global Status Word object, service or tag, so there is nothing for a ControlLogix controller to read or subscribe to.
The Global Status Word exchange belongs to the legacy DH+ data-sharing model: every station broadcasts its status to every other station as part of normal token traffic, with no request and no reply. The DHRIO bridges that network into CIP for explicit messaging only, so a value the PLC-5 logic puts into its Global Status Word never becomes a ControlLogix tag. Changing routes, rescanning the channel or editing module configuration cannot create a service the documentation does not define, and a guessed generic CIP class, instance or service returns an error or data you cannot trust. The fix is in the program design, not the module.
If your status words ride ControlNet through the 1756-DH bridge instead of a DHRIO DH+ channel, the gap is the same but the replacement path differs; that case is covered in replacing the DH+ Global Status Word on ControlNet.
Why do the active-node diagnostics work when the status words never arrive? #
Active-node data answers who is present and a message read answers what value sits at an address, while the Global Status Word exchange is a third function the module does not perform, so node visibility proves the channel and nothing more.
The DH+/Remote I/O interface module manual, publication 1756-UM514C-EN-P, describes the DH+ message as carrying only a node ID for a node on the network: you address one node, request an address range, and get that data back. Discovery lists which stations answered the token; it never carries application data. That is why the channel can show every node active while your status tags sit at zero. It also tells you where you stand: if ordinary MSG traffic already crosses the channel, the transport is proven and the only missing piece is the replacement reads.
Which PLC-5 or SLC registers do you read instead? #
Read the integer the legacy rung writes just before it moves the value into its Global Status Word; that register almost always exists already, and when it does not you add one rung that copies the value into a readable integer block.
Work through the legacy program with its offline files and record, for every status word the migrated lines consume:
- the producing controller and the rung that calculates or moves the value;
- the source register and its bit meanings, including any inverted bits;
- the update condition and every consumer of the word.
If a value exists only inside the status exchange, you must edit the legacy program, which takes the family's programming software; which programming software each legacy PLC family needs names it per family. Where a PLC-5 already exchanges data by MSG, its control block is a 5-word integer file and the data file holds the transferred values; the PLC-5 quick reference, publication 1785-QR001, shows the pattern with a control block at N10:100 and data at N10:110, and such blocks are often ready-made sources. Copy every word that describes one machine state into a single contiguous block in one scan, because a read that straddles two updates can mix old and new state. Check the register online by watching normal state changes; do not force outputs to fake a machine condition.
How do you configure the MSG reads? #
Configure one MSG read per node for a contiguous integer block, trigger it only when the previous request has completed or errored, and keep exactly one request in flight per node so the channel never queues behind itself.
- Create a destination tag per node: an INT array sized to the block, for example 8 INTs for a block the legacy program writes at N12:20 through N12:27.
- Configure the message as a read of the destination's integer file with the element count set to the block length, using the read type the destination family's documentation specifies; how to configure ControlLogix MSG reads and writes to a PLC-5 covers the PLC-5 case in detail.
- Build the path: the controller, the DHRIO in its chassis, the DH+ channel, then the node address. Per the installation instructions 1756-IN070B-EN-P, a DH+ channel also needs its node address switches set. The module routes a message through up to four communication networks and three chassis (1756-UM543); this route uses two networks and one chassis. The path format is shown in how to route a ControlLogix MSG to a PLC-5 over DH+.
- Write the trigger rung so the request sets only when the previous run finished or errored; a message retriggered every scan piles up requests and lengthens every other node's update.
- Stagger the nodes: chain them so each read launches when the previous node's completes, or offset them on timers; simultaneous launches compete for the same token.
- Wire the message's done and error status into the per-node valid flag described under verification.
Should each controller read the legacy nodes or should one collector serve an array? #
Budget one channel connection per controller-and-node pair against the documented limit of 32 connections per DH+ channel (1756-UM514C-EN-P): controllers times nodes inside that limit means direct reads, past it means one collector controller reads an array the others consume.
Messages from one controller to the same node share that node's connection; each new controller-and-node pair holds one more. Worked example, with every input an illustration you replace with your own line: six legacy nodes (four PLC-5 processors, two SLC 5/04 processors) on one DHRIO channel, three ControlLogix controllers, and each node exposing one contiguous block of eight words.
