Monitoring sensors in Ignition without a PLC at each hub
Short answer
Yes. Ignition's built-in Modbus TCP driver can read Ethernet remote I/O or IO-Link masters directly, with no PLC at the hub; HTTP and MQTT are the alternatives. The binding limit is the update model: a polled snapshot tracks states that outlast one polling period and can miss shorter ones, so complete fault capture needs push-on-change MQTT, latching, or one aggregating PLC.
On this page
- What changes when there is no PLC at the hub
- Four acquisition paths compared
- Modbus TCP: the path to start with
- HTTP GET/POST and MQTT: pull and push alternatives
- Aggregating through one PLC: the OPC UA route
- The update-rate limit behind every polled path
- Example: can a 1 s poll catch a 400 ms fault pulse?
- Matching the path to each signal type
- Building the first hub
- The decision for your plant
- Questions asked
You can connect sensor hubs to Ignition without a PLC at any of them. Ignition's built-in Modbus TCP driver exists for exactly this job: it lets the OPC UA server talk to any device that speaks Modbus TCP, so an Ethernet remote I/O block or an IO-Link master with a Modbus TCP server becomes a hub Ignition reads directly. HTTP GET/POST and MQTT cover devices that offer no register map. The decision that actually matters is the acquisition layer's update model: a polled snapshot — including the planned one-second poll — reliably tracks states that outlast one polling period and can drop everything shorter. Short fault pulses need latching in the hub, push-on-change MQTT, or one aggregating PLC. This article compares the four paths, puts numbers on the polling limit, and ends with the choice for each signal in an eight-hub monitoring install.
What changes when there is no PLC at the hub #
A PLC scans its inputs every few milliseconds and holds state between scans. Remove it and the field device merely converts signals into network data: Ignition's poll then defines what the SCADA database ever gets to see, and a hub that is not being polled might as well be unpowered as far as the tags are concerned. That is why Modbus polling is not the same as remote I/O — a remote I/O drop under a controller updates on the fieldbus cycle whether the master asks or not.
Before changing hardware, separate acquisition failures from interpretation failures. A reachable hub can still deliver badly scaled values, stale values, or values that miss transitions entirely, and each failure has a different fix; isolating each control layer is what turns an ambiguous wrong value into a one-layer test — the method behind controls troubleshooting by isolating each layer. Then write the requirement in one line: a periodic status snapshot, or a complete event history? The eight-hub install this scenario assumes — one to four sensors per hub, so eight to thirty-two connections — mostly needs the snapshot; the faulted bit is the part that argues.
Four acquisition paths compared #
All four paths turn the same field wiring into Ignition tags. They differ in what the hub must provide, what you build on the Ignition side, and whether a fault pulse shorter than a polling period survives.
| Path | The hub must provide | Ignition-side work | Update model | Sub-second fault pulse |
|---|---|---|---|---|
| Modbus TCP | A Modbus TCP server and a documented register map | One device connection per hub, mapped addresses and data types | Polled snapshot | Can fall between polls |
| HTTP GET/POST | A configurable HTTP interface, set up in the vendor's web tool | Timer script or HTTP endpoint, JSON parsing, timeout and quality handling | Snapshot or push | Survives only if the device pushes on change |
| MQTT | A publisher, a broker, and an MQTT subscription on the Ignition side | Topic and payload mapping, session and staleness handling | Push on publish | Survives when the device publishes on change |
| One aggregating PLC | Masters on a fieldbus into a PLC serving OPC UA | OPC UA connection, browse or map tags | PLC scan plus subscription | Survives if the PLC logic latches it |
Modbus TCP: the path to start with #
This is the route with the least Ignition-side engineering, because the driver is built in and needs no scripting. Create one device connection per hub, point it at the hub's address, and map the registers: machine states as coils or discrete inputs, analog values as holding registers with the data type the manufacturer's map specifies. There is no device model to browse, so the register map is the whole contract — and an addressing-convention mismatch, zero-based versus one-based offsets, returns values that look plausible and read wrong, the failure behind why Ignition Modbus TCP tags read a Click PLC wrong. The check is cheap in effort: read the raw value, compare it against the sensor's local display or a meter, then apply scaling once, in one place.
Eight hubs at a one-second rate are a light load for the gateway — a transaction reading a few dozen registers completes in single-digit milliseconds on a healthy plant LAN, illustrative and dwarfed by the period — so the period you configure, not the network, decides what you capture. The floor on speed is the hub's embedded Modbus server, whose documentation states the minimum interval it tolerates.
