Matching PLC software versions to controller firmware revisions

PLC programming Published 7 min read By IMDHMI controls team

Short answer

Install one Logix Designer release per controller firmware major revision: v24, v30 and v33 need three installs, the latest minor of a major covers every controller with that major, and only one minor per major can sit on one PC. Download the newest minor of each major, run the part 1 stub once with every archive volume in one folder, then run Setup from the extracted directory.

On this page
  1. Count installs by major revision, not by controller
  2. Inventory every controller before you download anything
  3. What the five-part download really is
  4. Extract and install one release
  5. Worked example: three majors on one laptop
  6. Multiple installs or a flash to one major
  7. Questions asked

Count firmware major revisions, not controllers. A fleet of ControlLogix and CompactLogix controllers running 24.02, 30.02 and 33.04 needs three installs of Studio 5000 Logix Designer, one per major, because this software does not program across major revisions. One install per minor is neither needed nor possible: the latest minor of a major covers every controller that carries that major, and only one minor per major can be installed on a PC at all. Download the newest minor of each major in the fleet, unpack each release by running the part 1 executable once with every part in the same folder, and run Setup from the extracted directory. The steps below cover the inventory that finds the revisions you have not met yet, the extraction that the five-part download actually requires, and the disk arithmetic for the whole job.

Count installs by major revision, not by controller #

Each controller carries a major firmware revision, the 24, the 30 or the 33 in 24.02, 30.02 and 33.04. Only the Logix Designer release with the matching major can download to that controller and go online with it. A newer install does not cover older majors: v34 talks to controllers flashed to v34, not to the 30.02 unit beside them.

Different majors install side by side on one PC, which is exactly how a mixed fleet gets supported. Within a major the rule tightens and relaxes at once: only one minor per major can be installed, so v30.01 and v30.02 cannot coexist, and neither is needed, because the latest minor of a major works with any controller carrying that major regardless of the controller's own minor. A 30.01 controller and a 30.02 controller are both served by the newest v30 release.

One exception to memorize: major revision 21. The latest-minor rule does not hold there, so pull any v21 controller out of the set and pick its minor from the compatibility listing for that specific controller.

Version matching cuts both ways. A specific controller can also pin you to specific software, which is what the piece on why only Studio 5000 programs a ControlLogix 5571 shows for one controller nothing else can program.

Inventory every controller before you download anything #

The revision list you have is probably short, and every major discovered late costs a second multi-gigabyte download. Finish the inventory first:

  • Browse to each controller in RSLinx Classic, or go online with it, and read the revision from the controller itself. The revision a brand-new project displays follows the software that created that project, not the connected controller's firmware, so trust the module rather than the empty project.
  • Open the newest project file for each machine and note the revision it targets as a cross-check.
  • Record the catalog number beside each revision; you need both if a firmware upgrade is ever on the table.
  • Reduce the list to unique majors: 24.02 and 33.04 give v24 and v33.
  • For each major, take the newest minor listed for it in Rockwell Automation's Product Compatibility and Download Center, which maps each firmware revision to the software version that supports it. Do not chase a controller's exact minor.

That center lists versions product by product. When a large fleet makes the lookup tedious, the piece on looking up the latest device version with your own version comparer shows how to run that comparison across many devices in one pass.

What the five-part download really is #

The items named Part 1 through Part 5 are not folders. One release ships as a single compressed archive split into a self-extracting RAR set: 30.02.02-Studio5000-Web.part1.exe is the extractor stub, and 30.02.02-Studio5000-Web.part2.rar through 30.02.02-Studio5000-Web.part5.rar are the data volumes it reads in order. The split exists so a dropped connection costs one volume rather than the whole release, and so the pieces pass through download managers and file servers that struggle with single huge files. Other releases split into a different number of volumes; the pattern stays the same.

Before touching anything, make Windows show extensions: in File Explorer, open the View menu and turn on File name extensions, which on Windows 11 sits under View, then Show. Hidden extensions are the reason the set looks like one folder plus four mystery items.

What you see What it actually is What you do
Five items labeled Part 1 through Part 5 that look like folders Archive volumes with the extensions hidden Show extensions and confirm the part1.exe plus .rar pattern
A small Setup application of about 3,458 KB beside the parts A launcher stub, not the payload Let it run the extraction or run the part 1 stub directly; keep every part next to it
A prompt for the next volume, or a missing-volume error A part is incomplete, renamed or in a different directory Re-download that part and keep all parts in one directory under their original names
Extraction stops partway with a disk space error No room for the parts and the extracted tree at once Clear space and run the stub again

Extract and install one release #

  1. Download every part of one release into a single directory, straight from the download center. Never mix parts from different releases, even when the sizes look similar.
  2. If IT blocks multi-gigabyte downloads on the engineering laptop, fetch the set on a machine that is allowed and copy all the parts over together.
  3. With extensions visible, confirm you have the part1.exe stub and consecutive .rar volumes with no gaps.
  4. Compare the parts' sizes. A part far below its neighbors was cut off mid-download; delete and re-fetch it before anything else.
  5. Check that the drive holds room for the parts plus about the same again for the extracted tree.
  6. Run the stub, for this release 30.02.02-Studio5000-Web.part1.exe. Accept the destination, which defaults to C:\RA\Studio5000, and let it unpack parts 2 through 5 by itself. Do not double-click the .rar volumes.
  7. Open the extracted folder, for this release C:\RA\Studio5000\30.02.02-Studio5000-Web; the exact name can differ slightly between releases.
  8. Run Setup from that folder with administrator rights and finish the installer.
  9. Repeat the whole sequence for each remaining major, one release at a time, before you clear anything away.
  10. When setup finishes you can delete the extracted tree to recover disk; keep the archive parts on a share so a repair or reinstall never means another download.