- Direct reads: 3 controllers × 6 nodes = 18 connections, 14 spare under the limit, and 18 MSG instructions to maintain.
- Collector: 1 controller × 6 nodes = 6 connections; the collector's array is 6 nodes × 8 words = 48 INT, and the other two controllers read that array over EtherNet/IP using no DH+ connections.
- Boundary: 6 controllers × 6 nodes = 36 connections, past the limit, so at that size direct reads cannot fit on one channel and the collector is mandatory.
| Direct reads | Collector array | |
|---|---|---|
| DH+ channel connections | 18 | 6 |
| MSG instructions to maintain | 18 | 6, plus two array reads |
| Failure dependency | each controller on its own messages | every controller on the collector |
| Load on each legacy node | answers three controllers | answers one controller |
Decision for this line: direct reads, because the pair count fits with margin and no single controller becomes the data choke point. Move to the collector when the pair count passes the limit, when the channel already carries heavy traffic, or when the legacy processors are slow and should answer one requester.
What update rate can you expect and when is data stale? #
An explicit read refreshes only when its message completes, so the honest number is your measured round trip: at an example 60 ms per eight-word read, a six-node sweep run one request in flight completes in 360 ms.
The arithmetic: 6 reads × 60 ms = 360 ms per sweep. The legacy exchange repeated with the token without any request, so do not promise the old freshness; schedule it and measure it. Set the stale limit at three sweeps: 3 × 360 ms = 1080 ms, rounded up to a 1.5 s timer, and mark a node invalid when its data is older than that. The 60 ms is an example input: replace it with your own measurement taken during normal traffic and again with every other message on the channel running. If the sweep stretches past what the process needs, cut block sizes, stagger further apart, or move to the collector and accept one shared refresh for all controllers.
How do you verify the replacement before the cutover? #
Verify meaning and failure behavior end to end: each source register must follow its machine state, each destination tag must match bit for bit, and each consumer must reject data the moment a node stops answering.
- Watch the source register in the legacy program while the machine changes state normally, and confirm the value tracks the intended logic.
- Compare the ControlLogix destination against the source bit for bit using your documented bit map. An inverted faulted bit displays as healthy, which is the dangerous failure; treat migrated status bits as display and interlock data, never as a safety function.
- Measure the per-node update interval during normal traffic and again with the channel busy.
- Under an approved test procedure, disconnect one node's DH+ tap; confirm the message errors, the valid flag drops, and consumers show bad quality instead of the last value.
- Reconnect and confirm automatic recovery: the next request completes, the valid flag sets, and no duplicate or latched triggers appear.
The decisions, in one place: the DHRIO path is explicit MSG reads, never a status word service or a guessed CIP object. Direct reads when controllers times nodes fits the channel connection limit with margin; a collector array when it does not or the channel is already loaded. One request in flight per node, one valid flag per node, and a stale limit at three measured sweeps complete the design.
Questions asked
Can a produced or consumed tag carry the data through the 1756-DHRIO?
No. Produced and consumed tags are implicit CIP connections, and the DH+ side of the module carries explicit messages only, so the legacy nodes cannot produce or consume anything. Run the collector's produced tag between the ControlLogix controllers over EtherNet/IP, and keep the DH+ side to plain MSG reads.
What happens to the last reading when a legacy node stops answering?
The destination tag keeps its last value indefinitely; nothing in the message instruction clears it. The message's error status tells you the transfer failed, so your per-node valid flag must clear on any error or on the stale timer expiring, and set again only after a fresh completion. Without that flag, an operator sees a frozen machine state presented as live data.
Is the 1756-DHRIOXT any different for global status words?
No. The routing documentation names the 1756-DHRIO and the 1756-DHRIOXT together with the same limits, and both run the same messaging services, so the global status word gap and the MSG replacement are identical. Choose between them on the installation environment, not on protocol features.
What if a status word changes faster than the read sweep?
An explicit read can miss a state shorter than its sweep: a word that toggles and returns inside one refresh leaves no trace. Latch such events in the legacy program before the copy rung, or give that word its own faster-triggered read. Words that follow machine state normally change slowly, which is why one sweep usually suffices.