Decision: use Modbus TCP when the register map carries every value you need and every tracked state outlasts the polling period.
HTTP GET/POST and MQTT: pull and push alternatives #
HTTP is a separate integration, not a driver setting. Some IO-Link masters ship an HTTP application configured in the vendor's web tool: the master serves JSON you fetch with GET, or posts it to a listener with POST. On the Ignition side you run a gateway timer script to pull, or a small listener to receive, then parse the payload and manage timeouts and tag quality yourself. The payoff is access to what a register map usually omits — device identification such as serial numbers, and sensor-specific structures. Define the layout once as a user-defined type per sensor model and every new sensor is an instance rather than a rewrite.
MQTT decouples publisher from consumer through a broker: the hub publishes to a topic, the broker relays, Ignition subscribes through its MQTT support. It is the only direct path here that can carry sub-second events, and only when the device publishes on change rather than on a timer. JSON defines the payload shape, not the whole contract — topic structure, field names, units, and connection status are yours to define and police, and the broker is one more service to keep running.
Decision: choose HTTP when the Modbus map lacks identification or structured sensor data. Choose MQTT when change events must survive and the device supports push-on-change. Both take more configuration than Modbus TCP.
Aggregating through one PLC: the OPC UA route #
The route that puts one small PLC somewhere central, the masters hanging off it, and Ignition reading the PLC trades hardware and programming for the best data fidelity. The PLC serves OPC UA, so Ignition browses typed variables instead of mapping registers by hand. Its program runs every scan, so a fault input can set a latched bit that holds until acknowledged — pulse capture bounded by scan time rather than the polling period, which is what the PLC scan cycle does in each pass. The fieldbus link also carries the masters' diagnostics, not just process values.
What it takes is controller logic, the master-to-PLC mapping, and one cabinet location with power — more engineering than the direct routes and one more component to maintain.
Decision: aggregate through one PLC when fault events must be complete, when you want OPC UA browsing, or when control may later live in that controller. For a pure snapshot install it is more machine than the job needs.
The update-rate limit behind every polled path #
A polled system samples; it does not watch. Capture is guaranteed only when a state outlasts one full polling period — at the planned rate, anything under 1,000 ms is at risk. A shorter state is caught roughly in proportion to its width divided by the period: a pulse half as long as the period is seen about half the time, because whether a poll lands inside it depends on where the pulse falls between polls.
End-to-end latency adds the transaction time and the OPC UA publish on top of the period; at the planned rate those are rounding errors. The limit belongs to the snapshot model itself, so periodically fetched HTTP shares it. Push-on-change MQTT removes it, and PLC latching removes it.
One boundary on all of this: the link is for monitoring. Anything that must stop a machine — interlocks, guarded stops, safety functions — stays in the controller and the safety hardware, never routed through a polled SCADA path.
Example: can a 1 s poll catch a 400 ms fault pulse? #
Scenario: eight hubs on Modbus TCP, each polled at T = 1,000 ms; one older machine whose fault contact closes for w = 400 ms before the condition clears, about 40 times per 8 h shift.
- Widths: w = 400 ms is shorter than T, so capture is not guaranteed — the pulse can open and close entirely between two polls.
- Expected catch fraction: w / T = 400 / 1,000 = 0.4, so about 40% of these pulses are seen.
- Over the shift: 40 fault events × 0.4 = 16 logged, and 40 − 16 = 24 lost. The dashboard shows a machine that faults less than half as often as it really does — 16 of 40.
- The long states are safe: running stretches of 30 s and waits of 12 s both exceed T, so every poll lands inside them and every transition is timestamped.
- Fixing it with rate: poll every 200 ms and w / T = 400 / 200 = 2, so the pulse spans at least one full period and is always sampled; the gateway side stays trivial at 8 hubs × 5 reads/s = 40 reads/s, while the hub's embedded server sets the real floor.
- Fixing it at the source: stretch or latch the fault in the hub if its channels support it, or route that machine through the aggregating PLC — then the count is exact at any poll rate.
Decision from the example: the snapshot answers is-it-running-now and tracks motor load well; it cannot keep a complete 400 ms fault history.
Matching the path to each signal type #
Machine-status digits (24 V run, waiting, faulted): run and waiting outlast any sane polling period, so the Modbus TCP path tracks them as they are. The faulted bit is the only at-risk one — treat it with latching or stretching in the hub, MQTT push-on-change, or the PLC route.