Worked example: three majors on one laptop #

Take an example fleet of twelve controllers: four at 24.02, three at 30.02, one at 30.01 and five at 33.04. The unique majors are 24, 30 and 33, so the job needs three releases, not four and not twelve; the 30.01 unit folds into the v30 install. Download the newest minor of each: the latest v24, the latest v30 and the latest v33.

Disk arithmetic per release: five volumes of about 2 GB make 5 × 2 GB = 10 GB of parts. Three releases come to 3 × 10 GB = 30 GB of archive storage. Extraction holds one release's parts and its extracted tree at the same time, so the peak during a single install is 10 GB + 10 GB = 20 GB, plus the installed software's own footprint.

Decision: park all 30 GB of archives on a share, keep at least 20 GB clear on the laptop while each release installs, and run the three installs one at a time.

Multiple installs or a flash to one major #

The alternative to three installs is flashing every controller to one recent major, v34 in this example, and keeping a single install. Be exact about the mechanics: v34 software does not talk to a 30.02 or a 33.04 controller on its own. It covers them only after each controller's firmware is flashed to v34.

Path What it costs When it fits
Install one release per major Archive storage per major on a share, laptop disk, and choosing the right release at every connect Controllers that cannot stop, or hardware that cannot take newer firmware
Flash every controller to one major A planned outage per controller, the flash itself, converting each project to the new major, re-download and retest Sites with maintenance windows that want one install on the laptop

Flash firmware only from a safely stopped machine inside a planned outage, and retest the machine, its safety functions included, before it runs production again.

Decision: if any controller cannot stop or its hardware cannot take the target major, install one release per major, the latest v24, v30 and v33 in the example fleet, and let them coexist on the laptop. If every controller can take a maintenance window and supports the target major, flash the fleet to one major such as v34 and run a single install. Either way, several installs raise the licensing question, and the piece on which PLC software you actually need to buy covers what to acquire when a fleet needs more than one version.

Questions asked

Can a v33 install open a v30 project file?

It can open the file and convert it to v33, but the converted project only runs on a controller flashed to v33 firmware. Until that controller is upgraded, its project stays in v30 and only the v30 install works with it. Treat conversion as part of a planned firmware upgrade, not as a way to retire the older install.

How do I spot a download part that did not finish?

Compare file sizes with extensions visible. The volumes before the last one are each about 2 GB and nearly identical; the last one is smaller by design. A part that sits far below its neighbors was cut off mid-download. Delete it, fetch it again, and keep every part in one directory under its original name before you run the stub.

Does the installer need network access once the parts are down?

No. The extracted package carries everything setup needs, so the install itself runs offline. Network policy matters only while you download: a firewall or proxy that blocks multi-gigabyte files affects that step alone. If the engineering laptop cannot fetch them, download the full set on another machine and copy every part across together on a USB drive or share.

What should I do if the inventory turns up a v21 controller?

Handle it outside the latest-minor rule. Major revision 21 has a known issue, so the newest minor of v21 is not automatically the right choice. Take that controller's catalog number and revision to the compatibility listing and release notes for v21, pick the minor they call for, and download that one release separately from the others.

Keep reading

  • Explainer

    Which programming software each legacy PLC family needs

    No. RSLogix 5000 and Studio 5000 Logix Designer program only the Logix families: ControlLogix, CompactLogix and GuardLogix. A PLC-5 processor is programmed with RSLogix 5, and an SLC 500 (catalog series 1747) or MicroLogix (1763, 1764, 1766) processor is programmed with RSLogix 500; matching data types or shared instruction names does not change that.

    PLC programming

  • Selection guide

    Migrating a MicroLogix 1500 machine to a current PLC

    Quote CompactLogix as the baseline for the rebuild: Rockwell's migration reference gives the MicroLogix 1500 two documented destinations, MicroLogix 1400 or CompactLogix 5370 (L1/L2), and a low-volume machine rebuild does not justify the Micro850 route. Take the Micro850 only for high build volume, after the 11 uncovered inputs, serial Modbus, the drive interface and a trial CCW import are verified.

    PLC programming

  • How-to

    How to get RSLogix 500 through official channels

    Get RSLogix 500 or RSLogix Micro only from Rockwell Automation or an authorized distributor: sign in to the Product Compatibility and Download Center, download the release your controllers need, and activate it with a current license. File-sharing copies carry no entitlement and no verifiable signature, so they never reach a production workstation.

    PLC programming