Motor load from a current transducer on 0-10 V or 4-20 mA: choose hubs whose analog channels match the signal — verify per channel, because mixed cards exist — and scale once, from raw register to engineering units, checked against a meter. A trend at the polling rate suits load tracking; it will not characterize starting inrush or sub-second dips, which belong to a drive or power monitor, not to this layer.
Flow on 4-20 mA or IO-Link: analog channels as above, or an IO-Link port. IO-Link is the sensor-to-master link, so Ignition always talks to the master, never the sensor. The master's upstream data splits into cyclic process values and acyclic identification data — the same split what an EtherNet/IP IO-Link master exposes to your PLC describes — and identification is exactly what register maps omit, which is where the HTTP route earns its keep.
Hub checks before any protocol: input type per channel, analog modes, IO-Link port classes, supply budget for hubs plus sensors, and mounting that matches the environment — block-style housings for the floor, cabinet-mounted slice I/O where a cabinet already exists.
Building the first hub #
Build one hub — the hardest signal mix, not the easiest — before committing to eight:
- Create the device connection and confirm the hub answers.
- Read raw values and compare each against the sensor's local reading or a meter; correct addressing before touching scaling.
- Scale the analogs into engineering units in one place and label the tags with those units.
- Toggle a digital input by hand and record how long the change takes to appear in the tag; that measured latency plus the polling period is your worst-case awareness time.
- Leave it running for a shift and, if the hub keeps its own counters, reconcile them with what Ignition logged.
- Only then replicate: each new hub is a copy of the connection and its address map with a new address.
The decision for your plant #
- Snapshot monitoring of run and waiting states, motor load, and flow: Modbus TCP direct, using the built-in driver. No scripting, no broker, no PLC at the hub — done.
- Complete fault counts on machines with short pulses: order the fixes by added effort — latch or stretch in the hub if supported; MQTT push-on-change if the device offers it; otherwise one aggregating PLC with latch logic. Do not try to fix it by shaving the polling period to a fraction of the pulse width; the hub's server sets a floor, and the pulse still has to outlast the period to be guaranteed.
- OPC UA browsing with native diagnostics: the one-PLC route.
- Serial numbers and sensor-specific structures: HTTP alongside Modbus TCP on the same hub where the device offers both.
The deciding number is the shortest state you must never miss. If it outlasts the polling period, any path works and Modbus TCP is the simplest one. If it does not, that signal needs a latch or a push, whatever the rest of the plant uses.
Questions asked
Does each sensor hub need its own device connection in Ignition?
Yes. Each hub has its own IP address and register map, so each one is a separate device connection in the Ignition gateway with its own polling schedule. Define a user-defined type per hub model so a new hub is a copy-and-rebind exercise rather than a rebuild, and keep a written register map per device model, because a replacement hub from a different series rarely keeps the same layout.
Can Ignition read IO-Link sensors directly?
No. IO-Link is the point-to-point link between a sensor and its master, so the SCADA side always speaks an Ethernet protocol to the master. What you configure is the master's upstream interface — its Modbus TCP server, its HTTP application, or its MQTT publisher — plus the process values and diagnostics it exposes there. Check the master's documentation for how identification data such as serial numbers is exposed before promising it in Ignition.
How fast should the hubs be polled?
Work backward from the shortest state you must catch: capture is guaranteed only when the state outlasts one full polling period, and shorter pulses are caught roughly in proportion to their width divided by the period. Set the rate from that requirement, then verify the hub tolerates it — the embedded Modbus server in a field device, not the network, is usually what sets the floor.
Will Modbus TCP give the OPC UA browsing I wanted?
No. The OPC UA server lives in Ignition, and the Modbus TCP driver has no device model to browse, so you enter addresses and data types by hand for every hub. Browsing comes only from an intelligent endpoint that serves OPC UA itself — the main reason to aggregate the masters through one small PLC and read its server, where the hub data appears as typed, browsable variables.
How do I tell a stopped machine from a hub that dropped off the network?
Watch tag quality, not values. When the device connection times out, Ignition flags the affected tags as bad quality, so alarm on that transition and the dashboard separates machine idle from no data. For hubs that keep answering but stop changing, poll a diagnostic or heartbeat register and alarm when it freezes — after checking the hub's documentation for which diagnostic registers it really provides.